Companies

EVAPCO Unclaimed

992 listing(s) in HVAC Builder's catalog from EVAPCO's published data and 992 system(s) modelled on it — 0 built by hand and 992 derived from the listings themselves — selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; EVAPCO has not claimed it.

Are you EVAPCO?

Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Listings

All kindsCooling tower 992
Any certificationCTI STD-201 (validation C13A-99R28) 822
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 193–216 of 992

EVAPCO AT 17-4K14 cooling tower

Cooling tower — 960 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 31.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 17-4K18 cooling tower

Cooling tower — 1950 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 45.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 17-4K9 cooling tower

Cooling tower — 964 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 22.7 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 17-4L12 cooling tower

Cooling tower — 1271 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 30.7 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 17-4L14 cooling tower

Cooling tower — 1293 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 33.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 17-4M14 cooling tower

Cooling tower — 1459 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 35.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2F6 cooling tower

Cooling tower — 390 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 10.7 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2F8 cooling tower

Cooling tower — 478 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 12.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2G11 cooling tower

Cooling tower — 683 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 19.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2G6 cooling tower

Cooling tower — 491 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 12.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2G8 cooling tower

Cooling tower — 600 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 14.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2G9 cooling tower

Cooling tower — 591 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 16.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2H11 cooling tower

Cooling tower — 819 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 21.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2H12 cooling tower

Cooling tower — 889 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 23.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2H14 cooling tower

Cooling tower — 968 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 26.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2H6 cooling tower

Cooling tower — 539 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 14.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2H8 cooling tower

Cooling tower — 648 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 16.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2H9 cooling tower

Cooling tower — 710 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 19.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2I11 cooling tower

Cooling tower — 885 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 23.7 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2I12 cooling tower

Cooling tower — 1008 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 26.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2I14 cooling tower

Cooling tower — 1100 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 28.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2I8 cooling tower

Cooling tower — 697 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 18.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2I9 cooling tower

Cooling tower — 780 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 21.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-2J11 cooling tower

Cooling tower — 1012 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 26.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower
‹ Previous1…7891011…42Next ›

How the model reads against EVAPCO's data

Cooling-tower model, zero fitted parameters856mean −0.03 K, RMS 0.064 K, worst 0.24 K — NTU from the vendor's own Eurovent column, the shipped default exponent (−0.7, the joint minimum with Marley's table)
Cooling-tower model against a fourth maker's whole open-tower range, nothing fitted to it45 945 over 992 machinesmean −0.083 K, RMS 0.220 K, worst 1.89 K on leaving water. 0.098 K at the 78 °F rating wet bulb, where the NTU is derived, rising to 0.283 and 0.288 K at 50 and 90 °F. The fill's loading exponent was swept on either half of the range and the shipped default (−0.7, the joint minimum of EVAPCO's own LPT bulletin and Marley's table) is the minimum for this range too, so it carries no constant of its own — unlike BAC's five, which wanted −0.9 to −1.3

From the validation page; every row is held by a test.

Worked cases that run EVAPCO machines

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.