Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,417–1,440 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 210-4L36 cooling tower (984 tons, 4.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-4L36 — an AT cooling tower, 984 nominal tons (4324 kW): rated to cool 2961 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 105.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3243–5406 kWEUOpen in the builder
Baltimore Aircoil PCC-0395-1212N040 evaporative condenser (2.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0395-1212N040 — a PCC evaporative condenser rejecting 2399 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.5 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1800–2999 kWEUOpen in the builder
EVAPCO ATWB 7-4J12 closed-circuit cooler (165 tons, 723 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 7-4J12 — an ATWB closed-circuit cooler, 165 nominal tons (723 kW): rated to cool 413 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 23.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection543–904 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-3D1ES-L2 closed-circuit cooler (153 tons, 675 kW) — modelled Example modelled from published data
BAC's PFI-0718N-3D1ES-L2 — a PFi closed-circuit cooler, 153 nominal tons (675 kW): rated to cool 462 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 41.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection506–843 kWEUOpen in the builder
EVAPCO AT 210-4M24 cooling tower (782 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-4M24 — an AT cooling tower, 782 nominal tons (3439 kW): rated to cool 2355 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 83.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2580–4299 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-09LC cooling tower (570 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-09LC — a Series 1500 cooling tower, 570 nominal tons (2506 kW): rated to cool 1716 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1880–3133 kWEUOpen in the builder
EVAPCO ATWB 7-4J18 closed-circuit cooler (297 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 7-4J18 — an ATWB closed-circuit cooler, 297 nominal tons (1304 kW): rated to cool 744 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 38.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection978–1631 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-13Q cooling tower (894 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-13Q — a Series 3000 cooling tower, 894 nominal tons (3930 kW): rated to cool 2691 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 99.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2948–4913 kWEUOpen in the builder
EVAPCO AT 210-4M36 cooling tower (1041 tons, 4.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-4M36 — an AT cooling tower, 1041 nominal tons (4574 kW): rated to cool 3132 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 111.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3431–5718 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M1260-R cooling tower (1256 tons, 5.5 MW) — modelled Example modelled from published data
BAC's VT1-M1260-R — a Series V cooling tower, 1256 nominal tons (5521 kW): rated to cool 3780 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 112.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4140–6901 kWEUOpen in the builder
EVAPCO ATWB 7-5H18 closed-circuit cooler (253 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 7-5H18 — an ATWB closed-circuit cooler, 253 nominal tons (1113 kW): rated to cool 635 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 30.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection835–1392 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-072-41O closed-circuit cooler (86 tons, 377 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-072-41O — a Series V closed circuit closed-circuit cooler, 86 nominal tons (377 kW): rated to cool 258 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 24.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection283–471 kWEUOpen in the builder
EVAPCO AT 210-4N24 cooling tower (817 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-4N24 — an AT cooling tower, 817 nominal tons (3593 kW): rated to cool 2460 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 87.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2695–4491 kWEUOpen in the builder
Baltimore Aircoil VCA-235A evaporative condenser (1.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-235A — a VCA evaporative condenser rejecting 1013 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 18.3 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection759–1266 kWEUOpen in the builder
EVAPCO ATWB 7-5I18 closed-circuit cooler (278 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 7-5I18 — an ATWB closed-circuit cooler, 278 nominal tons (1221 kW): rated to cool 697 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 33.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection915–1526 kWEUOpen in the builder
Baltimore Aircoil VRC-0418B-1212N-JB evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0418B-1212N-JB — a Vertex VRC evaporative condenser rejecting 2533 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 42.3 m³/s of the maker's own printed air, with a 30.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1900–3166 kWEUOpen in the builder
EVAPCO AT 210-4N36 cooling tower (1136 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-4N36 — an AT cooling tower, 1136 nominal tons (4995 kW): rated to cool 3420 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 121.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3746–6243 kWEUOpen in the builder
Baltimore Aircoil CXVB-302-1212-20 evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-302-1212-20 — a CXVB evaporative condenser rejecting 1830 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.9 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1372–2287 kWEUOpen in the builder
EVAPCO ATWB 7-5J12 closed-circuit cooler (181 tons, 796 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 7-5J12 — an ATWB closed-circuit cooler, 181 nominal tons (796 kW): rated to cool 454 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 23.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection597–995 kWEUOpen in the builder
Baltimore Aircoil FXV-0818A-36H-M closed-circuit cooler (232 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0818A-36H-M — an FXV closed-circuit cooler, 232 nominal tons (1021 kW): rated to cool 699 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 44.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection766–1276 kWEUOpen in the builder
EVAPCO AT 212-2F9 cooling tower (178 tons, 784 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-2F9 — an AT cooling tower, 178 nominal tons (784 kW): rated to cool 537 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection588–980 kWEUOpen in the builder
Baltimore Aircoil PCC-0396-1212N040 evaporative condenser (2.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0396-1212N040 — a PCC evaporative condenser rejecting 2406 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.9 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1804–3007 kWEUOpen in the builder
EVAPCO ATWB 7-5J18 closed-circuit cooler (316 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 7-5J18 — an ATWB closed-circuit cooler, 316 nominal tons (1388 kW): rated to cool 792 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 37.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1041–1735 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-3D2DS-J2 closed-circuit cooler (128 tons, 561 kW) — modelled Example modelled from published data
BAC's PFI-0718N-3D2DS-J2 — a PFi closed-circuit cooler, 128 nominal tons (561 kW): rated to cool 384 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 34.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection421–701 kWEUOpen in the builder
‹ Previous1…5859606162…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers