Baltimore Aircoil Series V closed circuit VF1-288-31R closed-circuit cooler (304 tons, 1.3 MW) — modelled

Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Source: Baltimore Aircoil Product & Application Handbook volume VI, Series V closed circuit engineering data — the model's own row (nominal tonnage, airflow in CFM, fan motor, dimensions) and the sheet's own rating note: a nominal ton is 3 USGPM of water cooled from 95 °F to 85 °F at a 78 °F entering wet-bulb temperature (docs/bac-source.json). The figures below come from this model run against that data; the manufacturer has not reviewed them. Are you Baltimore Aircoil? Claim this page.

CTI STD-201 (validation C11K-00R03) ✓ verified — this model is named in the certification programme's own public register. It certifies the manufacturer's machine against their published ratings; it says nothing about the model of it that runs here, which is validated separately.

by HVAC Builder

Open this system in HVAC Builder Load it into the 3D builder, adjust it to your project, and solve it against your own climate — or drop it into a building model and simulate a full year.

BAC's VF1-288-31R — a Series V closed circuit closed-circuit cooler, 304 nominal tons (1336 kW): rated to cool 915 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 86.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Example1002–1670 kW coolingEU

Example system. Published by HVAC Builder to show suppliers what their own page looks like. There is no company behind it and it is not a product offer — the specification is generic and the performance is solved from the model on this page.

Design-point performance

1331.6 kWcooling
89.5 kWelectrical power
2826 l/hwater use
14.88system COP

Solved from this example's own model each time the page loads — the same numbers a supplier's page shows for their machine.

Component schedule

ComponentKindDuty
VF1-288-31R fillwetPack-1331.6 kW
VF1-288-31R fanfan-89.5 kW
VF1-288-31R tower-loop circulatorpump—

Are you a manufacturer?

Publish your own range and this slot becomes your branded page — your data, your logo, your product link, and quote requests that reach you. Free to register and free to publish.

Open the Company page How it works