Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Source: Baltimore Aircoil Product & Application Handbook volume VI, Series V engineering data — the model's own row (nominal tonnage, airflow in CFM, fan motor, dimensions) and the sheet's own rating note: a nominal ton is 3 USGPM of water cooled from 95 °F to 85 °F at a 78 °F entering wet-bulb temperature (docs/bac-source.json). The figures below come from this model run against that data; the manufacturer has not reviewed them. Are you Baltimore Aircoil? Claim this page.
by HVAC Builder
Open this system in HVAC Builder Load it into the 3D builder, adjust it to your project, and solve it against your own climate — or drop it into a building model and simulate a full year.
A 600-ton counterflow Series V — centrifugal fans, forced draft, 1 800 USGPM cooled from 95 to 85 °F at a 78 °F entering wet bulb on 61.9 m³/s of air. Its liquid-to-gas ratio of about 1.6 is the highest of the five published here, which is why its derived NTU is the highest too: a counterflow tower works its fill harder per unit of air than a crossflow one. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
Example2200–3200 kW coolingEUExample system. Published by HVAC Builder to show suppliers what their own page looks like. There is no company behind it and it is not a product offer — the specification is generic and the performance is solved from the model on this page.
Solved from this example's own model each time the page loads — the same numbers a supplier's page shows for their machine.
| Component | Kind | Duty |
|---|---|---|
| VT1-600-P fill | wetPack | -2571.0 kW |
| VT1-600-P fan | fan | -29.8 kW |