992 listing(s) in HVAC Builder's catalog from EVAPCO's published data and 992 system(s) modelled on it — 0 built by hand and 992 derived from the listings themselves — selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; EVAPCO has not claimed it.
Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page
Showing 673–696 of 992
Cooling tower — 2909 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 76.8 m³/s of air.
Cooling tower — 2029 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 53.0 m³/s of air.
Cooling tower — 2182 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 59.2 m³/s of air.
Cooling tower — 3343 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 87.2 m³/s of air.
Cooling tower — 2239 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 58.0 m³/s of air.
Cooling tower — 2782 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 64.8 m³/s of air.
Cooling tower — 3698 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 95.4 m³/s of air.
Cooling tower — 2423 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 62.2 m³/s of air.
Cooling tower — 2344 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 69.4 m³/s of air.
Cooling tower — 2738 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 73.5 m³/s of air.
Cooling tower — 2489 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 60.6 m³/s of air.
Cooling tower — 1744 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 41.9 m³/s of air.
Cooling tower — 1928 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 46.7 m³/s of air.
Cooling tower — 2852 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 68.9 m³/s of air.
Cooling tower — 1910 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 45.9 m³/s of air.
Cooling tower — 1709 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 51.2 m³/s of air.
Cooling tower — 3111 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 75.5 m³/s of air.
Cooling tower — 2156 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 52.2 m³/s of air.
Cooling tower — 2414 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 58.2 m³/s of air.
Cooling tower — 3514 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 85.8 m³/s of air.
Cooling tower — 2353 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 57.1 m³/s of air.
Cooling tower — 1897 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 63.7 m³/s of air.
Cooling tower — 3834 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 93.8 m³/s of air.
Cooling tower — 2515 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 61.2 m³/s of air.
| Cooling-tower model, zero fitted parameters | 856 | mean −0.03 K, RMS 0.064 K, worst 0.24 K — NTU from the vendor's own Eurovent column, the shipped default exponent (−0.7, the joint minimum with Marley's table) |
| Cooling-tower model against a fourth maker's whole open-tower range, nothing fitted to it | 45 945 over 992 machines | mean −0.083 K, RMS 0.220 K, worst 1.89 K on leaving water. 0.098 K at the 78 °F rating wet bulb, where the NTU is derived, rising to 0.283 and 0.288 K at 50 and 90 °F. The fill's loading exponent was swept on either half of the range and the shipped default (−0.7, the joint minimum of EVAPCO's own LPT bulletin and Marley's table) is the minimum for this range too, so it carries no constant of its own — unlike BAC's five, which wanted −0.9 to −1.3 |
From the validation page; every row is held by a test.
Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.