Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1,345–1,368 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 210-3I24 cooling tower (527 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-3I24 — an AT cooling tower, 527 nominal tons (2318 kW): rated to cool 1587 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1738–2897 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-072-31N closed-circuit cooler (74 tons, 324 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-072-31N — a Series V closed circuit closed-circuit cooler, 74 nominal tons (324 kW): rated to cool 222 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 23.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 243–405 kW | EU | Open in the builder |
| EVAPCO ATWB 4-3G12 closed-circuit cooler (86 tons, 380 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 4-3G12 — an ATWB closed-circuit cooler, 86 nominal tons (380 kW): rated to cool 217 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 13.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 285–475 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-2019A evaporative condenser (8.7 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-2019A — a VCA evaporative condenser rejecting 8698 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 128.2 m³/s of the maker's own printed air, with a 111.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 6524–10873 kW | EU | Open in the builder |
| EVAPCO AT 210-3I36 cooling tower (665 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-3I36 — an AT cooling tower, 665 nominal tons (2922 kW): rated to cool 2001 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2192–3653 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0412B-1212N-MA evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0412B-1212N-MA — a Vertex VRC evaporative condenser rejecting 2499 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 42.3 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1874–3123 kW | EU | Open in the builder |
| EVAPCO ATWB 4-4E12 closed-circuit cooler (75 tons, 331 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 4-4E12 — an ATWB closed-circuit cooler, 75 nominal tons (331 kW): rated to cool 189 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 10.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 249–414 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-284-0812-30 evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-284-0812-30 — a CXVB evaporative condenser rejecting 1721 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 38.0 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1290–2151 kW | EU | Open in the builder |
| EVAPCO AT 210-3J24 cooling tower (616 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-3J24 — an AT cooling tower, 616 nominal tons (2708 kW): rated to cool 1854 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2031–3385 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0818A-23T-M closed-circuit cooler (216 tons, 951 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0818A-23T-M — an FXV closed-circuit cooler, 216 nominal tons (951 kW): rated to cool 651 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 45.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 713–1188 kW | EU | Open in the builder |
| EVAPCO ATWB 4-4E9 closed-circuit cooler (57 tons, 251 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 4-4E9 — an ATWB closed-circuit cooler, 57 nominal tons (251 kW): rated to cool 143 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 8.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 188–314 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0365-1212N030 evaporative condenser (2.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0365-1212N030 — a PCC evaporative condenser rejecting 2217 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 38.5 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1663–2771 kW | EU | Open in the builder |
| EVAPCO AT 210-3J36 cooling tower (787 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-3J36 — an AT cooling tower, 787 nominal tons (3461 kW): rated to cool 2370 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2596–4327 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0718N-2D4ES-M2 closed-circuit cooler (136 tons, 596 kW) — modelled Example modelled from published data BAC's PFI-0718N-2D4ES-M2 — a PFi closed-circuit cooler, 136 nominal tons (596 kW): rated to cool 408 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 44.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 447–745 kW | EU | Open in the builder |
| EVAPCO ATWB 4-4F12 closed-circuit cooler (85 tons, 374 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 4-4F12 — an ATWB closed-circuit cooler, 85 nominal tons (374 kW): rated to cool 213 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 11.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 280–467 kW | EU | Open in the builder |
| Baltimore Aircoil PT2-1218A-2Q cooling tower (672 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓ BAC's PT2-1218A-2Q — a PT2 cooling tower, 672 nominal tons (2953 kW): rated to cool 2022 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 74.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2215–3691 kW | EU | Open in the builder |
| EVAPCO AT 210-3K24 cooling tower (674 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-3K24 — an AT cooling tower, 674 nominal tons (2962 kW): rated to cool 2028 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 74.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2221–3702 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1218-09JN-2 cooling tower (977 tons, 4.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1218-09JN-2 — a Series 1500 cooling tower, 977 nominal tons (4294 kW): rated to cool 2940 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 106.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3220–5367 kW | EU | Open in the builder |
| EVAPCO ATWB 4-4F9 closed-circuit cooler (64 tons, 283 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 4-4F9 — an ATWB closed-circuit cooler, 64 nominal tons (283 kW): rated to cool 162 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 9.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 213–354 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-12S-2 cooling tower (1954 tons, 8.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-12S-2 — a Series 3000 cooling tower, 1954 nominal tons (8592 kW): rated to cool 5883 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 216.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 6444–10740 kW | EU | Open in the builder |
| EVAPCO AT 210-3K36 cooling tower (870 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-3K36 — an AT cooling tower, 870 nominal tons (3825 kW): rated to cool 2619 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 99.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2869–4781 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-M1113-P cooling tower (1109 tons, 4.9 MW) — modelled Example modelled from published data BAC's VT1-M1113-P — a Series V cooling tower, 1109 nominal tons (4876 kW): rated to cool 3339 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 99.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3657–6096 kW | EU | Open in the builder |
| EVAPCO ATWB 4-4G12 closed-circuit cooler (99 tons, 434 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 4-4G12 — an ATWB closed-circuit cooler, 99 nominal tons (434 kW): rated to cool 248 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 13.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 326–543 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-072-31O closed-circuit cooler (81 tons, 355 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-072-31O — a Series V closed circuit closed-circuit cooler, 81 nominal tons (355 kW): rated to cool 243 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 24.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 266–444 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers