992 listing(s) in HVAC Builder's catalog from EVAPCO's published data and 992 system(s) modelled on it — 0 built by hand and 992 derived from the listings themselves — selectable in the builder and solved with the catalog's own figures. This page is listed by HVAC Builder from published data; EVAPCO has not claimed it.

Are you EVAPCO?

Claim this page from the app's Company page: register as a supplier (company name and contact email), open the Profile sub-tab and claim the brand. The page and its listings are then yours — attributed to your company, quote requests for designs that use them reach whoever you name with the design attached, and any listing is yours to edit or withdraw. No charge, no commission. Open the Company page

Listings

All kindsCooling tower 992
Any certificationCTI STD-201 (validation C13A-99R28) 822
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 289–312 of 992

EVAPCO AT 210-2K24 cooling tower

Cooling tower — 2677 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 76.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-2K36 cooling tower

Cooling tower — 3413 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 101.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-2L24 cooling tower

Cooling tower — 2852 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 81.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-2L36 cooling tower

Cooling tower — 3680 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 108.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-2M24 cooling tower

Cooling tower — 2997 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 86.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-2M36 cooling tower

Cooling tower — 3899 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 115.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3I24 cooling tower

Cooling tower — 2318 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 60.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3I36 cooling tower

Cooling tower — 2922 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 79.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3J24 cooling tower

Cooling tower — 2708 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 68.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3J36 cooling tower

Cooling tower — 3461 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 90.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3K24 cooling tower

Cooling tower — 2962 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 74.7 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3K36 cooling tower

Cooling tower — 3825 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 99.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3L24 cooling tower

Cooling tower — 3163 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 80.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3L36 cooling tower

Cooling tower — 4123 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 106.8 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3M24 cooling tower

Cooling tower — 3330 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 84.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3M36 cooling tower

Cooling tower — 4368 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 113.0 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-3N36 cooling tower

Cooling tower — 4789 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 123.7 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-4I24 cooling tower

Cooling tower — 2432 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 59.1 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-4I36 cooling tower

Cooling tower — 3185 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 78.6 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-4J24 cooling tower

Cooling tower — 2822 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 67.2 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-4J36 cooling tower

Cooling tower — 3676 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 89.4 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-4K24 cooling tower

Cooling tower — 3071 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 73.5 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-4K36 cooling tower

Cooling tower — 4035 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 97.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower

EVAPCO AT 210-4L24 cooling tower

Cooling tower — 3269 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 78.9 m³/s of air.

catalogCTI STD-201 (validation C13A-99R28) ✓
Cooling tower
‹ Previous1…1112131415…42Next ›

How the model reads against EVAPCO's data

Cooling-tower model, zero fitted parameters856mean −0.03 K, RMS 0.064 K, worst 0.24 K — NTU from the vendor's own Eurovent column, the shipped default exponent (−0.7, the joint minimum with Marley's table)
Cooling-tower model against a fourth maker's whole open-tower range, nothing fitted to it45 945 over 992 machinesmean −0.083 K, RMS 0.220 K, worst 1.89 K on leaving water. 0.098 K at the 78 °F rating wet bulb, where the NTU is derived, rising to 0.283 and 0.288 K at 50 and 90 °F. The fill's loading exponent was swept on either half of the range and the shipped default (−0.7, the joint minimum of EVAPCO's own LPT bulletin and Marley's table) is the minimum for this range too, so it carries no constant of its own — unlike BAC's five, which wanted −0.9 to −1.3

From the validation page; every row is held by a test.

Worked cases that run EVAPCO machines

Listed from published data with the source named on every entry; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.