Tecumseh Unclaimed

1,891 listings in HVAC Builder's catalog from Tecumseh's published data, selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; Tecumseh has not claimed it.

Compressor maps by refrigerant: R404A 327, R452A 250, R448A 245, R449A 240, R134a 180, R455A 115, R290 111, R454C 106, R22 97, R513A 89, R407C 61, R1234yf 53, R600a 10, R410A 4, R407A 3.

Tecumseh compressor ranges

Each range on a page of its own: every model code with its refrigerants, frequencies and ratings, and every model a page.

Are you Tecumseh?

Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. We confirm each claim by hand before it takes effect; from then the page and its listings are yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Components

Showing 913–936 of 1,891

NameTypeRatingMarketsOpen in the builder
Tecumseh AJ2446Z-TZ1B (R449A hermetic, LBP, EN12900, 50 Hz) CatalogCompressorsR449A compressor — 0.59 kW cooling, 0.61 kW input, COP 0.97 at -30/45 °C (evaporating/condensing), inside its published envelope.EUOpen in the builder
Tecumseh FH4518Y-XG1A (R134a hermetic, HBP, EN12900, 50 Hz) CatalogCompressorsR134a compressor — 3.9 kW cooling, 1.47 kW input, COP 2.65 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AE4430P-FZ1A (R404A hermetic, HBP, EN12900, 50 Hz) CatalogCompressorsR404A compressor — 0.67 kW cooling, 0.35 kW input, COP 1.90 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AG2525P-TZ1A (R449A hermetic, LBP, EN12900, 60 Hz) CatalogCompressorsR449A compressor — 3.8 kW cooling, 3.37 kW input, COP 1.14 at -30/45 °C (evaporating/condensing), inside its published envelope.EUOpen in the builder
Tecumseh AGB4573ZKZ (R407C hermetic, HBP, EN12900, 60 Hz) CatalogCompressorsR407C compressor — 17.8 kW cooling, 8.00 kW input, COP 2.23 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AJ2446Z-TZ1B (R449A hermetic, LBP, EN12900, 60 Hz) CatalogCompressorsR449A compressor — 0.71 kW cooling, 0.72 kW input, COP 0.99 at -30/45 °C (evaporating/condensing), inside its published envelope.EUOpen in the builder
Tecumseh FH4518Y-XG1A (R134a hermetic, HBP, EN12900, 60 Hz) CatalogCompressorsR134a compressor — 4.7 kW cooling, 1.76 kW input, COP 2.69 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AE4430P-FZ1A (R448A hermetic, HBP, ASHRAE, 50 Hz) CatalogCompressorsR448A compressor — 0.79 kW cooling, 0.32 kW input, COP 2.46 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AG2525P-TZ1A (R452A hermetic, LBP, EN12900, 50 Hz) CatalogCompressorsR452A compressor — 2.4 kW cooling, 2.26 kW input, COP 1.04 at -35/45 °C (evaporating/condensing), inside its published envelope.EUOpen in the builder
Tecumseh AGB4573ZKZ (R448A hermetic, HBP, EN12900, 50 Hz) CatalogCompressorsR448A compressor — 15.4 kW cooling, 6.71 kW input, COP 2.29 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AJ2446Z-TZ1B (R452A hermetic, LBP, EN12900, 50 Hz) CatalogCompressorsR452A compressor — 0.47 kW cooling, 0.53 kW input, COP 0.90 at -35/45 °C (evaporating/condensing), inside its published envelope.EUOpen in the builder
Tecumseh FH4518Y-XG1A (R513A hermetic, HBP, EN12900, 50 Hz) CatalogCompressorsR513A compressor — 3.9 kW cooling, 1.54 kW input, COP 2.55 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AE4430P-FZ1A (R449A hermetic, HBP, ASHRAE, 50 Hz) CatalogCompressorsR449A compressor — 0.79 kW cooling, 0.32 kW input, COP 2.46 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AG2525P-TZ1A (R452A hermetic, LBP, EN12900, 60 Hz) CatalogCompressorsR452A compressor — 3.0 kW cooling, 2.83 kW input, COP 1.06 at -35/45 °C (evaporating/condensing), inside its published envelope.EUOpen in the builder
Tecumseh AGB4573ZKZ (R448A hermetic, HBP, EN12900, 60 Hz) CatalogCompressorsR448A compressor — 18.5 kW cooling, 8.49 kW input, COP 2.17 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AJ2446Z-TZ1B (R452A hermetic, LBP, EN12900, 60 Hz) CatalogCompressorsR452A compressor — 0.57 kW cooling, 0.63 kW input, COP 0.92 at -35/45 °C (evaporating/condensing), inside its published envelope.EUOpen in the builder
Tecumseh FH4518Y-XG1A (R513A hermetic, HBP, EN12900, 60 Hz) CatalogCompressorsR513A compressor — 4.8 kW cooling, 1.84 kW input, COP 2.58 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AE4430P-FZ1A (R452A hermetic, HBP, ASHRAE, 50 Hz) CatalogCompressorsR452A compressor — 0.78 kW cooling, 0.34 kW input, COP 2.31 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AG2525P-TZ1A (R454C hermetic, LBP, EN12900, 50 Hz) CatalogCompressorsR454C compressor — 2.2 kW cooling, 2.14 kW input, COP 1.05 at -30/50 °C (evaporating/condensing), inside its published envelope.EUOpen in the builder
Tecumseh AGB4573ZKZ (R449A hermetic, HBP, EN12900, 50 Hz) CatalogCompressorsR449A compressor — 15.4 kW cooling, 6.71 kW input, COP 2.29 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AJ2446Z-XA3C (R404A hermetic, LBP, EN12900, 50 Hz) CatalogCompressorsR404A compressor — 0.54 kW cooling, 0.61 kW input, COP 0.89 at -35/45 °C (evaporating/condensing), inside its published envelope.EUOpen in the builder
Tecumseh FH4522P-KZ1A (R454C hermetic, HBP, EN12900, 50 Hz) CatalogCompressorsR454C compressor — 7.0 kW cooling, 2.68 kW input, COP 2.60 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AE4430P-FZ1A (R454C hermetic, HBP, ASHRAE, 50 Hz) CatalogCompressorsR454C compressor — 0.72 kW cooling, 0.29 kW input, COP 2.46 at the AHRI 7.2/54.4 °C rating point.EUOpen in the builder
Tecumseh AG2525P-TZ1A (R454C hermetic, LBP, EN12900, 60 Hz) CatalogCompressorsR454C compressor — 2.9 kW cooling, 2.69 kW input, COP 1.07 at -30/50 °C (evaporating/condensing), inside its published envelope.EUOpen in the builder
‹ Previous1…3738394041…79Next ›

How the model reads against Tecumseh's data

Tecumseh hermetic compressor maps, the maker's own coefficient sets1 883 maps from 313 models on fifteen fluids (R404A 324, R452A 250, R448A 244, R449A 240, R134a 178, R455A 115, R290 109, R454C 106, R22 97, R513A 89, R407C 61, R1234yf 53, R600a 10, R410A 4, R407A 3) at 93 application × refrigerant × frequency listingspower reads the selector's point within 0.95 % on every map (units and coefficient order, BTU/h sets scaled and Fahrenheit sets substituted exactly); the 1 019 zeotrope maps read it to 0.00 % at the selector's dew pair and 3–10 % low at its mid-point pair, which is how the polynomials were shown to be dew-point maps; 1 378 maps rate at their own basis and read the selector's capacity within 1 %; on the 505 the selector corrected from a liquid-temperature or return-gas basis to the regime, this solver's AHRI 540 §6 correction reproduces the selector's corrected capacity within +0.2 % on average (the raw polynomial sits +8.7 % over it), single maps ±11 % where a return-gas basis is carried as one reference superheat. The envelope limits, which the selector states on the mid-point, are converted through the selector's own mid ↔ dew pairs (within 0.05 K of every pair, within 0.7 K of its stated 63 °C-mid condensing ceiling). The bubble line the subcooling is measured from reads the selector's liquid temperatures within 0.4 K on R448A, R449A, R452A, R407C and R404A, 0.6 K on R454C and 1.0 K on R455A — the two property sources' own disagreement on the blends' saturation lines

From the validation page; every row is held by a test.

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.