Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1345–1368 of 3346

EVAPCO AT 114-4K24 cooling tower (769 tons, 3.4 MW) — modelled

EVAPCO's 114-4K24 — a AT cooling tower, 769 nominal tons (3382 kW): rated to cool 2316 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2537–4228 kW · EU

EVAPCO AT 114-4L24 cooling tower (831 tons, 3.7 MW) — modelled

EVAPCO's 114-4L24 — a AT cooling tower, 831 nominal tons (3654 kW): rated to cool 2502 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 78.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2741–4568 kW · EU

EVAPCO AT 114-4M24 cooling tower (869 tons, 3.8 MW) — modelled

EVAPCO's 114-4M24 — a AT cooling tower, 869 nominal tons (3821 kW): rated to cool 2616 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 82.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2865–4776 kW · EU

EVAPCO AT 114-4N24 cooling tower (944 tons, 4.1 MW) — modelled

EVAPCO's 114-4N24 — a AT cooling tower, 944 nominal tons (4149 kW): rated to cool 2841 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3112–5186 kW · EU

EVAPCO AT 114-4O24 cooling tower (995 tons, 4.4 MW) — modelled

EVAPCO's 114-4O24 — a AT cooling tower, 995 nominal tons (4373 kW): rated to cool 2994 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 97.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3279–5466 kW · EU

EVAPCO AT 114-4P24 cooling tower (1052 tons, 4.6 MW) — modelled

EVAPCO's 114-4P24 — a AT cooling tower, 1052 nominal tons (4627 kW): rated to cool 3168 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 103.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3470–5783 kW · EU

EVAPCO AT 114-4Q24 cooling tower (1131 tons, 5.0 MW) — modelled

EVAPCO's 114-4Q24 — a AT cooling tower, 1131 nominal tons (4973 kW): rated to cool 3405 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 110.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3730–6216 kW · EU

EVAPCO AT 114-5K26 cooling tower (1000 tons, 4.4 MW) — modelled

EVAPCO's 114-5K26 — a AT cooling tower, 1000 nominal tons (4395 kW): rated to cool 3009 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 94.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3296–5493 kW · EU

EVAPCO AT 114-5L26 cooling tower (1074 tons, 4.7 MW) — modelled

EVAPCO's 114-5L26 — a AT cooling tower, 1074 nominal tons (4723 kW): rated to cool 3234 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 101.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3542–5904 kW · EU

EVAPCO AT 114-5M26 cooling tower (1138 tons, 5.0 MW) — modelled

EVAPCO's 114-5M26 — a AT cooling tower, 1138 nominal tons (5004 kW): rated to cool 3426 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 107.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3753–6254 kW · EU

EVAPCO AT 114-5N26 cooling tower (1243 tons, 5.5 MW) — modelled

EVAPCO's 114-5N26 — a AT cooling tower, 1243 nominal tons (5464 kW): rated to cool 3741 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 117.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 4098–6829 kW · EU

EVAPCO AT 114-5O26 cooling tower (1328 tons, 5.8 MW) — modelled

EVAPCO's 114-5O26 — a AT cooling tower, 1328 nominal tons (5836 kW): rated to cool 3996 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 125.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 4377–7295 kW · EU

EVAPCO AT 14-2E4 cooling tower (33 tons, 145 kW) — modelled

EVAPCO's 14-2E4 — a AT cooling tower, 33 nominal tons (145 kW): rated to cool 99 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 4.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 108–181 kW · EU

EVAPCO AT 14-2E9 cooling tower (76 tons, 333 kW) — modelled

EVAPCO's 14-2E9 — a AT cooling tower, 76 nominal tons (333 kW): rated to cool 228 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 10.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 250–416 kW · EU

EVAPCO AT 14-2F12 cooling tower (115 tons, 504 kW) — modelled

EVAPCO's 14-2F12 — a AT cooling tower, 115 nominal tons (504 kW): rated to cool 345 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 378–630 kW · EU

EVAPCO AT 14-2F4 cooling tower (39 tons, 171 kW) — modelled

EVAPCO's 14-2F4 — a AT cooling tower, 39 nominal tons (171 kW): rated to cool 117 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 5.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 128–214 kW · EU

EVAPCO AT 14-2F6 cooling tower (57 tons, 250 kW) — modelled

EVAPCO's 14-2F6 — a AT cooling tower, 57 nominal tons (250 kW): rated to cool 171 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 7.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 187–312 kW · EU

EVAPCO AT 14-2F9 cooling tower (90 tons, 394 kW) — modelled

EVAPCO's 14-2F9 — a AT cooling tower, 90 nominal tons (394 kW): rated to cool 270 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 11.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 296–493 kW · EU

EVAPCO AT 14-2G12 cooling tower (137 tons, 600 kW) — modelled

EVAPCO's 14-2G12 — a AT cooling tower, 137 nominal tons (600 kW): rated to cool 411 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 17.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 450–750 kW · EU

EVAPCO AT 14-2G6 cooling tower (67 tons, 294 kW) — modelled

EVAPCO's 14-2G6 — a AT cooling tower, 67 nominal tons (294 kW): rated to cool 201 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 8.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 220–367 kW · EU

EVAPCO AT 14-3E4 cooling tower (37 tons, 162 kW) — modelled

EVAPCO's 14-3E4 — a AT cooling tower, 37 nominal tons (162 kW): rated to cool 111 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 4.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 122–203 kW · EU

EVAPCO AT 14-3E9 cooling tower (86 tons, 377 kW) — modelled

EVAPCO's 14-3E9 — a AT cooling tower, 86 nominal tons (377 kW): rated to cool 258 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 9.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 283–471 kW · EU

EVAPCO AT 14-3F12 cooling tower (129 tons, 565 kW) — modelled

EVAPCO's 14-3F12 — a AT cooling tower, 129 nominal tons (565 kW): rated to cool 387 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 14.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 424–706 kW · EU

EVAPCO AT 14-3F4 cooling tower (43 tons, 188 kW) — modelled

EVAPCO's 14-3F4 — a AT cooling tower, 43 nominal tons (188 kW): rated to cool 129 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 5.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 141–235 kW · EU
‹ Previous1…5556575859…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers