Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,225–1,248 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 19-4I12 cooling tower (267 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4I12 — an AT cooling tower, 267 nominal tons (1174 kW): rated to cool 804 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection881–1468 kWEUOpen in the builder
Baltimore Aircoil PFI-0709N-6D2ES-L1 closed-circuit cooler (93 tons, 407 kW) — modelled Example modelled from published data
BAC's PFI-0709N-6D2ES-L1 — a PFi closed-circuit cooler, 93 nominal tons (407 kW): rated to cool 279 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 17.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection306–509 kWEUOpen in the builder
EVAPCO ATWB 24-6L12 closed-circuit cooler (648 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6L12 — an ATWB closed-circuit cooler, 648 nominal tons (2850 kW): rated to cool 1626 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 73.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2138–3563 kWEUOpen in the builder
Baltimore Aircoil PT2-1214A-1O cooling tower (421 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11L-07R05) ✓
BAC's PT2-1214A-1O — a PT2 cooling tower, 421 nominal tons (1849 kW): rated to cool 1266 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 55.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1387–2311 kWEUOpen in the builder
EVAPCO AT 19-4I14 cooling tower (294 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4I14 — an AT cooling tower, 294 nominal tons (1293 kW): rated to cool 885 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection969–1616 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-07JN-2 cooling tower (851 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-07JN-2 — a Series 1500 cooling tower, 851 nominal tons (3742 kW): rated to cool 2562 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 94.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2806–4677 kWEUOpen in the builder
EVAPCO ATWB 24-6L14 closed-circuit cooler (722 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6L14 — an ATWB closed-circuit cooler, 722 nominal tons (3174 kW): rated to cool 1811 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 81.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2380–3967 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-12P-2 cooling tower (1619 tons, 7.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-12P-2 — a Series 3000 cooling tower, 1619 nominal tons (7115 kW): rated to cool 4872 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 180.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5337–8894 kWEUOpen in the builder
EVAPCO AT 19-4I6 cooling tower (156 tons, 688 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4I6 — an AT cooling tower, 156 nominal tons (688 kW): rated to cool 471 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 15.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection516–860 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-825-P cooling tower (822 tons, 3.6 MW) — modelled Example modelled from published data
BAC's VT1-825-P — a Series V cooling tower, 822 nominal tons (3615 kW): rated to cool 2475 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 116.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2711–4518 kWEUOpen in the builder
EVAPCO ATWB 24-6L28 closed-circuit cooler (1383 tons, 6.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6L28 — an ATWB closed-circuit cooler, 1383 nominal tons (6078 kW): rated to cool 3468 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 163.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4559–7598 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-048-41N closed-circuit cooler (70 tons, 307 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓
BAC's VF1-048-41N — a Series V closed circuit closed-circuit cooler, 70 nominal tons (307 kW): rated to cool 210 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 17.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection230–383 kWEUOpen in the builder
EVAPCO AT 19-4I8 cooling tower (186 tons, 819 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4I8 — an AT cooling tower, 186 nominal tons (819 kW): rated to cool 561 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 17.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection614–1024 kWEUOpen in the builder
Baltimore Aircoil VCA-1790A evaporative condenser (7.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-1790A — a VCA evaporative condenser rejecting 7712 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 108.5 m³/s of the maker's own printed air, with a 67.1 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection5784–9639 kWEUOpen in the builder
EVAPCO ATWB 24-6M12 closed-circuit cooler (688 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6M12 — an ATWB closed-circuit cooler, 688 nominal tons (3025 kW): rated to cool 1726 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 77.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2269–3782 kWEUOpen in the builder
Baltimore Aircoil VRC-0384B-1212N-LA evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0384B-1212N-LA — a Vertex VRC evaporative condenser rejecting 2331 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 38.5 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1748–2913 kWEUOpen in the builder
EVAPCO AT 19-4I9 cooling tower (208 tons, 916 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4I9 — an AT cooling tower, 208 nominal tons (916 kW): rated to cool 627 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 20.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection687–1145 kWEUOpen in the builder
Baltimore Aircoil CXVB-259-0812-20 evaporative condenser (1.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-259-0812-20 — a CXVB evaporative condenser rejecting 1569 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 33.6 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1177–1961 kWEUOpen in the builder
EVAPCO ATWB 24-6M14 closed-circuit cooler (766 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6M14 — an ATWB closed-circuit cooler, 766 nominal tons (3367 kW): rated to cool 1921 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 86.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2526–4209 kWEUOpen in the builder
Baltimore Aircoil FXV-0812B-36T-O closed-circuit cooler (200 tons, 881 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-0812B-36T-O — an FXV closed-circuit cooler, 200 nominal tons (881 kW): rated to cool 603 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection660–1101 kWEUOpen in the builder
EVAPCO AT 19-4J11 cooling tower (269 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 19-4J11 — an AT cooling tower, 269 nominal tons (1183 kW): rated to cool 810 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 26.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection887–1479 kWEUOpen in the builder
Baltimore Aircoil PCC-0328-1012N030 evaporative condenser (2.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0328-1012N030 — a PCC evaporative condenser rejecting 1992 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 31.7 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1494–2490 kWEUOpen in the builder
EVAPCO ATWB 24-6M18 closed-circuit cooler (915 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 24-6M18 — an ATWB closed-circuit cooler, 915 nominal tons (4024 kW): rated to cool 2296 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 106.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3018–5030 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-2D1DS-H2 closed-circuit cooler (91 tons, 399 kW) — modelled Example modelled from published data
BAC's PFI-0718N-2D1DS-H2 — a PFi closed-circuit cooler, 91 nominal tons (399 kW): rated to cool 273 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 32.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection299–498 kWEUOpen in the builder
‹ Previous1…5051525354…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers