Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1249–1272 of 3346

EVAPCO AT 110-3K18 cooling tower (436 tons, 1.9 MW) — modelled

EVAPCO's 110-3K18 — a AT cooling tower, 436 nominal tons (1915 kW): rated to cool 1311 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 49.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1436–2393 kW · EU

EVAPCO AT 110-3L12 cooling tower (360 tons, 1.6 MW) — modelled

EVAPCO's 110-3L12 — a AT cooling tower, 360 nominal tons (1582 kW): rated to cool 1083 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 40.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1186–1977 kW · EU

EVAPCO AT 110-3L18 cooling tower (469 tons, 2.1 MW) — modelled

EVAPCO's 110-3L18 — a AT cooling tower, 469 nominal tons (2064 kW): rated to cool 1413 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1548–2580 kW · EU

EVAPCO AT 110-3M12 cooling tower (379 tons, 1.7 MW) — modelled

EVAPCO's 110-3M12 — a AT cooling tower, 379 nominal tons (1665 kW): rated to cool 1140 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1249–2081 kW · EU

EVAPCO AT 110-3M18 cooling tower (497 tons, 2.2 MW) — modelled

EVAPCO's 110-3M18 — a AT cooling tower, 497 nominal tons (2186 kW): rated to cool 1497 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1640–2733 kW · EU

EVAPCO AT 110-3N18 cooling tower (545 tons, 2.4 MW) — modelled

EVAPCO's 110-3N18 — a AT cooling tower, 545 nominal tons (2397 kW): rated to cool 1641 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1797–2996 kW · EU

EVAPCO AT 110-4I12 cooling tower (276 tons, 1.2 MW) — modelled

EVAPCO's 110-4I12 — a AT cooling tower, 276 nominal tons (1214 kW): rated to cool 831 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 910–1517 kW · EU

EVAPCO AT 110-4I18 cooling tower (363 tons, 1.6 MW) — modelled

EVAPCO's 110-4I18 — a AT cooling tower, 363 nominal tons (1595 kW): rated to cool 1092 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1196–1994 kW · EU

EVAPCO AT 110-4J12 cooling tower (321 tons, 1.4 MW) — modelled

EVAPCO's 110-4J12 — a AT cooling tower, 321 nominal tons (1411 kW): rated to cool 966 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1058–1764 kW · EU

EVAPCO AT 110-4J18 cooling tower (419 tons, 1.8 MW) — modelled

EVAPCO's 110-4J18 — a AT cooling tower, 419 nominal tons (1840 kW): rated to cool 1260 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 44.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1380–2300 kW · EU

EVAPCO AT 110-4K12 cooling tower (349 tons, 1.5 MW) — modelled

EVAPCO's 110-4K12 — a AT cooling tower, 349 nominal tons (1533 kW): rated to cool 1050 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1150–1917 kW · EU

EVAPCO AT 110-4K18 cooling tower (458 tons, 2.0 MW) — modelled

EVAPCO's 110-4K18 — a AT cooling tower, 458 nominal tons (2015 kW): rated to cool 1380 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 49.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1512–2519 kW · EU

EVAPCO AT 110-4L12 cooling tower (372 tons, 1.6 MW) — modelled

EVAPCO's 110-4L12 — a AT cooling tower, 372 nominal tons (1634 kW): rated to cool 1119 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 39.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1226–2043 kW · EU

EVAPCO AT 110-4L18 cooling tower (491 tons, 2.2 MW) — modelled

EVAPCO's 110-4L18 — a AT cooling tower, 491 nominal tons (2160 kW): rated to cool 1479 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1620–2700 kW · EU

EVAPCO AT 110-4M12 cooling tower (392 tons, 1.7 MW) — modelled

EVAPCO's 110-4M12 — a AT cooling tower, 392 nominal tons (1722 kW): rated to cool 1179 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1291–2152 kW · EU

EVAPCO AT 110-4M18 cooling tower (520 tons, 2.3 MW) — modelled

EVAPCO's 110-4M18 — a AT cooling tower, 520 nominal tons (2287 kW): rated to cool 1566 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 55.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1715–2859 kW · EU

EVAPCO AT 110-4N12 cooling tower (409 tons, 1.8 MW) — modelled

EVAPCO's 110-4N12 — a AT cooling tower, 409 nominal tons (1796 kW): rated to cool 1230 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 43.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1347–2245 kW · EU

EVAPCO AT 110-4N18 cooling tower (568 tons, 2.5 MW) — modelled

EVAPCO's 110-4N18 — a AT cooling tower, 568 nominal tons (2497 kW): rated to cool 1710 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1873–3122 kW · EU

EVAPCO AT 112-2I12 cooling tower (279 tons, 1.2 MW) — modelled

EVAPCO's 112-2I12 — a AT cooling tower, 279 nominal tons (1227 kW): rated to cool 840 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 920–1533 kW · EU

EVAPCO AT 112-2I14 cooling tower (298 tons, 1.3 MW) — modelled

EVAPCO's 112-2I14 — a AT cooling tower, 298 nominal tons (1310 kW): rated to cool 897 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 983–1638 kW · EU

EVAPCO AT 112-2J12 cooling tower (333 tons, 1.5 MW) — modelled

EVAPCO's 112-2J12 — a AT cooling tower, 333 nominal tons (1463 kW): rated to cool 1002 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1098–1829 kW · EU

EVAPCO AT 112-2J14 cooling tower (358 tons, 1.6 MW) — modelled

EVAPCO's 112-2J14 — a AT cooling tower, 358 nominal tons (1573 kW): rated to cool 1077 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1180–1966 kW · EU

EVAPCO AT 112-2J18 cooling tower (438 tons, 1.9 MW) — modelled

EVAPCO's 112-2J18 — a AT cooling tower, 438 nominal tons (1923 kW): rated to cool 1317 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published data
Cooling tower / heat rejection · 1443–2404 kW · EU

EVAPCO AT 112-2K12 cooling tower (363 tons, 1.6 MW) — modelled

EVAPCO's 112-2K12 — a AT cooling tower, 363 nominal tons (1595 kW): rated to cool 1092 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1196–1994 kW · EU
‹ Previous1…5152535455…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers