Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Systems modelled on Baltimore Aircoil's published data

Built in this model on the maker's own published data — not verified by Baltimore Aircoil. Each page names the document it was read from and what the model was held to.

Baltimore Aircoil VT0-12-E cooling tower (12 tons, 53 kW) — modelledBaltimore Aircoil Product & Application Handbook volume VI, Series V engineering data — the model's own row (nominal tonnage, airflow in CFM, fan motor, dimensions) and the sheet's own rating note: a nominal ton is 3 USGPM of water cooled from 95 °F to 85 °F at a 78 °F entering wet-bulb temperature (docs/bac-source.json)
Baltimore Aircoil FXT-0709B-J cooling tower (130 tons, 571 kW) — modelledBaltimore Aircoil Product & Application Handbook volume VI, FXT engineering data — the model's own row (nominal tonnage, airflow in CFM, fan motor, dimensions) and the sheet's own rating note: a nominal ton is 3 USGPM of water cooled from 95 °F to 85 °F at a 78 °F entering wet-bulb temperature (docs/bac-source.json)
Baltimore Aircoil Series 1500 S15E-1285-09LN cooling tower (253 tons, 1.1 MW) — modelledBaltimore Aircoil Product & Application Handbook volume VI, Series 1500 engineering data — the model's own row (nominal tonnage, airflow in CFM, fan motor, dimensions) and the sheet's own rating note: a nominal ton is 3 USGPM of water cooled from 95 °F to 85 °F at a 78 °F entering wet-bulb temperature (docs/bac-source.json)
Baltimore Aircoil VT1-600-P cooling tower (600 tons, 2.6 MW) — modelledBaltimore Aircoil Product & Application Handbook volume VI, Series V engineering data — the model's own row (nominal tonnage, airflow in CFM, fan motor, dimensions) and the sheet's own rating note: a nominal ton is 3 USGPM of water cooled from 95 °F to 85 °F at a 78 °F entering wet-bulb temperature (docs/bac-source.json)
Baltimore Aircoil Series 3000 S3E-1222-06N cooling tower (471 tons, 2.1 MW) — modelledBaltimore Aircoil Product & Application Handbook volume VI, Series 3000 engineering data — the model's own row (nominal tonnage, airflow in CFM, fan motor, dimensions) and the sheet's own rating note: a nominal ton is 3 USGPM of water cooled from 95 °F to 85 °F at a 78 °F entering wet-bulb temperature (docs/bac-source.json)
Baltimore Aircoil VFL-036-32M closed-circuit cooler (56 tons, 246 kW) — modelledBaltimore Aircoil Product & Application Handbook volume VI, Series V closed circuit engineering data — the model's own row (nominal tonnage, airflow in CFM, fan motor, dimensions) and the sheet's own rating note: a nominal ton is 3 USGPM of water cooled from 95 °F to 85 °F at a 78 °F entering wet-bulb temperature (docs/bac-source.json)

Listings

All kindsCooling tower 677
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 73–96 of 677

Baltimore Aircoil Series 1500 S15E-1218-10KN cooling tower

Cooling tower — 2458 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 60.2 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-10KN-2 cooling tower

Cooling tower — 4916 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 120.4 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-10LC cooling tower

Cooling tower — 2629 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 64.2 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-10LC-2 cooling tower

Cooling tower — 5258 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 128.4 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-10LN cooling tower

Cooling tower — 2756 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 67.8 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-10LN-2 cooling tower

Cooling tower — 5512 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 135.6 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-10MN cooling tower

Cooling tower — 3041 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 73.9 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-10MN-2 cooling tower

Cooling tower — 6081 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 147.7 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-11KN cooling tower

Cooling tower — 2559 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 62.3 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-11KN-2 cooling tower

Cooling tower — 5117 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 124.7 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-11LC cooling tower

Cooling tower — 2738 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 66.5 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-11LC-2 cooling tower

Cooling tower — 5477 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 133.0 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-11LN cooling tower

Cooling tower — 2870 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 70.2 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-11LN-2 cooling tower

Cooling tower — 5740 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 140.5 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-11MN cooling tower

Cooling tower — 3163 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 76.4 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-11MN-2 cooling tower

Cooling tower — 6327 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 152.9 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-12KN cooling tower

Cooling tower — 2651 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 64.3 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-12KN-2 cooling tower

Cooling tower — 5301 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 128.5 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-12LC cooling tower

Cooling tower — 2835 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 68.5 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-12LC-2 cooling tower

Cooling tower — 5670 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 137.0 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-12LN cooling tower

Cooling tower — 2971 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 72.4 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-12LN-2 cooling tower

Cooling tower — 5941 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 144.7 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-12MN cooling tower

Cooling tower — 3273 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 78.7 m³/s of air.

catalog
Cooling tower

Baltimore Aircoil Series 1500 S15E-1218-12MN-2 cooling tower

Cooling tower — 6546 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 157.5 m³/s of air.

catalog
Cooling tower