Baltimore Aircoil Series V VT1-M1137-Q cooling tower (1133 tons, 5.0 MW) — modelled

Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Source: Baltimore Aircoil Product & Application Handbook volume VI, Series V engineering data — the model's own row (nominal tonnage, airflow in CFM, fan motor, dimensions) and the sheet's own rating note: a nominal ton is 3 USGPM of water cooled from 95 °F to 85 °F at a 78 °F entering wet-bulb temperature (docs/bac-source.json). The figures below come from this model run against that data; the manufacturer has not reviewed them. Are you Baltimore Aircoil? Claim this page.

CTI STD-201: the line, not this model — Baltimore Aircoil's Series V Open line is certified (validation C11B-92R07), but this model is not named in the disclosure that covers it, so nothing is claimed for it here: the disclosure says what it covers in its own title — the VT0 and VT1 Group A models — so the larger VT1 frames (VT1-550 upward) and the VT1-M and VT1-N groups are not in it, and nothing here says whether they are certified elsewhere. What the model of it reads against the maker's published tables is a separate question.

by HVAC Builder

Open this system in HVAC Builder Load it into the 3D builder, adjust it to your project, and solve it against your own climate — or drop it into a building model and simulate a full year.

BAC's VT1-M1137-Q — a Series V cooling tower, 1133 nominal tons (4982 kW): rated to cool 3411 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 107.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Example3736–6227 kW coolingEU

Example system. Published by HVAC Builder to show suppliers what their own page looks like. There is no company behind it and it is not a product offer — the specification is generic and the performance is solved from the model on this page.

Design-point performance

4918.5 kWcooling
111.9 kWelectrical power
7214 l/hwater use
43.97system COP

Solved from this example's own model each time the page loads — the same numbers a supplier's page shows for their machine.

Component schedule

ComponentKindDuty
VT1-M1137-Q fillwetPack-4918.5 kW
VT1-M1137-Q fanfan-111.9 kW
VT1-M1137-Q tower-loop circulatorpump—

Are you a manufacturer?

Publish your own range and this slot becomes your branded page — your data, your logo, your product link, and quote requests that reach you. Free to register and free to publish.

Open the Company page How it works