Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,465–1,488 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 212-2J36 cooling tower (874 tons, 3.8 MW) — modelled Example modelled from published data
EVAPCO's 212-2J36 — an AT cooling tower, 874 nominal tons (3842 kW): rated to cool 2631 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 103.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2882–4803 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M328-O cooling tower (327 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-M328-O — a Series V cooling tower, 327 nominal tons (1437 kW): rated to cool 984 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1078–1796 kWEUOpen in the builder
EVAPCO ATWB 7-6K12 closed-circuit cooler (221 tons, 970 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 7-6K12 — an ATWB closed-circuit cooler, 221 nominal tons (970 kW): rated to cool 554 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 24.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection728–1213 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-096-31P closed-circuit cooler (93 tons, 407 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-096-31P — a Series V closed circuit closed-circuit cooler, 93 nominal tons (407 kW): rated to cool 279 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 27.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection306–509 kWEUOpen in the builder
EVAPCO AT 212-2K24 cooling tower (727 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-2K24 — an AT cooling tower, 727 nominal tons (3194 kW): rated to cool 2187 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 84.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2396–3993 kWEUOpen in the builder
Baltimore Aircoil VCA-261A evaporative condenser (1.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-261A — a VCA evaporative condenser rejecting 1125 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 20.5 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection843–1406 kWEUOpen in the builder
EVAPCO ATWB 7-7I18 closed-circuit cooler (323 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 7-7I18 — an ATWB closed-circuit cooler, 323 nominal tons (1421 kW): rated to cool 811 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 31.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1066–1777 kWEUOpen in the builder
Baltimore Aircoil VRC-0429B-1224N-GA evaporative condenser (2.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0429B-1224N-GA — a Vertex VRC evaporative condenser rejecting 2602 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 47.6 m³/s of the maker's own printed air, with a 8.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1951–3252 kWEUOpen in the builder
EVAPCO AT 212-2K28 cooling tower (784 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-2K28 — an AT cooling tower, 784 nominal tons (3448 kW): rated to cool 2361 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 91.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2586–4310 kWEUOpen in the builder
Baltimore Aircoil CXVB-310-0818-15 evaporative condenser (1.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-310-0818-15 — a CXVB evaporative condenser rejecting 1878 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.0 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1409–2348 kWEUOpen in the builder
EVAPCO ATWB 7-7J18 closed-circuit cooler (366 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 7-7J18 — an ATWB closed-circuit cooler, 366 nominal tons (1611 kW): rated to cool 919 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 35.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1208–2014 kWEUOpen in the builder
Baltimore Aircoil FXV-0818B-16Q-O closed-circuit cooler (203 tons, 894 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0818B-16Q-O — an FXV closed-circuit cooler, 203 nominal tons (894 kW): rated to cool 612 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 60.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection670–1117 kWEUOpen in the builder
EVAPCO AT 212-2K36 cooling tower (991 tons, 4.4 MW) — modelled Example modelled from published data
EVAPCO's 212-2K36 — an AT cooling tower, 991 nominal tons (4355 kW): rated to cool 2982 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 113.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3266–5444 kWEUOpen in the builder
Baltimore Aircoil PCC-0416-1024N020 evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0416-1024N020 — a PCC evaporative condenser rejecting 2527 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 54.7 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1895–3159 kWEUOpen in the builder
EVAPCO ATWB 7-7K12 closed-circuit cooler (247 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 7-7K12 — an ATWB closed-circuit cooler, 247 nominal tons (1084 kW): rated to cool 619 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 23.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection813–1355 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-3D4DS-M2 closed-circuit cooler (164 tons, 723 kW) — modelled Example modelled from published data
BAC's PFI-0718N-3D4DS-M2 — a PFi closed-circuit cooler, 164 nominal tons (723 kW): rated to cool 495 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 42.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection542–904 kWEUOpen in the builder
EVAPCO AT 212-2K40 cooling tower (915 tons, 4.0 MW) — modelled Example modelled from published data
EVAPCO's 212-2K40 — an AT cooling tower, 915 nominal tons (4022 kW): rated to cool 2754 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 116.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3017–5028 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-09LN-2 cooling tower (1208 tons, 5.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-09LN-2 — a Series 1500 cooling tower, 1208 nominal tons (5310 kW): rated to cool 3636 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 130.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3983–6638 kWEUOpen in the builder
EVAPCO ATWB 9-3G8 closed-circuit cooler (74 tons, 324 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-3G8 — an ATWB closed-circuit cooler, 74 nominal tons (324 kW): rated to cool 185 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 13.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection243–405 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-13R-2 cooling tower (1889 tons, 8.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-13R-2 — a Series 3000 cooling tower, 1889 nominal tons (8303 kW): rated to cool 5685 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 208.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6227–10378 kWEUOpen in the builder
EVAPCO AT 212-2L24 cooling tower (779 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-2L24 — an AT cooling tower, 779 nominal tons (3426 kW): rated to cool 2346 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2570–4283 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M348-P cooling tower (347 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-M348-P — a Series V cooling tower, 347 nominal tons (1525 kW): rated to cool 1044 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1144–1906 kWEUOpen in the builder
EVAPCO ATWB 9-3H11 closed-circuit cooler (111 tons, 488 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-3H11 — an ATWB closed-circuit cooler, 111 nominal tons (488 kW): rated to cool 279 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 19.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection366–611 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-096-31Q closed-circuit cooler (102 tons, 447 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-096-31Q — a Series V closed circuit closed-circuit cooler, 102 nominal tons (447 kW): rated to cool 306 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 30.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection335–559 kWEUOpen in the builder
‹ Previous1…6061626364…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers