Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 49–72 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
Midea V6 MV6-560WV2GN1 (20 HP, 56 kW) — modelled Example modelled from published data
Midea's 20 HP V6 outdoor unit as this model runs it: two catalog R410A inverter scrolls behind an air-cooled condenser, modulated to the rated 56.0 kW the way the control runs it, within +0.5 to +3.6 % of Midea's published power input from 25 to 35 °C outdoor at the 100 % combination ratio. Modelled from the maker's published data — not verified by the manufacturer. Published as an example; the figures below are solved from this model.
HVAC BuilderVRF / multi-split55–80 kWEUOpen in the builder
KeepRite Refrigeration KEZA150L8 low-temperature scroll condensing unit (Copeland ZF49K5E, R448A) — modelled Example modelled from published data
KeepRite's KEZA150L8, a two-fan air-cooled scroll condensing unit for a walk-in freezer, as this model runs it: the Copeland ZF49K5E its manual names — the catalog's own map, the low-temperature scroll the example freezer unit runs — on R448A, an air-cooled condenser on the cabinet's face, its fins louvered for the enhanced tube and fin the manual names, and the two fans (800 W) that draw air through it. The condenser's airflow is the one figure fitted, on the manual's R404A cell nearest AHRI 1250's freezer rating point (−20 °F suction on a 95 °F day, 53 100 Btu/h), and it stands for the condenser's conductance, not for air: the 10 080 cfm it comes to takes about three times the air power the printed fans could give through that coil, so the fans could not move it — read at the compressor's own rating basis, the tables ask more of the condenser than this model's coil gives behind those fans, as nearly every freezer table in the manual does. That same condenser holds all 162 cells the manual prints for this unit on R404A, R407A and R448A within −5.3 to +2.8 % (RMS 2.5 %). At −20 °F suction on a 95 °F day it gives 14.40 kW on R448A, against the 50 900 Btu/h (14.92 kW) printed. Modelled from the maker's published data — not verified by the manufacturer. Published as an example; the figures below are solved from this model.
HVAC BuilderCondensing unit11–18 kWNAOpen in the builder
Cooling Tower Systems T-2100 cooling tower (76 tons, 336 kW) — modelled Example modelled from published data
CTS's T-2100 — a T-2 cooling tower, 76 tons (336 kW): rated to cool 230 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 11.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one rated point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Cooling Tower Systems. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection252–420 kWNAOpen in the builder
VRF outdoor unit, 56 kW (20 HP) Example
A variable-refrigerant-flow outdoor unit: two Copeland JPV066AC inverter scrolls on R410A behind an air-cooled condenser, with an open suction and liquid line so any number of indoor units can be coupled to it. Sized and held to a maker's published 20 HP capacity grid — it makes that maker's rated 56.0 kW from 25 to 35 °C outdoor within +0.5 to +3.6 % on power input, with the compressor at 0.62 to 0.70 of full output the way an inverter does. The design point below is the machine flat out, which is the larger figure — and it moves a few kilowatts with the property backend, which is why the advertised band is wide. Published as an example; the figures below are solved from this model.
HVAC BuilderVRF / multi-split55–80 kWEUOpen in the builder
EVAPCO ATWB 10-3I12 closed-circuit cooler (155 tons, 681 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 10-3I12 — an ATWB closed-circuit cooler, 155 nominal tons (681 kW): rated to cool 389 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 26.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection511–851 kWEUOpen in the builder
American Cooling Tower ACC-106F cooling tower (128 tons, 561 kW) — modelled Example modelled from published data CTI STD-201 (validation C38E-25R00) ✓
American Cooling Tower's ACC-106F — an ACC cooling tower, 128 nominal tons (561 kW): rated to cool 384 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection421–701 kWNAOpen in the builder
Baltimore Aircoil FXT-0506A-E cooling tower (46 tons, 202 kW) — modelled Example modelled from published data
BAC's FXT-0506A-E — an FXT cooling tower, 46 nominal tons (202 kW): rated to cool 138 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 6.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection151–252 kWEUOpen in the builder
Cooling Tower Systems T-2125 cooling tower (96 tons, 422 kW) — modelled Example modelled from published data
CTS's T-2125 — a T-2 cooling tower, 96 tons (422 kW): rated to cool 289 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 13.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one rated point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Cooling Tower Systems. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection317–528 kWNAOpen in the builder
EVAPCO AT 110-2I18 cooling tower (289 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 110-2I18 — an AT cooling tower, 289 nominal tons (1271 kW): rated to cool 870 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 40.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection953–1588 kWEUOpen in the builder
American Cooling Tower ACX-1012-1 cooling tower (117 tons, 513 kW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-1012-1 — an ACX cooling tower, 117 nominal tons (513 kW): rated to cool 351 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 17.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection384–641 kWNAOpen in the builder
Baltimore Aircoil FXV-0806A-12D-K closed-circuit cooler (39 tons, 171 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0806A-12D-K — an FXV closed-circuit cooler, 39 nominal tons (171 kW): rated to cool 117 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 15.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection128–214 kWEUOpen in the builder
Cooling Tower Systems T-215 cooling tower (11 tons, 48 kW) — modelled Example modelled from published data
CTS's T-215 — a T-2 cooling tower, 11 tons (48 kW): rated to cool 33 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 2.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one rated point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Cooling Tower Systems. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection36–60 kWNAOpen in the builder
EVAPCO ATWB 10-3I36 closed-circuit cooler (461 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 10-3I36 — an ATWB closed-circuit cooler, 461 nominal tons (2025 kW): rated to cool 1155 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 69.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1519–2531 kWEUOpen in the builder
American Cooling Tower ACC-45B cooling tower (24 tons, 105 kW) — modelled Example modelled from published data CTI STD-201 (validation C38E-25R00) ✓
American Cooling Tower's ACC-45B — an ACC cooling tower, 24 nominal tons (105 kW): rated to cool 72 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 4.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection79–131 kWNAOpen in the builder
Baltimore Aircoil Nexus NXF-0403N-CS2TT-H1 closed-circuit cooler (20 tons, 88 kW) — modelled Example modelled from published data CTI STD-201 (validation C11Q-18R02) ✓
BAC's NXF-0403N-CS2TT-H1 — a Nexus closed-circuit cooler, 20 nominal tons (88 kW): rated to cool 60 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 4.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection66–110 kWEUOpen in the builder
Cooling Tower Systems T-2150 cooling tower (117 tons, 516 kW) — modelled Example modelled from published data
CTS's T-2150 — a T-2 cooling tower, 117 tons (516 kW): rated to cool 353 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 15.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one rated point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Cooling Tower Systems. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection387–644 kWNAOpen in the builder
EVAPCO AT 110-2J12 cooling tower (275 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 110-2J12 — an AT cooling tower, 275 nominal tons (1209 kW): rated to cool 828 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection907–1512 kWEUOpen in the builder
American Cooling Tower ACX-1013-1 cooling tower (139 tons, 609 kW) — modelled Example modelled from published data CTI STD-201 (validation C38C-18R02) ✓
American Cooling Tower's ACX-1013-1 — an ACX cooling tower, 139 nominal tons (609 kW): rated to cool 417 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection457–761 kWNAOpen in the builder
Baltimore Aircoil PCC-0046-0406N003 evaporative condenser (279 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0046-0406N003 — a PCC evaporative condenser rejecting 279 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 6.3 m³/s of the maker's own printed air, with a 2.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection209–349 kWEUOpen in the builder
Cooling Tower Systems T-2175 cooling tower (135 tons, 594 kW) — modelled Example modelled from published data
CTS's T-2175 — a T-2 cooling tower, 135 tons (594 kW): rated to cool 407 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 19.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one rated point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Cooling Tower Systems. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection446–743 kWNAOpen in the builder
EVAPCO ATWB 10-3J36 closed-circuit cooler (529 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 10-3J36 — an ATWB closed-circuit cooler, 529 nominal tons (2326 kW): rated to cool 1327 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 79.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1744–2907 kWEUOpen in the builder
American Cooling Tower ACC-45C cooling tower (31 tons, 136 kW) — modelled Example modelled from published data CTI STD-201 (validation C38E-25R00) ✓
American Cooling Tower's ACC-45C — an ACC cooling tower, 31 nominal tons (136 kW): rated to cool 93 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 6.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection102–170 kWNAOpen in the builder
Baltimore Aircoil PFI-0406N-3D1DZ-G1 closed-circuit cooler (18 tons, 79 kW) — modelled Example modelled from published data
BAC's PFI-0406N-3D1DZ-G1 — a PFi closed-circuit cooler, 18 nominal tons (79 kW): rated to cool 54 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 6.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection59–99 kWEUOpen in the builder
Cooling Tower Systems T-220 cooling tower (15 tons, 66 kW) — modelled Example modelled from published data
CTS's T-220 — a T-2 cooling tower, 15 tons (66 kW): rated to cool 45 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 3.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one rated point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Cooling Tower Systems. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection49–82 kWNAOpen in the builder
‹ Previous12345…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers