Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1,321–1,344 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 210-2K24 cooling tower (609 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-2K24 — an AT cooling tower, 609 nominal tons (2677 kW): rated to cool 1833 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2008–3346 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-M1050-O cooling tower (1047 tons, 4.6 MW) — modelled Example modelled from published data BAC's VT1-M1050-O — a Series V cooling tower, 1047 nominal tons (4600 kW): rated to cool 3150 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 89.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3450–5751 kW | EU | Open in the builder |
| EVAPCO ATWB 24-7O20 closed-circuit cooler (1236 tons, 5.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-7O20 — an ATWB closed-circuit cooler, 1236 nominal tons (5432 kW): rated to cool 3100 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 128.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4074–6790 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-072-31M closed-circuit cooler (67 tons, 294 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-072-31M — a Series V closed circuit closed-circuit cooler, 67 nominal tons (294 kW): rated to cool 201 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 21.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 220–367 kW | EU | Open in the builder |
| EVAPCO AT 210-2K36 cooling tower (776 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-2K36 — an AT cooling tower, 776 nominal tons (3413 kW): rated to cool 2337 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 101.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2560–4266 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-192A evaporative condenser (827 kW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-192A — a VCA evaporative condenser rejecting 827 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 17.0 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 620–1034 kW | EU | Open in the builder |
| EVAPCO ATWB 24-7P20 closed-circuit cooler (1308 tons, 5.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 24-7P20 — an ATWB closed-circuit cooler, 1308 nominal tons (5750 kW): rated to cool 3281 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 135.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4312–7187 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0405B-1212N-HB evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0405B-1212N-HB — a Vertex VRC evaporative condenser rejecting 2457 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 33.9 m³/s of the maker's own printed air, with a 19.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1843–3071 kW | EU | Open in the builder |
| EVAPCO AT 210-2L24 cooling tower (649 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-2L24 — an AT cooling tower, 649 nominal tons (2852 kW): rated to cool 1953 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 81.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2139–3565 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-281-0818-15 evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-281-0818-15 — a CXVB evaporative condenser rejecting 1702 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1277–2128 kW | EU | Open in the builder |
| EVAPCO ATWB 4-3E12 closed-circuit cooler (66 tons, 288 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 4-3E12 — an ATWB closed-circuit cooler, 66 nominal tons (288 kW): rated to cool 165 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 10.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 216–361 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0818A-23Q-M closed-circuit cooler (208 tons, 916 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0818A-23Q-M — an FXV closed-circuit cooler, 208 nominal tons (916 kW): rated to cool 627 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 45.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 687–1145 kW | EU | Open in the builder |
| EVAPCO AT 210-2L36 cooling tower (837 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-2L36 — an AT cooling tower, 837 nominal tons (3680 kW): rated to cool 2520 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 108.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2760–4600 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0355-1212N025 evaporative condenser (2.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0355-1212N025 — a PCC evaporative condenser rejecting 2156 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 34.7 m³/s of the maker's own printed air, with a 18.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1617–2696 kW | EU | Open in the builder |
| EVAPCO ATWB 4-3E9 closed-circuit cooler (50 tons, 219 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 4-3E9 — an ATWB closed-circuit cooler, 50 nominal tons (219 kW): rated to cool 125 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 8.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 164–274 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0718N-2D4ES-J2 closed-circuit cooler (113 tons, 495 kW) — modelled Example modelled from published data BAC's PFI-0718N-2D4ES-J2 — a PFi closed-circuit cooler, 113 nominal tons (495 kW): rated to cool 339 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 32.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 371–619 kW | EU | Open in the builder |
| EVAPCO AT 210-2M24 cooling tower (682 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-2M24 — an AT cooling tower, 682 nominal tons (2997 kW): rated to cool 2052 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 86.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2248–3746 kW | EU | Open in the builder |
| Baltimore Aircoil PT2-1218A-1P cooling tower (548 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓ BAC's PT2-1218A-1P — a PT2 cooling tower, 548 nominal tons (2410 kW): rated to cool 1650 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1807–3012 kW | EU | Open in the builder |
| EVAPCO ATWB 4-3F12 closed-circuit cooler (74 tons, 326 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 4-3F12 — an ATWB closed-circuit cooler, 74 nominal tons (326 kW): rated to cool 186 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 11.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 245–408 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1218-09JN cooling tower (488 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1218-09JN — a Series 1500 cooling tower, 488 nominal tons (2147 kW): rated to cool 1470 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1610–2684 kW | EU | Open in the builder |
| EVAPCO AT 210-2M36 cooling tower (887 tons, 3.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 210-2M36 — an AT cooling tower, 887 nominal tons (3899 kW): rated to cool 2670 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 115.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2925–4874 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-12S cooling tower (978 tons, 4.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-12S — a Series 3000 cooling tower, 978 nominal tons (4298 kW): rated to cool 2943 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 108.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3224–5373 kW | EU | Open in the builder |
| EVAPCO ATWB 4-3F9 closed-circuit cooler (56 tons, 247 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 4-3F9 — an ATWB closed-circuit cooler, 56 nominal tons (247 kW): rated to cool 141 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 9.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 186–309 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-M1056-P cooling tower (1052 tons, 4.6 MW) — modelled Example modelled from published data BAC's VT1-M1056-P — a Series V cooling tower, 1052 nominal tons (4627 kW): rated to cool 3168 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 100.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3470–5783 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers