Copeland ZF11KQE-TFC (R22 scroll, 50 Hz, LL)
R22 compressor — 2.5 kW cooling, 1.74 kW input, COP 1.43 at -35/30 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TFC (R22 scroll, 60 Hz, LL)
R22 compressor — 3.0 kW cooling, 1.89 kW input, COP 1.59 at -35/30 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TFC (R404A scroll, 50 Hz, LL)
R404A compressor — 2.6 kW cooling, 1.88 kW input, COP 1.39 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TFC (R404A scroll, 60 Hz, LL)
R404A compressor — 3.1 kW cooling, 2.17 kW input, COP 1.44 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TF5 (R407A scroll, 50 Hz, LL)
R407A compressor — 2.1 kW cooling, 1.90 kW input, COP 1.11 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TF5 (R407A scroll, 60 Hz, LL)
R407A compressor — 2.5 kW cooling, 2.08 kW input, COP 1.22 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TF5 (R407C scroll, 60 Hz, LL)
R407C compressor — 2.4 kW cooling, 1.98 kW input, COP 1.20 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TF5 (R407F scroll, 50 Hz, LL)
R407F compressor — 2.1 kW cooling, 1.90 kW input, COP 1.11 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TF5 (R407F scroll, 60 Hz, LL)
R407F compressor — 2.5 kW cooling, 2.08 kW input, COP 1.22 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TF5 (R448A scroll, 50 Hz, LL)
R448A compressor — 2.2 kW cooling, 1.71 kW input, COP 1.30 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TF5 (R448A scroll, 60 Hz, LL)
R448A compressor — 2.7 kW cooling, 2.01 kW input, COP 1.34 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TF5 (R449A scroll, 50 Hz, LL)
R449A compressor — 2.2 kW cooling, 1.71 kW input, COP 1.30 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TF5 (R449A scroll, 60 Hz, LL)
R449A compressor — 2.7 kW cooling, 2.01 kW input, COP 1.34 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TFC (R507 scroll, 50 Hz, LL)
R507 compressor — 2.6 kW cooling, 1.98 kW input, COP 1.31 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF11KQE-TFC (R507 scroll, 60 Hz, LL)
R507 compressor — 3.1 kW cooling, 2.17 kW input, COP 1.44 at -35/35 °C (evaporating/condensing), inside its published envelope.
Copeland ZF13K4E-TF5 (R134A scroll, 50 Hz, HT)
R134a compressor — 7.4 kW cooling, 2.58 kW input, COP 2.88 at the AHRI 7.2/54.4 °C rating point.
Copeland ZF13K4E-TF5 (R134A scroll, 60 Hz, HT)
R134a compressor — 8.9 kW cooling, 3.10 kW input, COP 2.88 at the AHRI 7.2/54.4 °C rating point.
Copeland ZF13K4E-TF5 (R404A scroll, 50 Hz, LL)
R404A compressor — 4.1 kW cooling, 1.97 kW input, COP 2.09 at -30/25 °C (evaporating/condensing), inside its published envelope.
Copeland ZF13K4E-TF5 (R404A scroll, 60 Hz, LL)
R404A compressor — 4.9 kW cooling, 2.37 kW input, COP 2.09 at -30/25 °C (evaporating/condensing), inside its published envelope.
Copeland ZF13K4E-TF5 (R407A scroll, 50 Hz, LL)
R407A compressor — 3.4 kW cooling, 1.77 kW input, COP 1.94 at -30/25 °C (evaporating/condensing), inside its published envelope.
Copeland ZF13K4E-TF5 (R407A scroll, 60 Hz, LL)
R407A compressor — 4.1 kW cooling, 2.12 kW input, COP 1.94 at -30/25 °C (evaporating/condensing), inside its published envelope.
Copeland ZF13K4E-TF5 (R407C scroll, 60 Hz, LL)
R407C compressor — 3.8 kW cooling, 2.01 kW input, COP 1.89 at -30/25 °C (evaporating/condensing), inside its published envelope.
Copeland ZF13K4E-TF5 (R407F scroll, 50 Hz, LL)
R407F compressor — 3.4 kW cooling, 1.77 kW input, COP 1.94 at -30/25 °C (evaporating/condensing), inside its published envelope.
Copeland ZF13K4E-TF5 (R407F scroll, 60 Hz, LL)
R407F compressor — 4.1 kW cooling, 2.12 kW input, COP 1.94 at -30/25 °C (evaporating/condensing), inside its published envelope.