Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1417–1440 of 3346

EVAPCO AT 17-4I12 cooling tower (219 tons, 964 kW) — modelled

EVAPCO's 17-4I12 — a AT cooling tower, 219 nominal tons (964 kW): rated to cool 660 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 723–1205 kW · EU

EVAPCO AT 17-4I14 cooling tower (196 tons, 863 kW) — modelled

EVAPCO's 17-4I14 — a AT cooling tower, 196 nominal tons (863 kW): rated to cool 591 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 647–1079 kW · EU

EVAPCO AT 17-4I18 cooling tower (361 tons, 1.6 MW) — modelled

EVAPCO's 17-4I18 — a AT cooling tower, 361 nominal tons (1586 kW): rated to cool 1086 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1190–1983 kW · EU

EVAPCO AT 17-4I9 cooling tower (178 tons, 784 kW) — modelled

EVAPCO's 17-4I9 — a AT cooling tower, 178 nominal tons (784 kW): rated to cool 537 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 18.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 588–980 kW · EU

EVAPCO AT 17-4J12 cooling tower (248 tons, 1.1 MW) — modelled

EVAPCO's 17-4J12 — a AT cooling tower, 248 nominal tons (1091 kW): rated to cool 747 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 818–1364 kW · EU

EVAPCO AT 17-4J14 cooling tower (278 tons, 1.2 MW) — modelled

EVAPCO's 17-4J14 — a AT cooling tower, 278 nominal tons (1222 kW): rated to cool 837 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 917–1528 kW · EU

EVAPCO AT 17-4J18 cooling tower (407 tons, 1.8 MW) — modelled

EVAPCO's 17-4J18 — a AT cooling tower, 407 nominal tons (1788 kW): rated to cool 1224 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1341–2235 kW · EU

EVAPCO AT 17-4J9 cooling tower (201 tons, 885 kW) — modelled

EVAPCO's 17-4J9 — a AT cooling tower, 201 nominal tons (885 kW): rated to cool 606 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 20.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 664–1106 kW · EU

EVAPCO AT 17-4K12 cooling tower (270 tons, 1.2 MW) — modelled

EVAPCO's 17-4K12 — a AT cooling tower, 270 nominal tons (1187 kW): rated to cool 813 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 891–1484 kW · EU

EVAPCO AT 17-4K14 cooling tower (218 tons, 960 kW) — modelled

EVAPCO's 17-4K14 — a AT cooling tower, 218 nominal tons (960 kW): rated to cool 657 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 31.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 720–1199 kW · EU

EVAPCO AT 17-4K18 cooling tower (444 tons, 1.9 MW) — modelled

EVAPCO's 17-4K18 — a AT cooling tower, 444 nominal tons (1950 kW): rated to cool 1335 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1462–2437 kW · EU

EVAPCO AT 17-4K9 cooling tower (219 tons, 964 kW) — modelled

EVAPCO's 17-4K9 — a AT cooling tower, 219 nominal tons (964 kW): rated to cool 660 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 22.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 723–1205 kW · EU

EVAPCO AT 17-4L12 cooling tower (289 tons, 1.3 MW) — modelled

EVAPCO's 17-4L12 — a AT cooling tower, 289 nominal tons (1271 kW): rated to cool 870 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 953–1588 kW · EU

EVAPCO AT 17-4L14 cooling tower (294 tons, 1.3 MW) — modelled

EVAPCO's 17-4L14 — a AT cooling tower, 294 nominal tons (1293 kW): rated to cool 885 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 969–1616 kW · EU

EVAPCO AT 17-4M14 cooling tower (332 tons, 1.5 MW) — modelled

EVAPCO's 17-4M14 — a AT cooling tower, 332 nominal tons (1459 kW): rated to cool 999 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 35.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1094–1824 kW · EU

EVAPCO AT 19-2F6 cooling tower (89 tons, 390 kW) — modelled

EVAPCO's 19-2F6 — a AT cooling tower, 89 nominal tons (390 kW): rated to cool 267 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 10.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 292–487 kW · EU

EVAPCO AT 19-2F8 cooling tower (109 tons, 478 kW) — modelled

EVAPCO's 19-2F8 — a AT cooling tower, 109 nominal tons (478 kW): rated to cool 327 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 12.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 358–597 kW · EU

EVAPCO AT 19-2G11 cooling tower (155 tons, 683 kW) — modelled

EVAPCO's 19-2G11 — a AT cooling tower, 155 nominal tons (683 kW): rated to cool 468 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 19.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 513–854 kW · EU

EVAPCO AT 19-2G6 cooling tower (112 tons, 491 kW) — modelled

EVAPCO's 19-2G6 — a AT cooling tower, 112 nominal tons (491 kW): rated to cool 336 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 12.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 368–613 kW · EU

EVAPCO AT 19-2G8 cooling tower (137 tons, 600 kW) — modelled

EVAPCO's 19-2G8 — a AT cooling tower, 137 nominal tons (600 kW): rated to cool 411 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 450–750 kW · EU

EVAPCO AT 19-2G9 cooling tower (135 tons, 591 kW) — modelled

EVAPCO's 19-2G9 — a AT cooling tower, 135 nominal tons (591 kW): rated to cool 405 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 16.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 444–739 kW · EU

EVAPCO AT 19-2H11 cooling tower (186 tons, 819 kW) — modelled

EVAPCO's 19-2H11 — a AT cooling tower, 186 nominal tons (819 kW): rated to cool 561 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 614–1024 kW · EU

EVAPCO AT 19-2H12 cooling tower (202 tons, 889 kW) — modelled

EVAPCO's 19-2H12 — a AT cooling tower, 202 nominal tons (889 kW): rated to cool 609 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 667–1112 kW · EU

EVAPCO AT 19-2H14 cooling tower (220 tons, 968 kW) — modelled

EVAPCO's 19-2H14 — a AT cooling tower, 220 nominal tons (968 kW): rated to cool 663 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 726–1210 kW · EU
‹ Previous1…5859606162…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers