Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1,489–1,512 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 212-2L28 cooling tower (847 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-2L28 — an AT cooling tower, 847 nominal tons (3724 kW): rated to cool 2550 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 98.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2793–4655 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-288A evaporative condenser (1.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-288A — a VCA evaporative condenser rejecting 1241 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 23.5 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 931–1551 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3H18 closed-circuit cooler (242 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3H18 — an ATWB closed-circuit cooler, 242 nominal tons (1063 kW): rated to cool 607 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 35.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 797–1329 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0432B-1018N-JA evaporative condenser (2.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0432B-1018N-JA — a Vertex VRC evaporative condenser rejecting 2624 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 38.6 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1968–3279 kW | EU | Open in the builder |
| EVAPCO AT 212-2L36 cooling tower (1048 tons, 4.6 MW) — modelled Example modelled from published data EVAPCO's 212-2L36 — an AT cooling tower, 1048 nominal tons (4605 kW): rated to cool 3153 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 122.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3454–5756 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-314-1212-15 evaporative condenser (1.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-314-1212-15 — a CXVB evaporative condenser rejecting 1902 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 37.7 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1427–2378 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3H21 closed-circuit cooler (279 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3H21 — an ATWB closed-circuit cooler, 279 nominal tons (1228 kW): rated to cool 701 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 39.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 921–1535 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0818B-24Q-O closed-circuit cooler (264 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0818B-24Q-O — an FXV closed-circuit cooler, 264 nominal tons (1161 kW): rated to cool 795 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 59.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 871–1451 kW | EU | Open in the builder |
| EVAPCO AT 212-2L40 cooling tower (1010 tons, 4.4 MW) — modelled Example modelled from published data EVAPCO's 212-2L40 — an AT cooling tower, 1010 nominal tons (4438 kW): rated to cool 3039 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 124.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3329–5548 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0416-2012N020 evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0416-2012N020 — a PCC evaporative condenser rejecting 2527 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 54.7 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1895–3159 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3H8 closed-circuit cooler (86 tons, 380 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3H8 — an ATWB closed-circuit cooler, 86 nominal tons (380 kW): rated to cool 217 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 15.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 285–475 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0718N-4D2DS-J2 closed-circuit cooler (143 tons, 627 kW) — modelled Example modelled from published data BAC's PFI-0718N-4D2DS-J2 — a PFi closed-circuit cooler, 143 nominal tons (627 kW): rated to cool 429 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 32.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 470–783 kW | EU | Open in the builder |
| EVAPCO AT 212-2M24 cooling tower (825 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-2M24 — an AT cooling tower, 825 nominal tons (3628 kW): rated to cool 2484 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 95.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2721–4535 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1218-10KN cooling tower (559 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1218-10KN — a Series 1500 cooling tower, 559 nominal tons (2458 kW): rated to cool 1683 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1843–3072 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3I11 closed-circuit cooler (124 tons, 543 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3I11 — an ATWB closed-circuit cooler, 124 nominal tons (543 kW): rated to cool 310 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 21.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 407–679 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-13S cooling tower (1010 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-13S — a Series 3000 cooling tower, 1010 nominal tons (4438 kW): rated to cool 3039 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 111.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3329–5548 kW | EU | Open in the builder |
| EVAPCO AT 212-2M28 cooling tower (897 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-2M28 — an AT cooling tower, 897 nominal tons (3943 kW): rated to cool 2700 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 104.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2957–4929 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-M350-O cooling tower (349 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VT1-M350-O — a Series V cooling tower, 349 nominal tons (1533 kW): rated to cool 1050 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1150–1917 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3I14 closed-circuit cooler (165 tons, 726 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3I14 — an ATWB closed-circuit cooler, 165 nominal tons (726 kW): rated to cool 414 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 26.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 545–908 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-096-41O closed-circuit cooler (87 tons, 381 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-096-41O — a Series V closed circuit closed-circuit cooler, 87 nominal tons (381 kW): rated to cool 261 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 25.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 286–476 kW | EU | Open in the builder |
| EVAPCO AT 212-2M36 cooling tower (1103 tons, 4.9 MW) — modelled Example modelled from published data EVAPCO's 212-2M36 — an AT cooling tower, 1103 nominal tons (4850 kW): rated to cool 3321 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 129.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3638–6063 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-300A evaporative condenser (1.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-300A — a VCA evaporative condenser rejecting 1292 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 28.2 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 969–1616 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3I18 closed-circuit cooler (266 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3I18 — an ATWB closed-circuit cooler, 266 nominal tons (1169 kW): rated to cool 667 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 39.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 877–1461 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0435B-1018N-HB evaporative condenser (2.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0435B-1018N-HB — a Vertex VRC evaporative condenser rejecting 2641 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 50.3 m³/s of the maker's own printed air, with a 25.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1980–3301 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers