Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 3,169–3,192 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| Baltimore Aircoil Series 1500 XES15E-1285-07FN cooling tower (111 tons, 486 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1285-07FN — a Series 1500 cooling tower, 111 nominal tons (486 kW): rated to cool 333 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 12.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 365–608 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1424-07M cooling tower (543 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1424-07M — a Series 3000 cooling tower, 543 nominal tons (2388 kW): rated to cool 1635 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1791–2985 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-048-41L closed-circuit cooler (49 tons, 215 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-048-41L — a Series V closed circuit closed-circuit cooler, 49 nominal tons (215 kW): rated to cool 147 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 13.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 161–268 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1173-1240N080 evaporative condenser (7.1 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1173-1240N080 — a PCC evaporative condenser rejecting 7123 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 127.6 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5342–8904 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1218N-3D1DS-O1 closed-circuit cooler (219 tons, 964 kW) — modelled Example modelled from published data BAC's PFI-1218N-3D1DS-O1 — a PFi closed-circuit cooler, 219 nominal tons (964 kW): rated to cool 660 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 63.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 723–1205 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1285-07GN cooling tower (128 tons, 561 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1285-07GN — a Series 1500 cooling tower, 128 nominal tons (561 kW): rated to cool 384 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 421–701 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1424-07N cooling tower (583 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1424-07N — a Series 3000 cooling tower, 583 nominal tons (2563 kW): rated to cool 1755 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1922–3204 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-072-22N closed-circuit cooler (69 tons, 302 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-072-22N — a Series V closed circuit closed-circuit cooler, 69 nominal tons (302 kW): rated to cool 207 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 21.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 227–378 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1180-2418N100 evaporative condenser (7.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1180-2418N100 — a PCC evaporative condenser rejecting 7168 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 120.9 m³/s of the maker's own printed air, with a 74.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5376–8960 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1218N-3D1ES-R1 closed-circuit cooler (271 tons, 1.2 MW) — modelled Example modelled from published data BAC's PFI-1218N-3D1ES-R1 — a PFi closed-circuit cooler, 271 nominal tons (1192 kW): rated to cool 816 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 76.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 894–1490 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1285-07HN cooling tower (150 tons, 657 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1285-07HN — a Series 1500 cooling tower, 150 nominal tons (657 kW): rated to cool 450 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 16.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 493–822 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1424-12L cooling tower (689 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1424-12L — a Series 3000 cooling tower, 689 nominal tons (3028 kW): rated to cool 2073 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2271–3784 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-072-22O closed-circuit cooler (75 tons, 329 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-072-22O — a Series V closed circuit closed-circuit cooler, 75 nominal tons (329 kW): rated to cool 225 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 22.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 246–411 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1182-2420N080 evaporative condenser (7.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1182-2420N080 — a PCC evaporative condenser rejecting 7180 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 127.6 m³/s of the maker's own printed air, with a 59.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5385–8975 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1218N-3D2DS-M1 closed-circuit cooler (208 tons, 916 kW) — modelled Example modelled from published data BAC's PFI-1218N-3D2DS-M1 — a PFi closed-circuit cooler, 208 nominal tons (916 kW): rated to cool 627 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 54.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 687–1145 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1285-07JN cooling tower (173 tons, 762 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1285-07JN — a Series 1500 cooling tower, 173 nominal tons (762 kW): rated to cool 522 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 19.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 572–953 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1424-12M cooling tower (752 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1424-12M — a Series 3000 cooling tower, 752 nominal tons (3308 kW): rated to cool 2265 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2481–4135 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-072-31N closed-circuit cooler (75 tons, 329 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-072-31N — a Series V closed circuit closed-circuit cooler, 75 nominal tons (329 kW): rated to cool 225 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 21.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 246–411 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1208-1236N100 evaporative condenser (7.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1208-1236N100 — a PCC evaporative condenser rejecting 7340 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 115.9 m³/s of the maker's own printed air, with a 74.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5505–9175 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1218N-3D2DS-P1 closed-circuit cooler (240 tons, 1.1 MW) — modelled Example modelled from published data BAC's PFI-1218N-3D2DS-P1 — a PFi closed-circuit cooler, 240 nominal tons (1056 kW): rated to cool 723 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 67.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 792–1320 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 XES15E-1285-09FN cooling tower (131 tons, 574 kW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES15E-1285-09FN — a Series 1500 cooling tower, 131 nominal tons (574 kW): rated to cool 393 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 430–717 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 XES3E-1424-12N cooling tower (805 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's XES3E-1424-12N — a Series 3000 cooling tower, 805 nominal tons (3540 kW): rated to cool 2424 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2655–4425 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VFL-072-31O closed-circuit cooler (81 tons, 355 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VFL-072-31O — a Series V closed circuit closed-circuit cooler, 81 nominal tons (355 kW): rated to cool 243 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 22.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 266–444 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-1218-1240N100 evaporative condenser (7.4 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-1218-1240N100 — a PCC evaporative condenser rejecting 7400 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 137.7 m³/s of the maker's own printed air, with a 74.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 5550–9250 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers