Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 3,049–3,072 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| Baltimore Aircoil Series 3000 XES3E-1222-10N cooling tower (653 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1222-10N — a Series 3000 cooling tower, 653 nominal tons (2870 kW): rated to cool 1965 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 74.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2152–3587 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-012-12H closed-circuit cooler (9 tons, 39 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-012-12H — a Series V closed circuit closed-circuit cooler, 9 nominal tons (39 kW): rated to cool 27 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 5.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 30–49 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-S1071A evaporative condenser (4.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-S1071A — a VCA evaporative condenser rejecting 4614 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 77.2 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3461–5768 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-1023B-1036N-HB evaporative condenser (6.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-1023B-1036N-HB — a Vertex VRC evaporative condenser rejecting 6205 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 84.5 m³/s of the maker's own printed air, with a 51.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4654–7756 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1073-1236N080 evaporative condenser (6.5 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1073-1236N080 — a PCC evaporative condenser rejecting 6520 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 120.2 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4890–8150 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1212N-5D1DS-O1 closed-circuit cooler (187 tons, 824 kW) — modelled Example modelled from published data BAC's PFI-1212N-5D1DS-O1 — a PFi closed-circuit cooler, 187 nominal tons (824 kW): rated to cool 564 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 43.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 618–1030 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1218-10GN cooling tower (384 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1218-10GN — a Series 1500 cooling tower, 384 nominal tons (1687 kW): rated to cool 1155 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1265–2109 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1222-10O cooling tower (691 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1222-10O — a Series 3000 cooling tower, 691 nominal tons (3036 kW): rated to cool 2079 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2277–3795 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-012-22F closed-circuit cooler (8 tons, 35 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-012-22F — a Series V closed circuit closed-circuit cooler, 8 nominal tons (35 kW): rated to cool 24 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 3.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 26–44 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-S1124A evaporative condenser (4.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-S1124A — a VCA evaporative condenser rejecting 4842 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 76.9 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3632–6053 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-1032B-1236N-JB evaporative condenser (6.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-1032B-1236N-JB — a Vertex VRC evaporative condenser rejecting 6253 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 131.3 m³/s of the maker's own printed air, with a 79.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4690–7816 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1079-1240N080 evaporative condenser (6.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1079-1240N080 — a PCC evaporative condenser rejecting 6556 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 138.4 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4917–8195 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1212N-5D2ES-N1 closed-circuit cooler (198 tons, 872 kW) — modelled Example modelled from published data BAC's PFI-1212N-5D2ES-N1 — a PFi closed-circuit cooler, 198 nominal tons (872 kW): rated to cool 597 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 654–1090 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1218-10HN cooling tower (450 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1218-10HN — a Series 1500 cooling tower, 450 nominal tons (1976 kW): rated to cool 1353 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 48.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1482–2470 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1222-12K cooling tower (526 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1222-12K — a Series 3000 cooling tower, 526 nominal tons (2313 kW): rated to cool 1584 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1735–2892 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-012-22H closed-circuit cooler (11 tons, 48 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-012-22H — a Series V closed circuit closed-circuit cooler, 11 nominal tons (48 kW): rated to cool 33 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 5.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 36–60 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-S1204A evaporative condenser (5.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-S1204A — a VCA evaporative condenser rejecting 5187 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 84.7 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 3890–6484 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-1052B-1036N-JB evaporative condenser (6.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-1052B-1036N-JB — a Vertex VRC evaporative condenser rejecting 6383 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 95.8 m³/s of the maker's own printed air, with a 79.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4787–7978 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1080-2420N060 evaporative condenser (6.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1080-2420N060 — a PCC evaporative condenser rejecting 6560 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 117.9 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 4920–8201 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1212N-5D4DS-O1 closed-circuit cooler (196 tons, 863 kW) — modelled Example modelled from published data BAC's PFI-1212N-5D4DS-O1 — a PFi closed-circuit cooler, 196 nominal tons (863 kW): rated to cool 591 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 647–1079 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1218-10JN cooling tower (512 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1218-10JN — a Series 1500 cooling tower, 512 nominal tons (2252 kW): rated to cool 1542 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 55.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1689–2815 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1222-12L cooling tower (598 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1222-12L — a Series 3000 cooling tower, 598 nominal tons (2629 kW): rated to cool 1800 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1972–3286 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-012-32G closed-circuit cooler (12 tons, 53 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-012-32G — a Series V closed circuit closed-circuit cooler, 12 nominal tons (53 kW): rated to cool 36 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 4.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 39–66 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-S700A evaporative condenser (3.0 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-S700A — a VCA evaporative condenser rejecting 3017 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 52.3 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2263–3772 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers