Baltimore Aircoil Series 3000 XES3E-8518-05G cooling tower (170 tons, 749 kW) — modelled

Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Source: Baltimore Aircoil Product & Application Handbook volume VI, Series 3000 engineering data — the model's own row (nominal tonnage, airflow in CFM, fan motor, dimensions) and the sheet's own rating note: a nominal ton is 3 USGPM of water cooled from 95 °F to 85 °F at a 78 °F entering wet-bulb temperature (docs/bac-source.json). The figures below come from this model run against that data; the manufacturer has not reviewed them. Are you Baltimore Aircoil? Claim this page.

CTI STD-201 (validation C11F-92R20) ✓ verified — this model is named in the certification programme's own public register. It certifies the manufacturer's machine against their published ratings; it says nothing about the model of it that runs here, which is validated separately.

by HVAC Builder

Open this system in HVAC Builder Load it into the 3D builder, adjust it to your project, and solve it against your own climate — or drop it into a building model and simulate a full year.

BAC's XES3E-8518-05G — a Series 3000 cooling tower, 170 nominal tons (749 kW): rated to cool 513 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 22.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Example562–937 kW coolingEU

Example system. Published by HVAC Builder to show suppliers what their own page looks like. There is no company behind it and it is not a product offer — the specification is generic and the performance is solved from the model on this page.

Design-point performance

742.1 kWcooling
2.2 kWelectrical power
1173 l/hwater use
331.76system COP

Solved from this example's own model each time the page loads — the same numbers a supplier's page shows for their machine.

Component schedule

ComponentKindDuty
XES3E-8518-05G fillwetPack-742.1 kW
XES3E-8518-05G fanfan-2.2 kW
XES3E-8518-05G tower-loop circulatorpump—

Are you a manufacturer?

Publish your own range and this slot becomes your branded page — your data, your logo, your product link, and quote requests that reach you. Free to register and free to publish.

Open the Company page How it works