Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 3,025–3,048 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
Baltimore Aircoil PCC-1054-1236N080 evaporative condenser (6.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1054-1236N080 — a PCC evaporative condenser rejecting 6400 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 120.9 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4800–8000 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-4D2ES-P1 closed-circuit cooler (202 tons, 889 kW) — modelled Example modelled from published data
BAC's PFI-1212N-4D2ES-P1 — a PFi closed-circuit cooler, 202 nominal tons (889 kW): rated to cool 609 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 46.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection667–1112 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1218-09GN cooling tower (365 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1218-09GN — a Series 1500 cooling tower, 365 nominal tons (1604 kW): rated to cool 1098 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 40.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1203–2004 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-1222-10K cooling tower (489 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-1222-10K — a Series 3000 cooling tower, 489 nominal tons (2151 kW): rated to cool 1473 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1613–2689 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VFL-012-02F closed-circuit cooler (4 tons, 18 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VFL-012-02F — a Series V closed circuit closed-circuit cooler, 4 nominal tons (18 kW): rated to cool 12 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 3.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection13–22 kWEUOpen in the builder
Baltimore Aircoil VCA-957A evaporative condenser (4.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-957A — a VCA evaporative condenser rejecting 4123 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 59.5 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3092–5154 kWEUOpen in the builder
Baltimore Aircoil VRC-0977B-1236N-KA evaporative condenser (5.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0977B-1236N-KA — a Vertex VRC evaporative condenser rejecting 5928 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 103.5 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4446–7410 kWEUOpen in the builder
Baltimore Aircoil PCC-1060-2424N060 evaporative condenser (6.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1060-2424N060 — a PCC evaporative condenser rejecting 6439 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 141.3 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4829–8048 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-4D3DS-P1 closed-circuit cooler (193 tons, 850 kW) — modelled Example modelled from published data
BAC's PFI-1212N-4D3DS-P1 — a PFi closed-circuit cooler, 193 nominal tons (850 kW): rated to cool 582 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 45.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection637–1062 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1218-09HN cooling tower (429 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1218-09HN — a Series 1500 cooling tower, 429 nominal tons (1884 kW): rated to cool 1290 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1413–2355 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-1222-10L cooling tower (557 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-1222-10L — a Series 3000 cooling tower, 557 nominal tons (2449 kW): rated to cool 1677 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1837–3061 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VFL-012-02G closed-circuit cooler (5 tons, 22 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VFL-012-02G — a Series V closed circuit closed-circuit cooler, 5 nominal tons (22 kW): rated to cool 15 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 4.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection16–27 kWEUOpen in the builder
Baltimore Aircoil VCA-982A evaporative condenser (4.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-982A — a VCA evaporative condenser rejecting 4230 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 67.2 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3173–5288 kWEUOpen in the builder
Baltimore Aircoil VRC-1004B-1036N-KA evaporative condenser (6.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-1004B-1036N-KA — a Vertex VRC evaporative condenser rejecting 6092 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 88.9 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4569–7615 kWEUOpen in the builder
Baltimore Aircoil PCC-1062-2418N080 evaporative condenser (6.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1062-2418N080 — a PCC evaporative condenser rejecting 6451 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 120.9 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4838–8063 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-4D3ES-M1 closed-circuit cooler (175 tons, 771 kW) — modelled Example modelled from published data
BAC's PFI-1212N-4D3ES-M1 — a PFi closed-circuit cooler, 175 nominal tons (771 kW): rated to cool 528 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 36.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection578–964 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1218-10EN cooling tower (304 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1218-10EN — a Series 1500 cooling tower, 304 nominal tons (1336 kW): rated to cool 915 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1002–1670 kWEUOpen in the builder
Baltimore Aircoil Series 3000 XES3E-1222-10M cooling tower (609 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES3E-1222-10M — a Series 3000 cooling tower, 609 nominal tons (2677 kW): rated to cool 1833 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 69.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2008–3346 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VFL-012-12F closed-circuit cooler (7 tons, 31 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VFL-012-12F — a Series V closed circuit closed-circuit cooler, 7 nominal tons (31 kW): rated to cool 21 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 3.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection23–38 kWEUOpen in the builder
Baltimore Aircoil VCA-S1019A evaporative condenser (4.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-S1019A — a VCA evaporative condenser rejecting 4390 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 72.4 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection3292–5487 kWEUOpen in the builder
Baltimore Aircoil VRC-1020B-1236N-HB evaporative condenser (6.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-1020B-1236N-HB — a Vertex VRC evaporative condenser rejecting 6186 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 108.5 m³/s of the maker's own printed air, with a 51.3 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4640–7733 kWEUOpen in the builder
Baltimore Aircoil PCC-1071-1240N060 evaporative condenser (6.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-1071-1240N060 — a PCC evaporative condenser rejecting 6508 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 117.9 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4881–8135 kWEUOpen in the builder
Baltimore Aircoil PFI-1212N-4D4ES-N1 closed-circuit cooler (187 tons, 824 kW) — modelled Example modelled from published data
BAC's PFI-1212N-4D4ES-N1 — a PFi closed-circuit cooler, 187 nominal tons (824 kW): rated to cool 564 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 37.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection618–1030 kWEUOpen in the builder
Baltimore Aircoil Series 1500 XES15E-1218-10FN cooling tower (334 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's XES15E-1218-10FN — a Series 1500 cooling tower, 334 nominal tons (1468 kW): rated to cool 1005 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1101–1835 kWEUOpen in the builder
‹ Previous1…125126127128129…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers