992 listing(s) in HVAC Builder's catalog from EVAPCO's published data and 992 system(s) modelled on it — 0 built by hand and 992 derived from the listings themselves — selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; EVAPCO has not claimed it.

Are you EVAPCO?

Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Listings

All kindsCooling tower 992
Any certificationCTI STD-201 (validation C13A-99R28) 822
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 241–264 of 992

EVAPCO AT 19-3J11 cooling tower

Cooling tower — 1122 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 26.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-3J12 cooling tower

Cooling tower — 1266 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 29.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-3J14 cooling tower

Cooling tower — 1380 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 32.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-3J8 cooling tower

Cooling tower — 863 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 20.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-3J9 cooling tower

Cooling tower — 1016 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 23.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-3K11 cooling tower

Cooling tower — 1249 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 28.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-3K12 cooling tower

Cooling tower — 1398 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 32.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-3K14 cooling tower

Cooling tower — 1520 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 35.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-3L12 cooling tower

Cooling tower — 1490 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 34.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-3L14 cooling tower

Cooling tower — 1652 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 37.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-3M14 cooling tower

Cooling tower — 1748 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 40.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4F6 cooling tower

Cooling tower — 478 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 10.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4F8 cooling tower

Cooling tower — 583 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 12.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4G11 cooling tower

Cooling tower — 832 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 18.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4G6 cooling tower

Cooling tower — 570 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 12.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4G8 cooling tower

Cooling tower — 697 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 14.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4G9 cooling tower

Cooling tower — 723 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 16.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4H11 cooling tower

Cooling tower — 964 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 20.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4H12 cooling tower

Cooling tower — 1065 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 23.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4H14 cooling tower

Cooling tower — 1165 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 25.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4H6 cooling tower

Cooling tower — 627 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 13.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4H8 cooling tower

Cooling tower — 758 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 16.3 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4H9 cooling tower

Cooling tower — 837 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 18.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 19-4I11 cooling tower

Cooling tower — 1043 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 22.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower
‹ Previous1…910111213…42Next ›

How the model reads against EVAPCO's data

Cooling-tower model, zero fitted parameters856mean −0.03 K, RMS 0.064 K, worst 0.24 K — NTU from the vendor's own Eurovent column, the shipped default exponent (−0.7, the joint minimum with Marley's table)
Cooling-tower model against a fourth maker's whole open-tower range, nothing fitted to it45 945 over 992 machinesmean −0.083 K, RMS 0.220 K, worst 1.89 K on leaving water. 0.098 K at the 78 °F rating wet bulb, where the NTU is derived, rising to 0.283 and 0.288 K at 50 and 90 °F. The fill's loading exponent was swept on either half of the range and the shipped default (−0.7, the joint minimum of EVAPCO's own LPT bulletin and Marley's table) is the minimum for this range too, so it carries no constant of its own — unlike BAC's five, which wanted −0.9 to −1.3

From the validation page; every row is held by a test.

Worked cases that run EVAPCO machines

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.