Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 3,097–3,120 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| Baltimore Aircoil Series 1500 XES15E-1218-11HN cooling tower (468 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1218-11HN — a Series 1500 cooling tower, 468 nominal tons (2059 kW): rated to cool 1410 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1544–2574 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1222-13K cooling tower (543 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1222-13K — a Series 3000 cooling tower, 543 nominal tons (2388 kW): rated to cool 1635 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 62.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1791–2985 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-024-22J closed-circuit cooler (24 tons, 105 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-024-22J — a Series V closed circuit closed-circuit cooler, 24 nominal tons (105 kW): rated to cool 72 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 8.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 79–131 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-S884A evaporative condenser (3.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-S884A — a VCA evaporative condenser rejecting 3807 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 56.6 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2855–4759 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-1131B-1036N-JB evaporative condenser (6.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-1131B-1036N-JB — a Vertex VRC evaporative condenser rejecting 6861 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 98.1 m³/s of the maker's own printed air, with a 79.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5146–8576 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1119-1236N100 evaporative condenser (6.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1119-1236N100 — a PCC evaporative condenser rejecting 6797 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 129.3 m³/s of the maker's own printed air, with a 74.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5098–8497 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1212N-6D1ES-P1 closed-circuit cooler (231 tons, 1.0 MW) — modelled Example modelled from published data BAC's PFI-1212N-6D1ES-P1 — a PFi closed-circuit cooler, 231 nominal tons (1016 kW): rated to cool 696 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 45.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 762–1271 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1218-11JN cooling tower (534 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1218-11JN — a Series 1500 cooling tower, 534 nominal tons (2348 kW): rated to cool 1608 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1761–2936 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1222-13L cooling tower (618 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1222-13L — a Series 3000 cooling tower, 618 nominal tons (2716 kW): rated to cool 1860 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2037–3396 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-024-32H closed-circuit cooler (26 tons, 114 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-024-32H — a Series V closed circuit closed-circuit cooler, 26 nominal tons (114 kW): rated to cool 78 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 7.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 85–142 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-S932A evaporative condenser (4.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-S932A — a VCA evaporative condenser rejecting 4015 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 69.0 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3011–5019 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-1175B-1236N-LA evaporative condenser (7.1 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-1175B-1236N-LA — a Vertex VRC evaporative condenser rejecting 7126 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 115.3 m³/s of the maker's own printed air, with a 67.1 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5344–8907 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1125-1240N060 evaporative condenser (6.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1125-1240N060 — a PCC evaporative condenser rejecting 6834 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 110.2 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5125–8542 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1218N-2D1DS-N1 closed-circuit cooler (165 tons, 727 kW) — modelled Example modelled from published data BAC's PFI-1218N-2D1DS-N1 — a PFi closed-circuit cooler, 165 nominal tons (727 kW): rated to cool 498 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 63.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 545–909 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1218-12EN cooling tower (328 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1218-12EN — a Series 1500 cooling tower, 328 nominal tons (1441 kW): rated to cool 987 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1081–1802 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1222-13M cooling tower (676 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1222-13M — a Series 3000 cooling tower, 676 nominal tons (2971 kW): rated to cool 2034 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2228–3713 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-024-32J closed-circuit cooler (30 tons, 131 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-024-32J — a Series V closed circuit closed-circuit cooler, 30 nominal tons (131 kW): rated to cool 90 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 8.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 99–164 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-S972A evaporative condenser (4.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-S972A — a VCA evaporative condenser rejecting 4187 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 67.4 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3141–5234 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-1198B-1236N-HB evaporative condenser (7.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-1198B-1236N-HB — a Vertex VRC evaporative condenser rejecting 7266 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 94.2 m³/s of the maker's own printed air, with a 51.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5450–9083 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1128-2418N100 evaporative condenser (6.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1128-2418N100 — a PCC evaporative condenser rejecting 6852 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 129.3 m³/s of the maker's own printed air, with a 74.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5139–8565 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1218N-2D2DS-N1 closed-circuit cooler (171 tons, 754 kW) — modelled Example modelled from published data BAC's PFI-1218N-2D2DS-N1 — a PFi closed-circuit cooler, 171 nominal tons (754 kW): rated to cool 516 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 61.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 565–942 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1218-12FN cooling tower (360 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1218-12FN — a Series 1500 cooling tower, 360 nominal tons (1582 kW): rated to cool 1083 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1186–1977 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1222-13N cooling tower (725 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1222-13N — a Series 3000 cooling tower, 725 nominal tons (3185 kW): rated to cool 2181 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 81.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2389–3982 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-036-22K closed-circuit cooler (35 tons, 153 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-036-22K — a Series V closed circuit closed-circuit cooler, 35 nominal tons (153 kW): rated to cool 105 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 11.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 115–192 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers