Glossary
The words the app uses, each in a sentence, with the section that says more.
DOAS — dedicated outside-air system
A machine whose only job is the ventilation air: 100 % outside air, recovered against the exhaust, dried once at the door and delivered neutral, the rooms' sensible load carried by other machines. Kinds of systems → Recovery unit and DOAS.
What is a DOAS (dedicated outside-air system)?
A DOAS separates the two jobs an air handler usually does at once. The ventilation air — the outside air a building must bring in for its occupants — is treated by one machine sized for exactly that flow: recovered against the exhaust in a plate core or a wheel, dried once at the door (often with a wrap-around heat pipe so the drying needs no reheat), and delivered at a neutral temperature. The rooms' own sensible loads — people, lights, sun — are carried by other machines: fan coils, VRF, a rooftop, radiant panels.
The reason it pays is latent load. Outside air on a humid day carries most of a building's moisture, and a machine that only has to dry that stream can be small, run at a steady state and hold a dew point precisely; a mixed-air unit has to over-cool its whole supply to get the same moisture out, then reheat it. In a building simulation a DOAS is the machine you give priority on the rooms it serves, so it carries the latent load and the machine behind it only what is left.
SZVAV — single-zone variable air volume
A machine serving one room that holds a supply-air setpoint, resets it upward as the load falls and slows its fan, so the room gets less air rather than warmer air. How a machine is run → Constant volume and SZVAV.
What is SZVAV (single-zone variable air volume)?
A constant-volume unit meets a smaller load by making its supply air warmer: the fan runs flat out and the coil unloads. A single-zone VAV unit does the opposite first — it holds a cold supply-air setpoint and slows its fan, so the room gets less of the same cold air. Fan power falls with roughly the cube of the airflow, which is why ASHRAE 90.1 §6.4.3.10 requires it on larger single-zone units: the same room, the same comfort, a fraction of the fan energy.
The setpoint itself is reset as the load falls — up toward the room temperature — so at light loads the machine runs both slower and warmer, inside a band the designer sets. HVAC Builder's SZVAV strategy carries the setpoint, the reset ceiling and a fan floor; the controller lands the fan speed and the coil together every hour, and a fan declared with a static-pressure setpoint reads its part-load power off its own curve rather than the cube law.
VAV terminal box
A room's own damper on a shared cold deck, metering its air between a minimum and a maximum and reheating at the minimum. Multi-zone VAV and terminal boxes.
What is a VAV terminal box?
One air handler makes one cold deck — a supply at, say, 13 °C — and every room has its own box on that deck: a damper that meters the room's air between a minimum and a maximum, and usually a reheat coil. A room that needs cooling opens its damper; a room that needs nothing sits at its minimum and, if that minimum is still too much cold air, reheats it. The handler's fan runs at the sum of the boxes, and the deck temperature is reset from the box that needs it coldest.
The reheat is the cost of the arrangement — cold air made by the chiller and warmed again by a coil — and the box minimum is what sets it, which is why minimums matter more than any other number on a VAV floor. HVAC Builder models the boxes on the serve links of a building run: each room's box carries its own load at the deck temperature, the critical-zone reset follows 90.1 §6.5.3.5, and the reheat is booked room by room, electric or hot-water.
Economiser
The outside-air damper opened past its minimum on a cooling hour when the outside air is cooler, or carries less heat, than the return: free cooling. Economiser and outside air.
What is an economiser (airside free cooling)?
When the outside air is cooler than the return air, mixing more of it in cools the building for the price of the fan. An airside economiser is the outside-air damper opened past its minimum on those hours, under a changeover rule: a dry-bulb limit, or an enthalpy comparison in a humid climate where cool-looking air can carry more heat than the room's. ASHRAE 90.1 §6.5.1 requires one on most cooling systems above about 54 kW.
In a building simulation the damper is placed before any stage is judged, by solving the ventilation stage shut and open and interpolating to the supply the rooms need — mixing is exactly linear in damper position, so two solves are enough. Free cooling is a stage with no compressor in it, which is why a fan in AUTO keeps that stage after hours: a night purge is free, and dropping it once sent an empty telecom shelter's cooling to the compressor.
Waterside economiser
A plate exchanger between the cooling-tower loop and the chilled-water loop: when the tower makes water colder than the chilled-water return, the exchanger carries the load and the chiller idles — free cooling on the water side, the way the airside economiser is free cooling on the air side. A building run gives a plant with one a free cooling stage ahead of its chiller stage. See the plate exchanger.
What is a waterside economiser?
A plate heat exchanger between the cooling-tower loop and the chilled-water loop. When the tower makes water colder than the chilled-water return — a winter or a dry night — the exchanger carries the load and the chiller idles; in between, the integrated arrangement puts the plate ahead of the evaporator so it pre-cools the return and the chiller trims what is left. The changeover valves keep it out of circuit when the tower water is warmer, or it would heat the chilled return instead.
It earns its keep on loads that persist in cold weather — data halls, laboratories, process cooling — and less on buildings whose handlers already free-cool on outside air, since those take the load away exactly when the tower is cold. HVAC Builder's plate exchanger kind carries the rated point a datasheet prints and an economiser flag; a plant holding a leaving-water setpoint with one gets a free-cooling stage ahead of its chiller stage, cycling and staging its tower fans on leaving-water temperature.
Demand-controlled ventilation
The outside-air minimum following how full the rooms are, down to the per-area share and no further. Economiser and outside air.
What is demand-controlled ventilation (DCV)?
Ventilation rates in ASHRAE 62.1 have two parts: a per-person rate and a per-area rate. Demand-controlled ventilation lets the outside-air damper's minimum position follow how full the space is — a CO₂ sensor in practice, an occupancy fraction in a model — so an auditorium at a tenth of its seats is not ventilated for a full house. 90.1 §6.4.3.9 requires it in dense spaces above a size.
The floor is the per-area share and the damper never closes below it. Outside air the machine does not have to condition is capacity it can spend on the rooms: on the example mall DCV is worth 2.2 MWh of heating and 0.9 of electricity on London's year at its 62.1-derived floors. In HVAC Builder the base fraction is a property of the rooms' use, computed from Table 6.2.2.1 over what each machine serves.
Face-and-bypass
A damper that sends part of the air across the coil and mixes the rest back; the coil dries the share it sees and the bypassed air is the reheat, for nothing. Humidity: ceilings and floors and the cleanroom case.
What is face-and-bypass?
A cooling coil dehumidifies by cooling air to its dew point; to hold a room's humidity without over-cooling it, the air must be warmed again afterwards. Face-and-bypass does that without a heater: a damper sends part of the air across the coil face and the rest around it, and the two streams mix back to the supply temperature the room needs. The bypassed air is warm and dry enough; the coil air is cold and dry; the mix lands on both targets.
It is the arrangement a cleanroom or a museum handler has, because the reheat is free. In a building simulation a split ahead of a cooling coil that re-merges behind it — the fan's outlet wired to the coil and to the plenum, the coil's outlet to the plenum — is recognised as one damper, and a humidity ceiling on the room is held by bisecting the share of air over the coil — the heater stays off. On the example cleanroom it takes the reheat from 273 MWh a year to none.
Head-pressure control
Condenser fans taken off on a cool day to hold a minimum condensing temperature — a constraint an expansion valve needs, not an economy. Head-pressure control.
What is head-pressure control?
On a cold day an air-cooled condenser rejects heat too well: the condensing pressure falls, the expansion valve loses the pressure difference it meters on, and the circuit starves. Head-pressure control holds the condensing temperature at a floor by taking condenser air away — fan cycling, a fan bank staged down, or a speed-controlled fan — the least air that keeps the head where the valve needs it.
It is a constraint, not an economy: at full output the staged point draws more than the free-floating one, because a higher condensing temperature costs compressor power. HVAC Builder settles the head before a stage is judged, walking the fan bank's ladder down until the running condensing temperature reaches the setpoint, and re-settles it at the part load the machine actually runs at.
Humidity ceiling and floor
A room's upper and lower bounds on moisture; the ceiling makes the machine over-cool and reheat (or bypass), the floor steers a humidifier. Humidity: ceilings and floors.
What are a humidity ceiling and a humidity floor?
A room's comfort has a moisture side. ASHRAE 55 bounds the humidity ratio at 0.012 kg/kg — a limit on moisture, not on relative humidity, which moves with temperature — and an operating suite or an archive holds a floor too. A ceiling makes the machine over-cool its supply to a lower dew point and warm it back, by a heater or a bypass damper; a floor makes a humidifier add steam to the supply.
In a building run each is a second requirement the controller judges every hour beside the temperature: the moisture balance of the room is inverted into the supply humidity that lands it on the bound, and the machine is modulated on both reads. Two rooms on one machine can ask for different things; the driest ask wins the ceiling, the wettest the floor. Rooms without a bound simply float, and the report counts the hours above 0.012 kg/kg.
Cycling and modulation
How a stage with too much capacity unloads: a fixed-speed compressor runs flat out for part of the hour, an inverter or a valve turns down. Cycling and modulation.
Cycling or modulation: how does a machine meet a part load?
A fixed-speed compressor has two outputs, all and nothing, so it meets a part load by running part of the hour — cycling — and pays for every start: AHRI 340/360's cycling degradation, and the fans and pumps in its condenser section that stop with it. An inverter compressor slows instead, and at part load runs at lower pressure ratios, which is where a scroll's COP is best; over a year that is worth about 15 % of a rooftop's electricity on a real map.
Which one a machine does is a fact about the machine, not a setting, which is why HVAC Builder's default is the conservative reading — it cycles — and an inverter must say so. Valves modulate too: a chilled-water coil fed from outside its graph unloads by its valve, continuously, and a coil that cannot get low enough shuts and cycles. A chiller on a trickle cycles on its freeze cutout rather than on water it cannot make.
Coupling
A join between two blocks at their open ports — water, air or refrigerant — carrying last hour's state across, one hour behind. Couplings between blocks.
What is a coupling between two systems?
A building is rarely one machine. A chiller makes water for three air handlers; a condensing unit on the roof feeds an indoor coil; an exhaust unit hands its air to a recovery unit. A coupling is that fact declared port by port on the building: this block's water outlet feeds that block's coil inlet, this coil's return goes back to that evaporator. The receiving block then sees its partner's actual leaving water, flow and all, rather than a fixed boundary.
Blocks step in order and the return path runs one hour behind, which on a water loop is a ±0.3 K limit cycle — measured, and left as it is, since a cross-block fixed point buys half a percent. A block can serve water instead of rooms, holding a leaving-water setpoint for its partners; several receivers on one port are a manifold, on water, refrigerant and air alike; refrigerant pairs put a condensing unit and its indoor unit in two blocks with the circuit split between them.
Priority
The order machines serving one room take it in: the lead is offered the whole load and the latent, the next what the lead did not deliver. Several machines on one room.
What is priority between machines serving one room?
When two machines serve the same room they could split its load in shares, and a share is always wrong for one of them: the load being divided is sensible only, and the machine doing the latent work — a DOAS — must not be throttled to a fraction. So machines take a room in turn instead. The leading machine is offered the whole demand; the next is offered what the lead did not actually deliver; equals divide what reaches them.
Declared rather than inferred, because nothing in a graph says which machine is the outside-air unit. The rule has a moisture side too: the machine behind a lead is asked for the supply humidity that lands the room on its bound beside the air the lead delivered, so a DOAS carries the latent and the handler behind it only the remainder. One wart to know: a lead's own unmet count reads hours it could not cover alone — the room's count is the comfort truth.
Category
What a system is — rooftop, split, air handler, chiller, condensing unit, fan coil, evaporative, recovery, plant, unit cooler, or a label of your own. Kinds of systems.
What is a system category?
Every system carries one word saying what kind of machine it is — air handler, rooftop, split, chiller, condensing unit, fan coil, evaporative cooler, recovery unit or DOAS, plant, unit cooler — or a custom label. It is what the public directory filters on, what a supplier declares they build, and since categories entered quote matching it is part of how a request finds the suppliers who make that kind of thing.
The vocabulary is fixed on purpose and small: ten words an engineer would use, translated in the app and on the public site, with room for a custom label where none fits. A supplier who declares no categories is matched on capabilities alone; one who declares them is matched only on requests of those kinds — the same shape as the refrigerant rule, which also excludes only when both sides have spoken.
Nested system
A saved or published system placed into a design as one block showing its open ports; the solver flattens it. Systems can contain systems.
What is a nested system?
A saved or published system can be placed into another design as one block, wired at its open ports, and solved as part of the whole: a chiller nested inside a plant, an air handler nested inside a campus. The composition addresses a nested port as `unit/coil`, three levels deep at most, and the solver flattens the whole tree before solving so nothing is silently ignored — a composition with an unresolved reference is refused, never solved around.
A reference follows its source — edit the saved chiller and the plant that nests it changes — until it is copied in, at which point it is the design's own; it can also be exploded into plain components with the block's name kept as a prefix. A supplier publishes a composition flattened, and another supplier's offering may be nested only where its owner has allowed reuse.
Design point and TMY year
One set of entering conditions a system tab solves at; a typical meteorological year is the 8 760 hours a building tab runs against. A solve is one condition; a simulation is a year of them.
Design point or TMY year: what is the difference?
A design point is one set of entering conditions — 35 °C outside, 24 °C return, a duty — and a solve at it answers what the machine does there: the coil's leaving air, the compressor's evaporating and condensing temperatures, the COP. It is what a catalog rating is, and what a selection is made on. A typical meteorological year is 8 760 of those conditions in the order a real year serves them, assembled by PVGIS from decades of measurements so that no month is unusually mild or harsh.
A simulation runs the machine — or the building — against that year, hour by hour, with the control deciding what runs and the rooms remembering what happened the hour before. The design point tells you whether the machine can; the year tells you what it costs, how often it falls short, and which day decides its size. HVAC Builder's system tab is the first, its building tab the second, and the same graph feeds both.
Superheat
How far the vapour leaving an evaporator is above its saturation (dew) temperature; a compressor map is published at one stated superheat and corrected to the operating one. The refrigerant charts carry the dew line it is measured from.
What is superheat, and why does a compressor map state it?
Superheat is how far the refrigerant vapour leaving an evaporator is above its saturation temperature at that pressure — on a blend, above the dew temperature, where the last drop of liquid boils off. It exists because the compressor must never draw liquid: the expansion valve holds a margin of a few kelvin past the point where evaporation is complete, typically 5 to 10 K on an air-conditioning unit. A freezer's suction line runs through a warm store and picks up far more — Copeland rates its refrigeration scrolls at a 65 °F (18 °C) return-gas temperature, which at −30 °C evaporating is nearly 50 K of superheat by the time the gas reaches the compressor.
A compressor map counts every kelvin of that superheat as capacity, because AHRI 540 measures capacity at the compressor inlet: the polynomial is published at one fixed superheat (11.1 K under AHRI 540, 10 K under EN 12900) and the mass flow it implies follows the density of the suction gas. Running the machine at a different superheat needs a correction to both the suction density and the refrigerating effect, which this solver applies to every catalog map and holds against Copeland's own EN 12900 tables within one percent. Only the superheat gained inside the coil is useful cooling; the rest is heat the suction line took from the room, and a freezer declares the split.
Subcooling
How far the liquid leaving a condenser is below its saturation temperature — the bubble temperature on a blend — and worth about a percent of capacity per two to three kelvin. The refrigerant charts carry the bubble line.
What is subcooling, and where is it measured from?
Subcooling is how far the liquid leaving a condenser is below its saturation temperature at the condensing pressure. It guarantees solid liquid at the expansion device — flash gas in the liquid line starves a valve and shows as hunting — and it adds refrigerating effect: every kelvin of subcooling is a kelvin of liquid the evaporator no longer has to flash off, worth roughly a percent of capacity per two to three kelvin. Compressor maps are published at a stated subcooling — 8.3 K under AHRI 540, none under EN 12900 — and a map rated at 8.3 K read at zero over-states capacity by about eight percent on R410A, which is why this solver corrects every map to the operating subcooling.
On a zeotropic blend the measurement point matters. The liquid leaves the condenser at the bubble temperature, which on R448A or R455A sits 4 to 13 K under the dew temperature at the same pressure; subcooling is measured down from the bubble line, and a selection program that states 'liquid temperature' beside a dew-point condition is saying exactly that. Reading it from the dew temperature credits the liquid with heat it never had — seven percent of R455A's effect — and this solver measures from the bubble point on every fluid, which is the identity on a pure one. The bubble line is on every blend's pressure–temperature chart here.
Sensible heat ratio (SHR)
The sensible share of a cooling duty, the rest being moisture condensed out; the slope of the process line on the chart. Draw one on the free chart.
What is the sensible heat ratio (SHR) of a cooling coil?
The sensible heat ratio is the share of a cooling duty that lowers the air's temperature, the rest being latent — moisture condensed out. A coil cooling dry air has an SHR of one; a comfort coil in a humid climate runs at 0.6 to 0.8, and a dehumidifier's is lower still. On the psychrometric chart the process line's slope is the SHR: a steep line is mostly latent, a flat one mostly sensible. The room has an SHR of its own — people, ventilation air and infiltration add moisture, lights and sun do not — and a coil whose SHR is higher than the room's leaves the humidity climbing however cold it blows.
A coil's SHR is set by its geometry and its conditions: a deeper coil, a colder surface or slower air drives the leaving state closer to the surface temperature and takes more moisture out, so a coil selected on temperature alone may be the wrong one for the moisture. Every process the solver reports carries its sensible duty beside its total, and a building simulation treats the moisture balance separately from the sensible load — which is why one machine can carry a room's latent load while another carries the rest, and why a room's humidity ceiling can make a unit over-cool and reheat.
Bypass factor
The fraction of the air a cooling coil leaves untouched; the rest leaves at the coil's surface temperature. The coil model computes it from the geometry.
What is a cooling coil's bypass factor?
A cooling coil's bypass factor is the fraction of the air that passes through as if it had never touched the coil; the rest leaves at the coil's apparatus dew point — effectively the surface temperature — and the actual leaving air is the mix of the two. It is a one-number picture of how completely the coil contacts its air: more rows, closer fins and slower air lower it, and typical values run from 0.05 on a deep coil to 0.3 on a shallow one. It decides the moisture a coil removes, because only the contacted air is brought to the surface where condensation happens — a shallow, sparse coil cools sensibly and dries poorly.
The factor is exp(−NTU) on the air side, so it comes from the air-side heat-transfer coefficient and the surface area. In this model the coefficient is computed from the coil's geometry through a published correlation with one calibration, and the fin-to-tube contact resistance is kept as its own term rather than folded into the air-side coefficient — folded in, it would inflate the bypass factor and misread the latent duty of a shallow coil by twenty percent, which is what the Carrier rating matrix the model is held against showed.
Wet-bulb temperature
What a wetted thermometer reads in moving air — the limit of evaporative cooling and the floor under every cooling tower. Plot a state from it.
What is the wet-bulb temperature?
The wet-bulb temperature is what a thermometer with a wetted wick reads in moving air: evaporation cools the wick until the heat the air gives it balances the heat the water takes, and that balance depends on how dry the air is. It is the lowest temperature evaporation alone can reach, very nearly the adiabatic saturation temperature, and with the dry-bulb temperature it fixes the air's moisture content — a design condition is quoted as the pair, 35 °C dry bulb and 24 °C wet bulb. The gap between them, the wet-bulb depression, is what an evaporative cooler works with: a pad's effectiveness is the fraction of the depression it achieves.
It also bounds every cooling tower: the water leaving a tower can approach the entering wet bulb but never go below it, so a tower's rating is a leaving-water temperature at a stated wet bulb and its approach grows on a humid afternoon. On the psychrometric chart the wet-bulb lines run nearly along the lines of constant enthalpy, which is why an adiabatic process such as a spray or a wetted pad draws as a line of constant wet bulb. The free chart on this site plots any state from its dry and wet bulb.
Dew point
The temperature at which cooled air begins to condense; a coil surface below it dries the air, one above it does not. The coil model solves the partly wet case in between.
What is the dew point, and why does a cooling coil care?
The dew point is the temperature at which moist air, cooled at constant pressure, becomes saturated and its water begins to condense; it is fixed by the moisture content alone, so a room at 24 °C and 50 % relative humidity has a dew point of about 12.9 °C whatever its dry-bulb temperature does. A cooling coil whose surface sits above the entering dew point cools the air dry; one whose surface is below it condenses, and a coil in between runs partly wet — this model solves that partially wet case as two sections meeting where the surface reaches the dew point, so the duty is continuous across the change.
A dedicated outside-air unit is specified on the supply dew point it holds, because the moisture it delivers is what sets the room's humidity once the sensible load is carried by other machines. The saturation line the dew point is read from is pure water's vapour pressure with a small enhancement factor for the presence of air; this solver uses Buck's factor as a function of pressure and temperature, held within 0.1 % of ASHRAE's published table, and the same line is drawn by the free psychrometric chart.
COP and EER
Output over electrical input, dimensionless or in Btu/h per watt (EER is 3.412 × COP); SEER and SCOP weight a season, which a year's simulation measures instead.
What are COP and EER, and how do they differ from SEER?
The coefficient of performance is the cooling — or heating — a machine delivers divided by the electricity it draws, in the same units, so a chiller delivering 300 kW for 60 kW of power has a COP of 5. EER is the same ratio with the cooling in Btu/h and the power in watts, which makes it 3.412 times the COP. A compressor map's COP counts only the compressor; a unit's COP adds the fans and pumps that run with it, which is why a packaged rooftop reads lower than the scroll inside it. Both are figures at one condition, and the condition must be stated: AHRI rates air conditioners at 35 °C outdoors.
SEER, SCOP and IEER weight several part-load conditions to estimate a season, on the assumption of a standard load profile and climate. An hourly simulation against the building's own weather year measures the seasonal figure directly, machine by machine, with the cycling and the fan energy in it — which is where the standard ratings and the building disagree. The thermodynamic ceiling is Carnot's: COP cannot exceed the cold temperature over the temperature lift, in kelvin, and real machines reach 40 to 60 % of it; this solver flags a compressor map claiming more than 80 % as a polynomial read outside its envelope.
Compressor map
A maker's ten-coefficient polynomial in evaporating and condensing temperature, valid inside its envelope. Read any of the catalog's at your conditions.
What is a compressor map (an AHRI 540 polynomial)?
A compressor map is the manufacturer's statement of what a compressor does across its operating range: capacity, power and mass flow as ten-coefficient polynomials in the evaporating and condensing saturation temperatures, published under AHRI 540 in North America and EN 12900 in Europe, each at a stated superheat and subcooling. A selection program evaluates the polynomial at a pair of temperatures; a system solver finds the pair where the evaporator, the compressor and the condenser balance, and reads the map there. The map is valid only inside the published operating envelope — the polygon on the datasheet — and a cubic read outside it answers plausibly and wrongly.
This catalog holds nearly ten thousand such maps from four makers' published data, each page sampling its map across its own envelope, and the free lookup reads any of them at your conditions. Inverter machines add part-load steps — the same polynomials at several speeds — which the solver interpolates between; without them a modulating machine's power is over-stated because its efficiency changes as it unloads. The standard also states how far a fitted map may stray from a measured point, and the tool that fits a map from a table reports each point against that limit.
Evaporating and condensing temperature
The two saturation temperatures a circuit runs between, found where evaporator, compressor and condenser balance — the solver's two unknowns per circuit. What a solve returns.
What are the evaporating and condensing temperatures of a refrigeration circuit?
A vapour-compression circuit runs between two pressures, and each pressure has a saturation temperature: the evaporating temperature, at which the refrigerant boils in the coil taking heat from the air or water it cools, and the condensing temperature, at which it condenses in the condenser giving that heat plus the compressor's work away. They are the two numbers a circuit is described by. The evaporating temperature sits below the fluid it cools by the coil's approach — 5 to 15 K on a direct-expansion coil — and the condensing temperature above the condenser's entering air by 10 to 15 K; a compressor's map is a function of exactly these two.
Neither is chosen by the designer directly: they are where the three components balance. A hotter day raises the condensing temperature, the compressor pumps less and draws more, and the evaporating temperature follows the reduced capacity upward. This solver treats the pair as the two unknowns of every circuit and finds them by Newton's method, with the head-pressure floor, the frost derate and the map envelope all expressed in the same two temperatures; a refrigerant's pressure–temperature chart converts either to the pressure a gauge on the circuit would read.
Range and approach
A cooling tower's water temperature drop, and how close its cold water gets to the entering wet bulb; the approach can never be zero. The tower model is rated from one point.
What are a cooling tower's range and approach?
A cooling tower's range is the temperature drop of its water, from hot inlet to cold outlet; its approach is how close the cold water gets to the entering air's wet-bulb temperature. A tower is rated at one point — 35 °C in, 29.4 °C out, at a 25.6 °C wet bulb is a common one, a range of 5.6 K and an approach of 3.9 K — and the approach is the harder number: it shrinks with less load or more air, grows on a humid day, and can never reach zero, since that would take an infinitely large tower. A rating with the cold water at or below the wet bulb is not a rating.
The same word is used of any heat exchanger — a condenser's approach is its condensing temperature over the entering air, a coil's the leaving fluid over the surface — and it is the number a designer buys with surface area. This model's tower takes the certified rating point and derives the tower's transfer capability from it once, then follows the water loading with a fitted exponent held against two makers' published performance tables; a free-cooling plant stages and cycles its tower fans to make the least air that meets the approach the plate exchanger needs.
Heat-recovery (three-pipe) VRF
Some indoor units cool while others heat on one outdoor unit, the heat moved between rooms rather than rejected. The clinic case measures it over a year.
What is a heat-recovery (three-pipe) VRF system?
A variable-refrigerant-flow system runs several indoor units on one outdoor unit through a shared refrigerant line. A two-pipe system has one direction at a time — every indoor unit cools, or every one heats. A heat-recovery, or three-pipe, system lets some rooms cool while others heat: the heat taken from a glazed south office is moved to a north waiting room instead of being rejected outdoors, and the outdoor coil handles only the difference. In a building whose rooms disagree by kilowatts — a clinic in spring, an office with a server room — the compressor works for the larger side and the smaller side's heat comes nearly free.
AHRI 1230 rates such a system on a simultaneous cooling-and-heating efficiency, the two outputs summed over the power, which is the sum of the two coefficients of performance. This model runs a heat-recovery block with both ends pinned by their coils, the recovered heat credited to the smaller side and the outdoor coil facing the way the larger side needs; the worked clinic case measures what the recovery is worth over a year. What decides the size of a VRF design is usually the indoor unit's ceiling rather than the outdoor unit's, which the same case shows.
Typical meteorological year (TMY)
8 760 hours of representative weather assembled from real years — for annual energy, not for sizing. Running a year.
What is a typical meteorological year (TMY)?
A typical meteorological year is 8 760 hours of weather assembled month by month from a run of real years — each month chosen as the most representative of its kind in the record, then stitched together — so that a simulation against it sees a normal year rather than any particular one. It carries dry-bulb temperature, humidity, wind and the solar components, and the European PVGIS service publishes one free for any point on the map, from which this site's weather library is drawn. Its purpose is annual energy and comfort: how many hours a machine runs, cycles, or falls short, and what the year costs.
It is not a sizing tool. Design conditions — the 0.4 % or 1 % dry bulb and wet bulb a machine is selected at — are percentiles of the whole record, and a typical year may not contain the design day at all; a machine sized on the year's own peak is sized on one year's luck. One trap in the data: PVGIS labels its hours in UTC, and a year used unrotated puts every occupancy schedule a time zone away from its sun, which this library corrects on the way in. A synthetic design year, built from the design conditions, is the other kind of year a building tab runs.