Companies

EVAPCO Unclaimed

992 listing(s) in HVAC Builder's catalog from EVAPCO's published data and 992 system(s) modelled on it — 0 built by hand and 992 derived from the listings themselves — selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; EVAPCO has not claimed it.

Are you EVAPCO?

Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Listings

All kindsCooling tower 992
Any certificationCTI STD-201 (validation C13A-99R28) 822
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 361–384 of 992

EVAPCO AT 212-3N28 cooling tower

Cooling tower — 4806 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 111.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-3N36 cooling tower

Cooling tower — 5915 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 139.3 m³/s of air.

catalog
Cooling tower

EVAPCO AT 212-3N40 cooling tower

Cooling tower — 6116 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 142.0 m³/s of air.

catalog
Cooling tower

EVAPCO AT 212-3O36 cooling tower

Cooling tower — 6344 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 149.6 m³/s of air.

catalog
Cooling tower

EVAPCO AT 212-3O40 cooling tower

Cooling tower — 6638 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 152.3 m³/s of air.

catalog
Cooling tower

EVAPCO AT 212-4F9 cooling tower

Cooling tower — 960 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 20.7 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4G9 cooling tower

Cooling tower — 1148 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 24.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4H9 cooling tower

Cooling tower — 1257 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 27.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4I24 cooling tower

Cooling tower — 2953 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 65.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4I28 cooling tower

Cooling tower — 3247 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 71.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4I9 cooling tower

Cooling tower — 1380 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 30.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4J24 cooling tower

Cooling tower — 3396 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 74.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4J28 cooling tower

Cooling tower — 3737 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 80.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4J36 cooling tower

Cooling tower — 4535 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 100.7 m³/s of air.

catalog
Cooling tower

EVAPCO AT 212-4J9 cooling tower

Cooling tower — 1507 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 34.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4K24 cooling tower

Cooling tower — 3694 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 81.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4K28 cooling tower

Cooling tower — 4035 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 88.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4K36 cooling tower

Cooling tower — 5017 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 110.2 m³/s of air.

catalog
Cooling tower

EVAPCO AT 212-4K40 cooling tower

Cooling tower — 5008 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 112.5 m³/s of air.

catalog
Cooling tower

EVAPCO AT 212-4L24 cooling tower

Cooling tower — 3978 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 87.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4L28 cooling tower

Cooling tower — 4324 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 95.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 212-4L36 cooling tower

Cooling tower — 5315 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 118.4 m³/s of air.

catalog
Cooling tower

EVAPCO AT 212-4L40 cooling tower

Cooling tower — 5411 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 120.7 m³/s of air.

catalog
Cooling tower

EVAPCO AT 212-4M24 cooling tower

Cooling tower — 4219 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 92.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower
‹ Previous1…1415161718…42Next ›

How the model reads against EVAPCO's data

Cooling-tower model, zero fitted parameters856mean −0.03 K, RMS 0.064 K, worst 0.24 K — NTU from the vendor's own Eurovent column, the shipped default exponent (−0.7, the joint minimum with Marley's table)
Cooling-tower model against a fourth maker's whole open-tower range, nothing fitted to it45 945 over 992 machinesmean −0.083 K, RMS 0.220 K, worst 1.89 K on leaving water. 0.098 K at the 78 °F rating wet bulb, where the NTU is derived, rising to 0.283 and 0.288 K at 50 and 90 °F. The fill's loading exponent was swept on either half of the range and the shipped default (−0.7, the joint minimum of EVAPCO's own LPT bulletin and Marley's table) is the minimum for this range too, so it carries no constant of its own — unlike BAC's five, which wanted −0.9 to −1.3

From the validation page; every row is held by a test.

Worked cases that run EVAPCO machines

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.