Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,201–1,224 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 19-4H12 cooling tower (242 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4H12 — an AT cooling tower, 242 nominal tons (1065 kW): rated to cool 729 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 23.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection799–1331 kWEUOpen in the builder
Baltimore Aircoil PFI-0709N-6D1ES-M1 closed-circuit cooler (99 tons, 434 kW) — modelled Example modelled from published data
BAC's PFI-0709N-6D1ES-M1 — a PFi closed-circuit cooler, 99 nominal tons (434 kW): rated to cool 297 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 19.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection325–542 kWEUOpen in the builder
EVAPCO ATWB 24-5N14 closed-circuit cooler (765 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-5N14 — an ATWB closed-circuit cooler, 765 nominal tons (3363 kW): rated to cool 1919 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 96.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2522–4203 kWEUOpen in the builder
Baltimore Aircoil PT2-1212A-5P cooling tower (531 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1212A-5P — a PT2 cooling tower, 531 nominal tons (2335 kW): rated to cool 1599 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 49.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1751–2919 kWEUOpen in the builder
EVAPCO AT 19-4H14 cooling tower (265 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4H14 — an AT cooling tower, 265 nominal tons (1165 kW): rated to cool 798 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection874–1457 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-07JN cooling tower (426 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-07JN — a Series 1500 cooling tower, 426 nominal tons (1871 kW): rated to cool 1281 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1403–2339 kWEUOpen in the builder
EVAPCO ATWB 24-5N18 closed-circuit cooler (930 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-5N18 — an ATWB closed-circuit cooler, 930 nominal tons (4089 kW): rated to cool 2333 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 119.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3066–5111 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-12P cooling tower (809 tons, 3.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-12P — a Series 3000 cooling tower, 809 nominal tons (3558 kW): rated to cool 2436 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 90.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2668–4447 kWEUOpen in the builder
EVAPCO AT 19-4H6 cooling tower (143 tons, 627 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4H6 — an AT cooling tower, 143 nominal tons (627 kW): rated to cool 429 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 13.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection470–783 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-800-Q cooling tower (797 tons, 3.5 MW) — modelled Example modelled from published data
BAC's VT1-800-Q — a Series V cooling tower, 797 nominal tons (3505 kW): rated to cool 2400 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 80.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2629–4381 kWEUOpen in the builder
EVAPCO ATWB 24-5N20 closed-circuit cooler (995 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-5N20 — an ATWB closed-circuit cooler, 995 nominal tons (4375 kW): rated to cool 2496 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 128.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3281–5468 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-048-41M closed-circuit cooler (63 tons, 276 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-048-41M — a Series V closed circuit closed-circuit cooler, 63 nominal tons (276 kW): rated to cool 189 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 16.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection207–345 kWEUOpen in the builder
EVAPCO AT 19-4H8 cooling tower (172 tons, 758 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4H8 — an AT cooling tower, 172 nominal tons (758 kW): rated to cool 519 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 16.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection568–947 kWEUOpen in the builder
Baltimore Aircoil VCA-178A evaporative condenser (767 kW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-178A — a VCA evaporative condenser rejecting 767 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 12.9 m³/s of the maker's own printed air, with a 5.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection575–959 kWEUOpen in the builder
EVAPCO ATWB 24-5O18 closed-circuit cooler (999 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-5O18 — an ATWB closed-circuit cooler, 999 nominal tons (4393 kW): rated to cool 2506 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 127.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3294–5491 kWEUOpen in the builder
Baltimore Aircoil VRC-0383B-1212N-JB evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0383B-1212N-JB — a Vertex VRC evaporative condenser rejecting 2326 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 45.0 m³/s of the maker's own printed air, with a 30.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1745–2908 kWEUOpen in the builder
EVAPCO AT 19-4H9 cooling tower (190 tons, 837 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4H9 — an AT cooling tower, 190 nominal tons (837 kW): rated to cool 573 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 18.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection628–1046 kWEUOpen in the builder
Baltimore Aircoil CXVB-248-0818-15 evaporative condenser (1.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-248-0818-15 — a CXVB evaporative condenser rejecting 1503 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 42.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1127–1878 kWEUOpen in the builder
EVAPCO ATWB 24-5O20 closed-circuit cooler (1069 tons, 4.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-5O20 — an ATWB closed-circuit cooler, 1069 nominal tons (4699 kW): rated to cool 2681 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 137.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3524–5874 kWEUOpen in the builder
Baltimore Aircoil CXVT-965-1426-60 evaporative condenser (5.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVT-965-1426-60 — a CXVT evaporative condenser rejecting 5861 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 106.6 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection4396–7326 kWEUOpen in the builder
EVAPCO AT 19-4I11 cooling tower (237 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4I11 — an AT cooling tower, 237 nominal tons (1043 kW): rated to cool 714 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 22.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection782–1303 kWEUOpen in the builder
Baltimore Aircoil FXV-0812B-32Q-O closed-circuit cooler (186 tons, 819 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0812B-32Q-O — an FXV closed-circuit cooler, 186 nominal tons (819 kW): rated to cool 561 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection614–1024 kWEUOpen in the builder
EVAPCO ATWB 24-5P20 closed-circuit cooler (1133 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-5P20 — an ATWB closed-circuit cooler, 1133 nominal tons (4980 kW): rated to cool 2842 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 144.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3735–6225 kWEUOpen in the builder
Baltimore Aircoil PCC-0324-0718N020 evaporative condenser (2.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0324-0718N020 — a PCC evaporative condenser rejecting 1968 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 40.4 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1476–2460 kWEUOpen in the builder
‹ Previous1…4950515253…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers