Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,273–1,296 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 19-4K12 cooling tower (329 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4K12 — an AT cooling tower, 329 nominal tons (1446 kW): rated to cool 990 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 31.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1084–1807 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-07KN-2 cooling tower (929 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-07KN-2 — a Series 1500 cooling tower, 929 nominal tons (4083 kW): rated to cool 2796 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 102.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3063–5104 kWEUOpen in the builder
EVAPCO ATWB 24-6O18 closed-circuit cooler (1077 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6O18 — an ATWB closed-circuit cooler, 1077 nominal tons (4735 kW): rated to cool 2702 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 123.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3552–5919 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-12Q-2 cooling tower (1731 tons, 7.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-12Q-2 — a Series 3000 cooling tower, 1731 nominal tons (7610 kW): rated to cool 5211 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 192.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5708–9513 kWEUOpen in the builder
EVAPCO AT 19-4K14 cooling tower (360 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4K14 — an AT cooling tower, 360 nominal tons (1582 kW): rated to cool 1083 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1186–1977 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-921-O cooling tower (918 tons, 4.0 MW) — modelled Example modelled from published data
BAC's VT1-921-O — a Series V cooling tower, 918 nominal tons (4035 kW): rated to cool 2763 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 105.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3026–5044 kWEUOpen in the builder
EVAPCO ATWB 24-6O20 closed-circuit cooler (1145 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6O20 — an ATWB closed-circuit cooler, 1145 nominal tons (5035 kW): rated to cool 2873 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 132.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3776–6293 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-072-21N closed-circuit cooler (69 tons, 302 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-072-21N — a Series V closed circuit closed-circuit cooler, 69 nominal tons (302 kW): rated to cool 207 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 23.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection227–378 kWEUOpen in the builder
EVAPCO AT 19-4K9 cooling tower (264 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4K9 — an AT cooling tower, 264 nominal tons (1161 kW): rated to cool 795 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection871–1451 kWEUOpen in the builder
Baltimore Aircoil VCA-1914A evaporative condenser (8.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1914A — a VCA evaporative condenser rejecting 8246 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 119.0 m³/s of the maker's own printed air, with a 89.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection6184–10307 kWEUOpen in the builder
EVAPCO ATWB 24-6P18 closed-circuit cooler (1141 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6P18 — an ATWB closed-circuit cooler, 1141 nominal tons (5016 kW): rated to cool 2862 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 129.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3762–6270 kWEUOpen in the builder
Baltimore Aircoil VRC-0399B-1018N-HB evaporative condenser (2.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0399B-1018N-HB — a Vertex VRC evaporative condenser rejecting 2419 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 54.1 m³/s of the maker's own printed air, with a 25.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1814–3024 kWEUOpen in the builder
EVAPCO AT 19-4L11 cooling tower (313 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4L11 — an AT cooling tower, 313 nominal tons (1376 kW): rated to cool 942 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1032–1720 kWEUOpen in the builder
Baltimore Aircoil CXVB-268-0818-15 evaporative condenser (1.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-268-0818-15 — a CXVB evaporative condenser rejecting 1624 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.7 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1218–2030 kWEUOpen in the builder
EVAPCO ATWB 24-6P20 closed-circuit cooler (1213 tons, 5.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6P20 — an ATWB closed-circuit cooler, 1213 nominal tons (5332 kW): rated to cool 3043 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 139.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3999–6665 kWEUOpen in the builder
Baltimore Aircoil FXV-0818A-16D-K closed-circuit cooler (160 tons, 705 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0818A-16D-K — an FXV closed-circuit cooler, 160 nominal tons (705 kW): rated to cool 483 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection529–882 kWEUOpen in the builder
EVAPCO AT 19-4L12 cooling tower (351 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4L12 — an AT cooling tower, 351 nominal tons (1542 kW): rated to cool 1056 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1157–1928 kWEUOpen in the builder
Baltimore Aircoil PCC-0346-1212N025 evaporative condenser (2.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0346-1212N025 — a PCC evaporative condenser rejecting 2102 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 36.4 m³/s of the maker's own printed air, with a 18.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1576–2627 kWEUOpen in the builder
EVAPCO ATWB 24-7L12 closed-circuit cooler (729 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-7L12 — an ATWB closed-circuit cooler, 729 nominal tons (3203 kW): rated to cool 1828 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 70.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2403–4004 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-2D3DS-K2 closed-circuit cooler (110 tons, 482 kW) — modelled Example modelled from published data
BAC's PFI-0718N-2D3DS-K2 — a PFi closed-circuit cooler, 110 nominal tons (482 kW): rated to cool 330 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection361–602 kWEUOpen in the builder
EVAPCO AT 19-4L14 cooling tower (390 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4L14 — an AT cooling tower, 390 nominal tons (1713 kW): rated to cool 1173 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1285–2141 kWEUOpen in the builder
Baltimore Aircoil PT2-1214A-4P cooling tower (567 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1214A-4P — a PT2 cooling tower, 567 nominal tons (2493 kW): rated to cool 1707 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 55.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1870–3116 kWEUOpen in the builder
EVAPCO ATWB 24-7L14 closed-circuit cooler (801 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-7L14 — an ATWB closed-circuit cooler, 801 nominal tons (3521 kW): rated to cool 2009 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 79.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2641–4401 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-07LC cooling tower (499 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-07LC — a Series 1500 cooling tower, 499 nominal tons (2195 kW): rated to cool 1503 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 54.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1646–2744 kWEUOpen in the builder
‹ Previous1…5253545556…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers