Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 3,409–3,432 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
Baltimore Aircoil PFI-2412N-3D1DS-P2 closed-circuit cooler (313 tons, 1.4 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D1DS-P2 — a PFi closed-circuit cooler, 313 nominal tons (1376 kW): rated to cool 942 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 105.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1032–1720 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D2DS-K2 closed-circuit cooler (245 tons, 1.1 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D2DS-K2 — a PFi closed-circuit cooler, 245 nominal tons (1078 kW): rated to cool 738 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 65.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection808–1347 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D2DS-L2 closed-circuit cooler (265 tons, 1.2 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D2DS-L2 — a PFi closed-circuit cooler, 265 nominal tons (1165 kW): rated to cool 798 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 74.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection874–1457 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D2DS-N2 closed-circuit cooler (295 tons, 1.3 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D2DS-N2 — a PFi closed-circuit cooler, 295 nominal tons (1297 kW): rated to cool 888 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 87.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection973–1621 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D2DS-O2 closed-circuit cooler (306 tons, 1.3 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D2DS-O2 — a PFi closed-circuit cooler, 306 nominal tons (1345 kW): rated to cool 921 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 92.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1009–1681 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D2ES-L2 closed-circuit cooler (287 tons, 1.3 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D2ES-L2 — a PFi closed-circuit cooler, 287 nominal tons (1262 kW): rated to cool 864 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 71.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection946–1577 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D2ES-M2 closed-circuit cooler (304 tons, 1.3 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D2ES-M2 — a PFi closed-circuit cooler, 304 nominal tons (1336 kW): rated to cool 915 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 78.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1002–1670 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D3ES-N2 closed-circuit cooler (323 tons, 1.4 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D3ES-N2 — a PFi closed-circuit cooler, 323 nominal tons (1420 kW): rated to cool 972 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 81.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1065–1774 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D4DS-L2 closed-circuit cooler (276 tons, 1.2 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D4DS-L2 — a PFi closed-circuit cooler, 276 nominal tons (1214 kW): rated to cool 831 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 69.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection910–1517 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D4ES-M2 closed-circuit cooler (315 tons, 1.4 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D4ES-M2 — a PFi closed-circuit cooler, 315 nominal tons (1385 kW): rated to cool 948 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 73.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1038–1731 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D4ES-O2 closed-circuit cooler (345 tons, 1.5 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D4ES-O2 — a PFi closed-circuit cooler, 345 nominal tons (1516 kW): rated to cool 1038 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 83.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1137–1895 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-3D4ES-P2 closed-circuit cooler (368 tons, 1.6 MW) — modelled Example modelled from published data
BAC's PFI-2412N-3D4ES-P2 — a PFi closed-circuit cooler, 368 nominal tons (1617 kW): rated to cool 1107 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 91.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1213–2021 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-4D2DS-M2 closed-circuit cooler (323 tons, 1.4 MW) — modelled Example modelled from published data
BAC's PFI-2412N-4D2DS-M2 — a PFi closed-circuit cooler, 323 nominal tons (1420 kW): rated to cool 972 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 77.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1065–1774 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-4D2DS-N2 closed-circuit cooler (340 tons, 1.5 MW) — modelled Example modelled from published data
BAC's PFI-2412N-4D2DS-N2 — a PFi closed-circuit cooler, 340 nominal tons (1494 kW): rated to cool 1023 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 83.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1121–1868 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-4D2ES-P2 closed-circuit cooler (406 tons, 1.8 MW) — modelled Example modelled from published data
BAC's PFI-2412N-4D2ES-P2 — a PFi closed-circuit cooler, 406 nominal tons (1783 kW): rated to cool 1221 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 93.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1337–2229 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-4D3DS-P2 closed-circuit cooler (388 tons, 1.7 MW) — modelled Example modelled from published data
BAC's PFI-2412N-4D3DS-P2 — a PFi closed-circuit cooler, 388 nominal tons (1704 kW): rated to cool 1167 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 91.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1278–2130 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-4D3ES-M2 closed-circuit cooler (351 tons, 1.5 MW) — modelled Example modelled from published data
BAC's PFI-2412N-4D3ES-M2 — a PFi closed-circuit cooler, 351 nominal tons (1542 kW): rated to cool 1056 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 72.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1157–1928 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-4D4ES-N2 closed-circuit cooler (375 tons, 1.6 MW) — modelled Example modelled from published data
BAC's PFI-2412N-4D4ES-N2 — a PFi closed-circuit cooler, 375 nominal tons (1647 kW): rated to cool 1128 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 75.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1236–2059 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-5D1DS-O2 closed-circuit cooler (375 tons, 1.6 MW) — modelled Example modelled from published data
BAC's PFI-2412N-5D1DS-O2 — a PFi closed-circuit cooler, 375 nominal tons (1647 kW): rated to cool 1128 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 87.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1236–2059 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-5D2ES-N2 closed-circuit cooler (396 tons, 1.7 MW) — modelled Example modelled from published data
BAC's PFI-2412N-5D2ES-N2 — a PFi closed-circuit cooler, 396 nominal tons (1739 kW): rated to cool 1191 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 77.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1305–2174 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-5D4DS-O2 closed-circuit cooler (394 tons, 1.7 MW) — modelled Example modelled from published data
BAC's PFI-2412N-5D4DS-O2 — a PFi closed-circuit cooler, 394 nominal tons (1731 kW): rated to cool 1185 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 77.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1298–2163 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-5D4ES-O2 closed-circuit cooler (418 tons, 1.8 MW) — modelled Example modelled from published data
BAC's PFI-2412N-5D4ES-O2 — a PFi closed-circuit cooler, 418 nominal tons (1836 kW): rated to cool 1257 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 75.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1377–2295 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-5D4ES-P2 closed-circuit cooler (446 tons, 2.0 MW) — modelled Example modelled from published data
BAC's PFI-2412N-5D4ES-P2 — a PFi closed-circuit cooler, 446 nominal tons (1958 kW): rated to cool 1341 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 82.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1469–2448 kWEUOpen in the builder
Baltimore Aircoil PFI-2412N-6D1DS-M2 closed-circuit cooler (369 tons, 1.6 MW) — modelled Example modelled from published data
BAC's PFI-2412N-6D1DS-M2 — a PFi closed-circuit cooler, 369 nominal tons (1621 kW): rated to cool 1110 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 74.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1216–2026 kWEUOpen in the builder
‹ Previous1…141142143144145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers