992 listing(s) in HVAC Builder's catalog from EVAPCO's published data and 992 system(s) modelled on it — 0 built by hand and 992 derived from the listings themselves — selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; EVAPCO has not claimed it.

Are you EVAPCO?

Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Listings

All kindsCooling tower 992
Any certificationCTI STD-201 (validation C13A-99R28) 822
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 937–960 of 992

EVAPCO AT 424-3I28 cooling tower

Cooling tower — 5792 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 139.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-3J24 cooling tower

Cooling tower — 6445 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 149.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-3J28 cooling tower

Cooling tower — 6848 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 158.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-3J36 cooling tower

Cooling tower — 8250 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 196.8 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-3K24 cooling tower

Cooling tower — 7032 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 163.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-3K28 cooling tower

Cooling tower — 7646 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 173.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-3K36 cooling tower

Cooling tower — 9236 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 215.3 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-3K40 cooling tower

Cooling tower — 8929 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 219.2 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-3L24 cooling tower

Cooling tower — 7567 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 175.7 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-3L28 cooling tower

Cooling tower — 8206 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 185.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-3L36 cooling tower

Cooling tower — 9841 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 231.1 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-3L40 cooling tower

Cooling tower — 9770 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 235.2 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-3M24 cooling tower

Cooling tower — 8040 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 186.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-3M28 cooling tower

Cooling tower — 8732 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 196.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-3M36 cooling tower

Cooling tower — 10397 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 244.8 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-3M40 cooling tower

Cooling tower — 10428 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 249.0 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-3N28 cooling tower

Cooling tower — 9635 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 215.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-3N36 cooling tower

Cooling tower — 11453 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 267.8 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-3N40 cooling tower

Cooling tower — 11698 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 272.2 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-3O36 cooling tower

Cooling tower — 12294 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 287.3 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-3O40 cooling tower

Cooling tower — 12706 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 291.8 m³/s of air.

catalog
Cooling tower

EVAPCO AT 424-4I24 cooling tower

Cooling tower — 5871 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 129.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-4I28 cooling tower

Cooling tower — 6283 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 136.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 424-4J24 cooling tower

Cooling tower — 6756 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 147.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower
‹ Previous1…3839404142Next ›

How the model reads against EVAPCO's data

Cooling-tower model, zero fitted parameters856mean −0.03 K, RMS 0.064 K, worst 0.24 K — NTU from the vendor's own Eurovent column, the shipped default exponent (−0.7, the joint minimum with Marley's table)
Cooling-tower model against a fourth maker's whole open-tower range, nothing fitted to it45 945 over 992 machinesmean −0.083 K, RMS 0.220 K, worst 1.89 K on leaving water. 0.098 K at the 78 °F rating wet bulb, where the NTU is derived, rising to 0.283 and 0.288 K at 50 and 90 °F. The fill's loading exponent was swept on either half of the range and the shipped default (−0.7, the joint minimum of EVAPCO's own LPT bulletin and Marley's table) is the minimum for this range too, so it carries no constant of its own — unlike BAC's five, which wanted −0.9 to −1.3

From the validation page; every row is held by a test.

Worked cases that run EVAPCO machines

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.