Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,369–1,392 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 210-3L24 cooling tower (720 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-3L24 — an AT cooling tower, 720 nominal tons (3163 kW): rated to cool 2166 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 80.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2373–3954 kWEUOpen in the builder
Baltimore Aircoil VCA-206A evaporative condenser (887 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-206A — a VCA evaporative condenser rejecting 887 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 18.7 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection666–1109 kWEUOpen in the builder
EVAPCO ATWB 4-5E12 closed-circuit cooler (81 tons, 357 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 4-5E12 — an ATWB closed-circuit cooler, 81 nominal tons (357 kW): rated to cool 204 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 9.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection268–446 kWEUOpen in the builder
Baltimore Aircoil VRC-0413B-1218N-JA evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0413B-1218N-JA — a Vertex VRC evaporative condenser rejecting 2503 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 48.5 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1877–3129 kWEUOpen in the builder
EVAPCO AT 210-3L36 cooling tower (938 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-3L36 — an AT cooling tower, 938 nominal tons (4123 kW): rated to cool 2823 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 106.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3092–5154 kWEUOpen in the builder
Baltimore Aircoil CXVB-285-1212-15 evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-285-1212-15 — a CXVB evaporative condenser rejecting 1727 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 38.0 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1295–2158 kWEUOpen in the builder
EVAPCO ATWB 4-5E9 closed-circuit cooler (62 tons, 271 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 4-5E9 — an ATWB closed-circuit cooler, 62 nominal tons (271 kW): rated to cool 154 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 8.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection203–338 kWEUOpen in the builder
Baltimore Aircoil FXV-0818A-24Q-M closed-circuit cooler (217 tons, 955 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0818A-24Q-M — an FXV closed-circuit cooler, 217 nominal tons (955 kW): rated to cool 654 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 45.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection716–1194 kWEUOpen in the builder
EVAPCO AT 210-3M24 cooling tower (757 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-3M24 — an AT cooling tower, 757 nominal tons (3330 kW): rated to cool 2280 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 84.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2497–4162 kWEUOpen in the builder
Baltimore Aircoil PCC-0375-1212N030 evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0375-1212N030 — a PCC evaporative condenser rejecting 2278 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 36.6 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1708–2847 kWEUOpen in the builder
EVAPCO ATWB 4-5F12 closed-circuit cooler (92 tons, 402 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 4-5F12 — an ATWB closed-circuit cooler, 92 nominal tons (402 kW): rated to cool 230 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 11.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection302–503 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-3D1DS-H2 closed-circuit cooler (115 tons, 504 kW) — modelled Example modelled from published data
BAC's PFI-0718N-3D1DS-H2 — a PFi closed-circuit cooler, 115 nominal tons (504 kW): rated to cool 345 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 30.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection378–630 kWEUOpen in the builder
EVAPCO AT 210-3M36 cooling tower (994 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-3M36 — an AT cooling tower, 994 nominal tons (4368 kW): rated to cool 2991 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 113.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3276–5460 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-09KN cooling tower (533 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-09KN — a Series 1500 cooling tower, 533 nominal tons (2344 kW): rated to cool 1605 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1758–2930 kWEUOpen in the builder
EVAPCO ATWB 4-5F6 closed-circuit cooler (38 tons, 167 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 4-5F6 — an ATWB closed-circuit cooler, 38 nominal tons (167 kW): rated to cool 96 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 5.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection126–209 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-13P cooling tower (836 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-13P — a Series 3000 cooling tower, 836 nominal tons (3676 kW): rated to cool 2517 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 93.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2757–4595 kWEUOpen in the builder
EVAPCO AT 210-3N36 cooling tower (1089 tons, 4.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-3N36 — an AT cooling tower, 1089 nominal tons (4789 kW): rated to cool 3279 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 123.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3592–5986 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M1137-Q cooling tower (1133 tons, 5.0 MW) — modelled Example modelled from published data
BAC's VT1-M1137-Q — a Series V cooling tower, 1133 nominal tons (4982 kW): rated to cool 3411 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 107.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3736–6227 kWEUOpen in the builder
EVAPCO ATWB 4-5F9 closed-circuit cooler (69 tons, 305 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 4-5F9 — an ATWB closed-circuit cooler, 69 nominal tons (305 kW): rated to cool 174 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 9.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection229–381 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-072-41M closed-circuit cooler (72 tons, 315 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-072-41M — a Series V closed circuit closed-circuit cooler, 72 nominal tons (315 kW): rated to cool 216 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 21.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection237–394 kWEUOpen in the builder
EVAPCO AT 210-4I24 cooling tower (553 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-4I24 — an AT cooling tower, 553 nominal tons (2432 kW): rated to cool 1665 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 59.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1824–3040 kWEUOpen in the builder
Baltimore Aircoil VCA-215A evaporative condenser (926 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-215A — a VCA evaporative condenser rejecting 926 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 16.5 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection695–1158 kWEUOpen in the builder
EVAPCO ATWB 4-5G12 closed-circuit cooler (106 tons, 467 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 4-5G12 — an ATWB closed-circuit cooler, 106 nominal tons (467 kW): rated to cool 267 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 13.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection350–584 kWEUOpen in the builder
Baltimore Aircoil VRC-0414B-1218N-HA evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0414B-1218N-HA — a Vertex VRC evaporative condenser rejecting 2507 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.1 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1880–3134 kWEUOpen in the builder
‹ Previous1…5657585960…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers