Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,297–1,320 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 19-4M12 cooling tower (362 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4M12 — an AT cooling tower, 362 nominal tons (1590 kW): rated to cool 1089 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 35.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1193–1988 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-12R cooling tower (914 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-12R — a Series 3000 cooling tower, 914 nominal tons (4018 kW): rated to cool 2751 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 101.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3013–5022 kWEUOpen in the builder
EVAPCO ATWB 24-7M14 closed-circuit cooler (849 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-7M14 — an ATWB closed-circuit cooler, 849 nominal tons (3732 kW): rated to cool 2130 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 83.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2799–4665 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M1044-P cooling tower (1041 tons, 4.6 MW) — modelled Example modelled from published data
BAC's VT1-M1044-P — a Series V cooling tower, 1041 nominal tons (4574 kW): rated to cool 3132 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 102.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3431–5718 kWEUOpen in the builder
EVAPCO AT 19-4M14 cooling tower (412 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4M14 — an AT cooling tower, 412 nominal tons (1810 kW): rated to cool 1239 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1357–2262 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-072-21O closed-circuit cooler (75 tons, 329 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-072-21O — a Series V closed circuit closed-circuit cooler, 75 nominal tons (329 kW): rated to cool 225 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 24.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection246–411 kWEUOpen in the builder
EVAPCO ATWB 24-7M18 closed-circuit cooler (996 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-7M18 — an ATWB closed-circuit cooler, 996 nominal tons (4379 kW): rated to cool 2499 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 103.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3284–5474 kWEUOpen in the builder
Baltimore Aircoil VCA-191A evaporative condenser (823 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-191A — a VCA evaporative condenser rejecting 823 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 14.2 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection617–1029 kWEUOpen in the builder
EVAPCO AT 210-2I24 cooling tower (453 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-2I24 — an AT cooling tower, 453 nominal tons (1994 kW): rated to cool 1365 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1495–2492 kWEUOpen in the builder
Baltimore Aircoil VRC-0399B-1018N-JA evaporative condenser (2.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0399B-1018N-JA — a Vertex VRC evaporative condenser rejecting 2413 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 45.2 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1809–3016 kWEUOpen in the builder
EVAPCO ATWB 24-7N14 closed-circuit cooler (930 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-7N14 — an ATWB closed-circuit cooler, 930 nominal tons (4088 kW): rated to cool 2333 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 90.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3066–5110 kWEUOpen in the builder
Baltimore Aircoil CXVB-270-0812-25 evaporative condenser (1.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-270-0812-25 — a CXVB evaporative condenser rejecting 1636 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 35.9 m³/s of the maker's own printed air, with a 18.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1227–2045 kWEUOpen in the builder
EVAPCO AT 210-2I36 cooling tower (578 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-2I36 — an AT cooling tower, 578 nominal tons (2541 kW): rated to cool 1740 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 81.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1906–3177 kWEUOpen in the builder
Baltimore Aircoil FXV-0818A-16Q-M closed-circuit cooler (170 tons, 749 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0818A-16Q-M — an FXV closed-circuit cooler, 170 nominal tons (749 kW): rated to cool 513 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 47.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection562–937 kWEUOpen in the builder
EVAPCO ATWB 24-7N18 closed-circuit cooler (1091 tons, 4.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-7N18 — an ATWB closed-circuit cooler, 1091 nominal tons (4795 kW): rated to cool 2736 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 111.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3596–5994 kWEUOpen in the builder
Baltimore Aircoil PCC-0349-0718N020 evaporative condenser (2.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0349-0718N020 — a PCC evaporative condenser rejecting 2120 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 29.4 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1590–2650 kWEUOpen in the builder
EVAPCO AT 210-2J24 cooling tower (551 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-2J24 — an AT cooling tower, 551 nominal tons (2423 kW): rated to cool 1659 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 69.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1817–3029 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-2D3ES-L2 closed-circuit cooler (125 tons, 548 kW) — modelled Example modelled from published data
BAC's PFI-0718N-2D3ES-L2 — a PFi closed-circuit cooler, 125 nominal tons (548 kW): rated to cool 375 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 41.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection411–685 kWEUOpen in the builder
EVAPCO ATWB 24-7N20 closed-circuit cooler (1152 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-7N20 — an ATWB closed-circuit cooler, 1152 nominal tons (5066 kW): rated to cool 2890 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 120.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3799–6332 kWEUOpen in the builder
Baltimore Aircoil PT2-1214A-5P cooling tower (583 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1214A-5P — a PT2 cooling tower, 583 nominal tons (2563 kW): rated to cool 1755 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1922–3204 kWEUOpen in the builder
EVAPCO AT 210-2J36 cooling tower (699 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 210-2J36 — an AT cooling tower, 699 nominal tons (3071 kW): rated to cool 2103 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 92.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2304–3839 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-07LC-2 cooling tower (999 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-07LC-2 — a Series 1500 cooling tower, 999 nominal tons (4390 kW): rated to cool 3006 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 109.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3293–5488 kWEUOpen in the builder
EVAPCO ATWB 24-7O18 closed-circuit cooler (1170 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-7O18 — an ATWB closed-circuit cooler, 1170 nominal tons (5142 kW): rated to cool 2934 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 119.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3857–6428 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-12R-2 cooling tower (1829 tons, 8.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-12R-2 — a Series 3000 cooling tower, 1829 nominal tons (8040 kW): rated to cool 5505 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 203.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6030–10050 kWEUOpen in the builder
‹ Previous1…5354555657…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers