992 listing(s) in HVAC Builder's catalog from EVAPCO's published data and 992 system(s) modelled on it — 0 built by hand and 992 derived from the listings themselves — selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; EVAPCO has not claimed it.

Are you EVAPCO?

Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Listings

All kindsCooling tower 992
Any certificationCTI STD-201 (validation C13A-99R28) 822
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 409–432 of 992

EVAPCO AT 214-2J9 cooling tower

Cooling tower — 1498 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 42.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-2K12 cooling tower

Cooling tower — 1954 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 58.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-2K14 cooling tower

Cooling tower — 2598 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 65.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-2K48 cooling tower

Cooling tower — 5280 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 148.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-2L14 cooling tower

Cooling tower — 2064 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 70.7 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-2L48 cooling tower

Cooling tower — 5854 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 158.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-2M48 cooling tower

Cooling tower — 6178 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 168.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-2N48 cooling tower

Cooling tower — 6690 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 184.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-2O48 cooling tower

Cooling tower — 7190 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 198.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3G18 cooling tower

Cooling tower — 2226 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 61.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3G9 cooling tower

Cooling tower — 1135 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 29.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3H12 cooling tower

Cooling tower — 1569 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 42.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3H14 cooling tower

Cooling tower — 1665 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 47.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3H18 cooling tower

Cooling tower — 2616 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 69.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3H9 cooling tower

Cooling tower — 1328 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 33.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3I12 cooling tower

Cooling tower — 1735 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 46.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3I14 cooling tower

Cooling tower — 2296 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 52.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3I18 cooling tower

Cooling tower — 2896 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 76.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3I9 cooling tower

Cooling tower — 1472 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 36.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3J12 cooling tower

Cooling tower — 1998 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 52.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3J14 cooling tower

Cooling tower — 2178 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 59.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3J18 cooling tower

Cooling tower — 3330 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 86.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3J9 cooling tower

Cooling tower — 1687 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 41.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 214-3K12 cooling tower

Cooling tower — 2208 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 57.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower
‹ Previous1…1617181920…42Next ›

How the model reads against EVAPCO's data

Cooling-tower model, zero fitted parameters856mean −0.03 K, RMS 0.064 K, worst 0.24 K — NTU from the vendor's own Eurovent column, the shipped default exponent (−0.7, the joint minimum with Marley's table)
Cooling-tower model against a fourth maker's whole open-tower range, nothing fitted to it45 945 over 992 machinesmean −0.083 K, RMS 0.220 K, worst 1.89 K on leaving water. 0.098 K at the 78 °F rating wet bulb, where the NTU is derived, rising to 0.283 and 0.288 K at 50 and 90 °F. The fill's loading exponent was swept on either half of the range and the shipped default (−0.7, the joint minimum of EVAPCO's own LPT bulletin and Marley's table) is the minimum for this range too, so it carries no constant of its own — unlike BAC's five, which wanted −0.9 to −1.3

From the validation page; every row is held by a test.

Worked cases that run EVAPCO machines

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.