Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1537–1560 of 3346

EVAPCO AT 210-3M36 cooling tower (994 tons, 4.4 MW) — modelled

EVAPCO's 210-3M36 — a AT cooling tower, 994 nominal tons (4368 kW): rated to cool 2991 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 113.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3276–5460 kW · EU

EVAPCO AT 210-3N36 cooling tower (1089 tons, 4.8 MW) — modelled

EVAPCO's 210-3N36 — a AT cooling tower, 1089 nominal tons (4789 kW): rated to cool 3279 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 123.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3592–5986 kW · EU

EVAPCO AT 210-4I24 cooling tower (553 tons, 2.4 MW) — modelled

EVAPCO's 210-4I24 — a AT cooling tower, 553 nominal tons (2432 kW): rated to cool 1665 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 59.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1824–3040 kW · EU

EVAPCO AT 210-4I36 cooling tower (725 tons, 3.2 MW) — modelled

EVAPCO's 210-4I36 — a AT cooling tower, 725 nominal tons (3185 kW): rated to cool 2181 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2389–3982 kW · EU

EVAPCO AT 210-4J24 cooling tower (642 tons, 2.8 MW) — modelled

EVAPCO's 210-4J24 — a AT cooling tower, 642 nominal tons (2822 kW): rated to cool 1932 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 67.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2116–3527 kW · EU

EVAPCO AT 210-4J36 cooling tower (836 tons, 3.7 MW) — modelled

EVAPCO's 210-4J36 — a AT cooling tower, 836 nominal tons (3676 kW): rated to cool 2517 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 89.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2757–4595 kW · EU

EVAPCO AT 210-4K24 cooling tower (699 tons, 3.1 MW) — modelled

EVAPCO's 210-4K24 — a AT cooling tower, 699 nominal tons (3071 kW): rated to cool 2103 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 73.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2304–3839 kW · EU

EVAPCO AT 210-4K36 cooling tower (918 tons, 4.0 MW) — modelled

EVAPCO's 210-4K36 — a AT cooling tower, 918 nominal tons (4035 kW): rated to cool 2763 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 97.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3026–5044 kW · EU

EVAPCO AT 210-4L24 cooling tower (744 tons, 3.3 MW) — modelled

EVAPCO's 210-4L24 — a AT cooling tower, 744 nominal tons (3269 kW): rated to cool 2238 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2451–4086 kW · EU

EVAPCO AT 210-4L36 cooling tower (984 tons, 4.3 MW) — modelled

EVAPCO's 210-4L36 — a AT cooling tower, 984 nominal tons (4324 kW): rated to cool 2961 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 105.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3243–5406 kW · EU

EVAPCO AT 210-4M24 cooling tower (782 tons, 3.4 MW) — modelled

EVAPCO's 210-4M24 — a AT cooling tower, 782 nominal tons (3439 kW): rated to cool 2355 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 83.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2580–4299 kW · EU

EVAPCO AT 210-4M36 cooling tower (1041 tons, 4.6 MW) — modelled

EVAPCO's 210-4M36 — a AT cooling tower, 1041 nominal tons (4574 kW): rated to cool 3132 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 111.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3431–5718 kW · EU

EVAPCO AT 210-4N24 cooling tower (817 tons, 3.6 MW) — modelled

EVAPCO's 210-4N24 — a AT cooling tower, 817 nominal tons (3593 kW): rated to cool 2460 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 87.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2695–4491 kW · EU

EVAPCO AT 210-4N36 cooling tower (1136 tons, 5.0 MW) — modelled

EVAPCO's 210-4N36 — a AT cooling tower, 1136 nominal tons (4995 kW): rated to cool 3420 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 121.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3746–6243 kW · EU

EVAPCO AT 212-2F9 cooling tower (178 tons, 784 kW) — modelled

EVAPCO's 212-2F9 — a AT cooling tower, 178 nominal tons (784 kW): rated to cool 537 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 588–980 kW · EU

EVAPCO AT 212-2G9 cooling tower (224 tons, 986 kW) — modelled

EVAPCO's 212-2G9 — a AT cooling tower, 224 nominal tons (986 kW): rated to cool 675 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 739–1232 kW · EU

EVAPCO AT 212-2H9 cooling tower (246 tons, 1.1 MW) — modelled

EVAPCO's 212-2H9 — a AT cooling tower, 246 nominal tons (1082 kW): rated to cool 741 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 812–1353 kW · EU

EVAPCO AT 212-2I24 cooling tower (558 tons, 2.5 MW) — modelled

EVAPCO's 212-2I24 — a AT cooling tower, 558 nominal tons (2454 kW): rated to cool 1680 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 67.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1840–3067 kW · EU

EVAPCO AT 212-2I28 cooling tower (596 tons, 2.6 MW) — modelled

EVAPCO's 212-2I28 — a AT cooling tower, 596 nominal tons (2620 kW): rated to cool 1794 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 73.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1965–3275 kW · EU

EVAPCO AT 212-2J24 cooling tower (665 tons, 2.9 MW) — modelled

EVAPCO's 212-2J24 — a AT cooling tower, 665 nominal tons (2922 kW): rated to cool 2001 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2192–3653 kW · EU

EVAPCO AT 212-2J28 cooling tower (715 tons, 3.1 MW) — modelled

EVAPCO's 212-2J28 — a AT cooling tower, 715 nominal tons (3141 kW): rated to cool 2151 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 83.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2356–3927 kW · EU

EVAPCO AT 212-2J36 cooling tower (874 tons, 3.8 MW) — modelled

EVAPCO's 212-2J36 — a AT cooling tower, 874 nominal tons (3842 kW): rated to cool 2631 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 103.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 2882–4803 kW · EU

EVAPCO AT 212-2K24 cooling tower (727 tons, 3.2 MW) — modelled

EVAPCO's 212-2K24 — a AT cooling tower, 727 nominal tons (3194 kW): rated to cool 2187 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 84.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2396–3993 kW · EU

EVAPCO AT 212-2K28 cooling tower (784 tons, 3.4 MW) — modelled

EVAPCO's 212-2K28 — a AT cooling tower, 784 nominal tons (3448 kW): rated to cool 2361 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 91.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2586–4310 kW · EU
‹ Previous1…6364656667…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers