992 listing(s) in HVAC Builder's catalog from EVAPCO's published data and 992 system(s) modelled on it — 0 built by hand and 992 derived from the listings themselves — selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; EVAPCO has not claimed it.
Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page
Showing 169–192 of 992
Cooling tower — 1704 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 42.6 m³/s of air.
Cooling tower — 846 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 21.1 m³/s of air.
Cooling tower — 1130 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 29.1 m³/s of air.
Cooling tower — 1406 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 31.9 m³/s of air.
Cooling tower — 1884 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 46.6 m³/s of air.
Cooling tower — 933 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 23.1 m³/s of air.
Cooling tower — 1222 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 31.2 m³/s of air.
Cooling tower — 1183 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 34.2 m³/s of air.
Cooling tower — 1380 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 36.2 m³/s of air.
Cooling tower — 1266 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 29.6 m³/s of air.
Cooling tower — 627 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 14.7 m³/s of air.
Cooling tower — 881 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 21.0 m³/s of air.
Cooling tower — 977 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 23.0 m³/s of air.
Cooling tower — 1455 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 33.7 m³/s of air.
Cooling tower — 719 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 16.7 m³/s of air.
Cooling tower — 964 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 23.0 m³/s of air.
Cooling tower — 863 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 25.2 m³/s of air.
Cooling tower — 1586 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 36.9 m³/s of air.
Cooling tower — 784 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 18.3 m³/s of air.
Cooling tower — 1091 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 26.2 m³/s of air.
Cooling tower — 1222 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 28.6 m³/s of air.
Cooling tower — 1788 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 41.9 m³/s of air.
Cooling tower — 885 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 20.8 m³/s of air.
Cooling tower — 1187 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 28.6 m³/s of air.
| Cooling-tower model, zero fitted parameters | 856 | mean −0.03 K, RMS 0.064 K, worst 0.24 K — NTU from the vendor's own Eurovent column, the shipped default exponent (−0.7, the joint minimum with Marley's table) |
| Cooling-tower model against a fourth maker's whole open-tower range, nothing fitted to it | 45 945 over 992 machines | mean −0.083 K, RMS 0.220 K, worst 1.89 K on leaving water. 0.098 K at the 78 °F rating wet bulb, where the NTU is derived, rising to 0.283 and 0.288 K at 50 and 90 °F. The fill's loading exponent was swept on either half of the range and the shipped default (−0.7, the joint minimum of EVAPCO's own LPT bulletin and Marley's table) is the minimum for this range too, so it carries no constant of its own — unlike BAC's five, which wanted −0.9 to −1.3 |
From the validation page; every row is held by a test.
Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.