Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1,393–1,416 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 210-4I36 cooling tower (725 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-4I36 — an AT cooling tower, 725 nominal tons (3185 kW): rated to cool 2181 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2389–3982 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-297-1212-10 evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-297-1212-10 — a CXVB evaporative condenser rejecting 1799 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.9 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1350–2249 kW | EU | Open in the builder |
| EVAPCO ATWB 7-3H18 closed-circuit cooler (225 tons, 990 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-3H18 — an ATWB closed-circuit cooler, 225 nominal tons (990 kW): rated to cool 565 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 32.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 743–1238 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0818A-24T-M closed-circuit cooler (225 tons, 990 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0818A-24T-M — an FXV closed-circuit cooler, 225 nominal tons (990 kW): rated to cool 678 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 45.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 743–1238 kW | EU | Open in the builder |
| EVAPCO AT 210-4J24 cooling tower (642 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-4J24 — an AT cooling tower, 642 nominal tons (2822 kW): rated to cool 1932 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 67.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2116–3527 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0381-1218N015 evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0381-1218N015 — a PCC evaporative condenser rejecting 2314 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 49.2 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1736–2893 kW | EU | Open in the builder |
| EVAPCO ATWB 7-3I18 closed-circuit cooler (247 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-3I18 — an ATWB closed-circuit cooler, 247 nominal tons (1088 kW): rated to cool 621 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 35.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 816–1360 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0718N-3D1DS-J2 closed-circuit cooler (124 tons, 543 kW) — modelled Example modelled from published data BAC's PFI-0718N-3D1DS-J2 — a PFi closed-circuit cooler, 124 nominal tons (543 kW): rated to cool 372 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 34.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 407–679 kW | EU | Open in the builder |
| EVAPCO AT 210-4J36 cooling tower (836 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-4J36 — an AT cooling tower, 836 nominal tons (3676 kW): rated to cool 2517 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 89.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2757–4595 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1218-09KN-2 cooling tower (1066 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1218-09KN-2 — a Series 1500 cooling tower, 1066 nominal tons (4688 kW): rated to cool 3210 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 115.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3516–5860 kW | EU | Open in the builder |
| EVAPCO ATWB 7-3J12 closed-circuit cooler (152 tons, 667 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-3J12 — an ATWB closed-circuit cooler, 152 nominal tons (667 kW): rated to cool 381 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 24.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 501–834 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-13P-2 cooling tower (1672 tons, 7.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-13P-2 — a Series 3000 cooling tower, 1672 nominal tons (7352 kW): rated to cool 5034 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 185.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5514–9190 kW | EU | Open in the builder |
| EVAPCO AT 210-4K24 cooling tower (699 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-4K24 — an AT cooling tower, 699 nominal tons (3071 kW): rated to cool 2103 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 73.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2304–3839 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-M1194-Q cooling tower (1190 tons, 5.2 MW) — modelled Example modelled from published data BAC's VT1-M1194-Q — a Series V cooling tower, 1190 nominal tons (5231 kW): rated to cool 3582 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 105.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3924–6539 kW | EU | Open in the builder |
| EVAPCO ATWB 7-3J24 closed-circuit cooler (304 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-3J24 — an ATWB closed-circuit cooler, 304 nominal tons (1335 kW): rated to cool 762 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 48.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1001–1668 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-072-41N closed-circuit cooler (80 tons, 351 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-072-41N — a Series V closed circuit closed-circuit cooler, 80 nominal tons (351 kW): rated to cool 240 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 22.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 263–438 kW | EU | Open in the builder |
| EVAPCO AT 210-4K36 cooling tower (918 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-4K36 — an AT cooling tower, 918 nominal tons (4035 kW): rated to cool 2763 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 97.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3026–5044 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-227A evaporative condenser (978 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-227A — a VCA evaporative condenser rejecting 978 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 21.4 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 733–1222 kW | EU | Open in the builder |
| EVAPCO ATWB 7-4H18 closed-circuit cooler (238 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-4H18 — an ATWB closed-circuit cooler, 238 nominal tons (1044 kW): rated to cool 596 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 31.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 783–1305 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0415B-1212N-LA evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0415B-1212N-LA — a Vertex VRC evaporative condenser rejecting 2520 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 36.4 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1890–3151 kW | EU | Open in the builder |
| EVAPCO AT 210-4L24 cooling tower (744 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-4L24 — an AT cooling tower, 744 nominal tons (3269 kW): rated to cool 2238 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2451–4086 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-299-1212-10 evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-299-1212-10 — a CXVB evaporative condenser rejecting 1811 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.5 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1359–2264 kW | EU | Open in the builder |
| EVAPCO ATWB 7-4I18 closed-circuit cooler (261 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-4I18 — an ATWB closed-circuit cooler, 261 nominal tons (1146 kW): rated to cool 654 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 34.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 859–1432 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0818A-32Q-M closed-circuit cooler (236 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0818A-32Q-M — an FXV closed-circuit cooler, 236 nominal tons (1038 kW): rated to cool 711 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 44.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 779–1298 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers