CaptiveAire Unclaimed
57 listing(s) in HVAC Builder's catalog from CaptiveAire's published data, selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; CaptiveAire has not claimed it.
- Fans — 57
Are you CaptiveAire?
Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. We confirm each claim by hand before it takes effect; from then the page and its listings are yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page
Listings
Showing 25–48 of 57
CaptiveAire DU33HFA direct-drive centrifugal upblast exhaust fan (Catalog #110C, November 2024; 1616 rpm)
Fan rated 0.38 m³/s at 0.30 kW.
CaptiveAire DU360HFA direct-drive centrifugal upblast exhaust fan (Catalog #110C, November 2024; 782 rpm)
Fan rated 5.90 m³/s at 8.05 kW.
CaptiveAire DU50HFA direct-drive centrifugal upblast exhaust fan (Catalog #110C, November 2024; 1456 rpm)
Fan rated 0.42 m³/s at 0.41 kW.
CaptiveAire DU85HFA direct-drive centrifugal upblast exhaust fan (Catalog #110C, November 2024; 1532 rpm)
Fan rated 0.80 m³/s at 0.76 kW.
CaptiveAire SIF10DD direct-drive inline exhaust fan (Catalog #110C, November 2024; 1639 rpm)
Fan rated 0.19 m³/s at 0.18 kW.
CaptiveAire SIF10DD-SS direct-drive inline exhaust fan (Catalog #110C, November 2024; 1639 rpm)
Fan rated 0.19 m³/s at 0.18 kW.
CaptiveAire SIF11DD direct-drive inline exhaust fan (Catalog #110C, November 2024; 2309 rpm)
Fan rated 0.47 m³/s at 0.99 kW.
CaptiveAire SIF11DD-HE direct-drive inline exhaust fan (Catalog #110C, November 2024; 3066 rpm)
Fan rated 0.61 m³/s at 1.19 kW.
CaptiveAire SIF11DD-SS direct-drive inline exhaust fan (Catalog #110C, November 2024; 2198 rpm)
Fan rated 0.38 m³/s at 0.83 kW.
CaptiveAire SIF13DD direct-drive inline exhaust fan (Catalog #110C, November 2024; 2278 rpm)
Fan rated 0.90 m³/s at 1.94 kW.
CaptiveAire SIF13DD-HE direct-drive inline exhaust fan (Catalog #110C, November 2024; 2811 rpm)
Fan rated 0.99 m³/s at 1.68 kW.
CaptiveAire SIF13DD-SS direct-drive inline exhaust fan (Catalog #110C, November 2024; 2072 rpm)
Fan rated 0.71 m³/s at 1.42 kW.
CaptiveAire SIF15DD direct-drive inline exhaust fan (Catalog #110C, November 2024; 2013 rpm)
Fan rated 1.13 m³/s at 2.39 kW.
CaptiveAire SIF15DD-HE direct-drive inline exhaust fan (Catalog #110C, November 2024; 2284 rpm)
Fan rated 1.32 m³/s at 1.88 kW.
CaptiveAire SIF15DD-SS direct-drive inline exhaust fan (Catalog #110C, November 2024; 1738 rpm)
Fan rated 1.13 m³/s at 1.56 kW.
CaptiveAire SIF18DD direct-drive inline exhaust fan (Catalog #110C, November 2024; 1741 rpm)
Fan rated 1.60 m³/s at 3.41 kW.
CaptiveAire SIF18DD-HE direct-drive inline exhaust fan (Catalog #110C, November 2024; 1759 rpm)
Fan rated 1.65 m³/s at 1.64 kW.
CaptiveAire SIF20DD direct-drive inline exhaust fan (Catalog #110C, November 2024; 1574 rpm)
Fan rated 1.98 m³/s at 3.96 kW.
CaptiveAire SIF20DD-HE direct-drive inline exhaust fan (Catalog #110C, November 2024; 1712 rpm)
Fan rated 2.36 m³/s at 2.88 kW.
CaptiveAire SIF24DD direct-drive inline exhaust fan (Catalog #110C, November 2024; 1221 rpm)
Fan rated 2.22 m³/s at 3.74 kW.
CaptiveAire SIF24DD-HE direct-drive inline exhaust fan (Catalog #110C, November 2024; 1603 rpm)
Fan rated 3.54 m³/s at 5.55 kW.
CaptiveAire SIF30DD direct-drive inline exhaust fan (Catalog #110C, November 2024; 962 rpm)
Fan rated 3.78 m³/s at 5.90 kW.
CaptiveAire SIF30DD-HE direct-drive inline exhaust fan (Catalog #110C, November 2024; 1423 rpm)
Fan rated 6.14 m³/s at 10.70 kW.
CaptiveAire SIF36DD direct-drive inline exhaust fan (Catalog #110C, November 2024; 812 rpm)
Fan rated 5.43 m³/s at 8.11 kW.
How the model reads against CaptiveAire's data
| Fan power through the fan laws, one curve per fan from a US multi-rating table | 2 813 cells over 57 fans; 49 withheld by name | every held cell's BHP within 2 % plus the half-hundredth it is printed to (the worst at 0.984 of that band; one cell from 0.5 BHP past a bare 2 %, at 2.4 %) and its speed within 0.95 %, read back by the solver's own fan-law solve; RMS 0.41 % on power over the 1 845 cells from 0.5 BHP up. Withheld: 41 cells at the high-static end of a low-flow row, left of the wheel's pressure peak; 6 off the fan laws; 2 printed slips (a 1 in. cell repeating its row's 0 in. figures, a 2.25 in. cell 168 rpm under the 2 in. one). The stainless copies print 71 of their sizes' cells a second time, all within rounding. The SIF9DD and its copy are not listed: their best static efficiency is under 0.2. Each rating lies on its curve (the curve's static at the design flow within 1.00 % of the design static), and the efficiency a listing states is the curves' read there — DU10HFA's best printed cell, 0.02 BHP, would claim 0.383 on input power where its curve reaches 0.353 |
| R454B's saturation line — the properties every R454B map in the catalog runs on — against a maker's printed pressure–temperature table | 40 temperatures × 2 lines, −40 to 155 °F (160–170 °F lie past the top of the backend's R454B line, 71 °C) | one offset, not scatter: at every temperature the backend's dew point is 0.05–0.15 K under the printed one (its dew pressure 0.2–0.5 % over) and its bubble point 0.26–0.33 K under (0.5–1.3 %), so its glide is about 0.2 K wider than the table's. The table does not say whose equation of state it prints, so the offset is held as a bracket on that side, not fitted |
From the validation page; every row is held by a test.
Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.