Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,249–1,272 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 19-4J12 cooling tower (298 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4J12 — an AT cooling tower, 298 nominal tons (1310 kW): rated to cool 897 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection983–1638 kWEUOpen in the builder
Baltimore Aircoil PT2-1214A-2P cooling tower (518 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1214A-2P — a PT2 cooling tower, 518 nominal tons (2278 kW): rated to cool 1560 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1709–2848 kWEUOpen in the builder
EVAPCO ATWB 24-6M28 closed-circuit cooler (1468 tons, 6.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6M28 — an ATWB closed-circuit cooler, 1468 nominal tons (6451 kW): rated to cool 3681 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 172.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4838–8064 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-07KN cooling tower (464 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-07KN — a Series 1500 cooling tower, 464 nominal tons (2042 kW): rated to cool 1398 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1531–2552 kWEUOpen in the builder
EVAPCO AT 19-4J14 cooling tower (328 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4J14 — an AT cooling tower, 328 nominal tons (1441 kW): rated to cool 987 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 31.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1081–1802 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-12Q cooling tower (866 tons, 3.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-12Q — a Series 3000 cooling tower, 866 nominal tons (3807 kW): rated to cool 2607 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 96.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2856–4759 kWEUOpen in the builder
EVAPCO ATWB 24-6N12 closed-circuit cooler (755 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6N12 — an ATWB closed-circuit cooler, 755 nominal tons (3321 kW): rated to cool 1895 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 83.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2490–4151 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-830-R cooling tower (827 tons, 3.6 MW) — modelled Example modelled from published data
BAC's VT1-830-R — a Series V cooling tower, 827 nominal tons (3637 kW): rated to cool 2490 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2727–4546 kWEUOpen in the builder
EVAPCO AT 19-4J6 cooling tower (170 tons, 749 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4J6 — an AT cooling tower, 170 nominal tons (749 kW): rated to cool 513 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 17.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection562–937 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-072-21M closed-circuit cooler (62 tons, 272 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-072-21M — a Series V closed circuit closed-circuit cooler, 62 nominal tons (272 kW): rated to cool 186 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 21.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection204–340 kWEUOpen in the builder
EVAPCO ATWB 24-6N14 closed-circuit cooler (840 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6N14 — an ATWB closed-circuit cooler, 840 nominal tons (3694 kW): rated to cool 2108 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 93.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2771–4618 kWEUOpen in the builder
Baltimore Aircoil VCA-182A evaporative condenser (784 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-182A — a VCA evaporative condenser rejecting 784 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 14.5 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection588–980 kWEUOpen in the builder
EVAPCO AT 19-4J8 cooling tower (206 tons, 907 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4J8 — an AT cooling tower, 206 nominal tons (907 kW): rated to cool 621 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 20.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection680–1134 kWEUOpen in the builder
Baltimore Aircoil VRC-0386B-1018N-KA evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0386B-1018N-KA — a Vertex VRC evaporative condenser rejecting 2339 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 52.1 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1754–2924 kWEUOpen in the builder
EVAPCO ATWB 24-6N18 closed-circuit cooler (1004 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6N18 — an ATWB closed-circuit cooler, 1004 nominal tons (4412 kW): rated to cool 2517 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 115.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3309–5515 kWEUOpen in the builder
Baltimore Aircoil CXVB-264-1212-10 evaporative condenser (1.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-264-1212-10 — a CXVB evaporative condenser rejecting 1599 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 33.2 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1199–1999 kWEUOpen in the builder
EVAPCO AT 19-4J9 cooling tower (241 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4J9 — an AT cooling tower, 241 nominal tons (1060 kW): rated to cool 726 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection795–1325 kWEUOpen in the builder
Baltimore Aircoil FXV-0818A-12D-M closed-circuit cooler (172 tons, 758 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0818A-12D-M — an FXV closed-circuit cooler, 172 nominal tons (758 kW): rated to cool 519 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 48.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection568–947 kWEUOpen in the builder
EVAPCO ATWB 24-6N20 closed-circuit cooler (1067 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6N20 — an ATWB closed-circuit cooler, 1067 nominal tons (4691 kW): rated to cool 2677 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 124.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3518–5864 kWEUOpen in the builder
Baltimore Aircoil PCC-0330-1212N025 evaporative condenser (2.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0330-1212N025 — a PCC evaporative condenser rejecting 2005 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 38.5 m³/s of the maker's own printed air, with a 18.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1503–2506 kWEUOpen in the builder
EVAPCO AT 19-4K11 cooling tower (297 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4K11 — an AT cooling tower, 297 nominal tons (1306 kW): rated to cool 894 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection979–1632 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-2D1DS-J2 closed-circuit cooler (97 tons, 425 kW) — modelled Example modelled from published data
BAC's PFI-0718N-2D1DS-J2 — a PFi closed-circuit cooler, 97 nominal tons (425 kW): rated to cool 291 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 36.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection319–531 kWEUOpen in the builder
EVAPCO ATWB 24-6N28 closed-circuit cooler (1611 tons, 7.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6N28 — an ATWB closed-circuit cooler, 1611 nominal tons (7081 kW): rated to cool 4040 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 186.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5311–8851 kWEUOpen in the builder
Baltimore Aircoil PT2-1214A-3P cooling tower (555 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1214A-3P — a PT2 cooling tower, 555 nominal tons (2440 kW): rated to cool 1671 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 54.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1830–3051 kWEUOpen in the builder
‹ Previous1…5152535455…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers