Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1225–1248 of 3346

Baltimore Aircoil PT2-1212A-4P cooling tower (510 tons, 2.2 MW) — modelled

BAC's PT2-1212A-4P — a PT2 cooling tower, 510 nominal tons (2243 kW): rated to cool 1536 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11L-07R05) ✓
Cooling tower / heat rejection · 1682–2804 kW · EU

Baltimore Aircoil PT2-1212A-5P cooling tower (531 tons, 2.3 MW) — modelled

BAC's PT2-1212A-5P — a PT2 cooling tower, 531 nominal tons (2335 kW): rated to cool 1599 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 49.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11L-07R05) ✓
Cooling tower / heat rejection · 1751–2919 kW · EU

Baltimore Aircoil PT2-1214A-1O cooling tower (421 tons, 1.8 MW) — modelled

BAC's PT2-1214A-1O — a PT2 cooling tower, 421 nominal tons (1849 kW): rated to cool 1266 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 55.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11L-07R05) ✓
Cooling tower / heat rejection · 1387–2311 kW · EU

Baltimore Aircoil PT2-1214A-2P cooling tower (518 tons, 2.3 MW) — modelled

BAC's PT2-1214A-2P — a PT2 cooling tower, 518 nominal tons (2278 kW): rated to cool 1560 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11L-07R05) ✓
Cooling tower / heat rejection · 1709–2848 kW · EU

Baltimore Aircoil PT2-1214A-3P cooling tower (555 tons, 2.4 MW) — modelled

BAC's PT2-1214A-3P — a PT2 cooling tower, 555 nominal tons (2440 kW): rated to cool 1671 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 54.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11L-07R05) ✓
Cooling tower / heat rejection · 1830–3051 kW · EU

Baltimore Aircoil PT2-1214A-4P cooling tower (567 tons, 2.5 MW) — modelled

BAC's PT2-1214A-4P — a PT2 cooling tower, 567 nominal tons (2493 kW): rated to cool 1707 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 55.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11L-07R05) ✓
Cooling tower / heat rejection · 1870–3116 kW · EU

Baltimore Aircoil PT2-1214A-5P cooling tower (583 tons, 2.6 MW) — modelled

BAC's PT2-1214A-5P — a PT2 cooling tower, 583 nominal tons (2563 kW): rated to cool 1755 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11L-07R05) ✓
Cooling tower / heat rejection · 1922–3204 kW · EU

Baltimore Aircoil PT2-1218A-1P cooling tower (548 tons, 2.4 MW) — modelled

BAC's PT2-1218A-1P — a PT2 cooling tower, 548 nominal tons (2410 kW): rated to cool 1650 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11L-07R05) ✓
Cooling tower / heat rejection · 1807–3012 kW · EU

Baltimore Aircoil PT2-1218A-2Q cooling tower (672 tons, 3.0 MW) — modelled

BAC's PT2-1218A-2Q — a PT2 cooling tower, 672 nominal tons (2953 kW): rated to cool 2022 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 74.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C11L-07R05) ✓
Cooling tower / heat rejection · 2215–3691 kW · EU

EVAPCO AT 110-2I12 cooling tower (226 tons, 995 kW) — modelled

EVAPCO's 110-2I12 — a AT cooling tower, 226 nominal tons (995 kW): rated to cool 681 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 746–1243 kW · EU

EVAPCO AT 110-2I18 cooling tower (289 tons, 1.3 MW) — modelled

EVAPCO's 110-2I18 — a AT cooling tower, 289 nominal tons (1271 kW): rated to cool 870 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 40.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 953–1588 kW · EU

EVAPCO AT 110-2J12 cooling tower (275 tons, 1.2 MW) — modelled

EVAPCO's 110-2J12 — a AT cooling tower, 275 nominal tons (1209 kW): rated to cool 828 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 907–1512 kW · EU

EVAPCO AT 110-2J18 cooling tower (350 tons, 1.5 MW) — modelled

EVAPCO's 110-2J18 — a AT cooling tower, 350 nominal tons (1538 kW): rated to cool 1053 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1153–1922 kW · EU

EVAPCO AT 110-2K12 cooling tower (304 tons, 1.3 MW) — modelled

EVAPCO's 110-2K12 — a AT cooling tower, 304 nominal tons (1336 kW): rated to cool 915 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1002–1670 kW · EU

EVAPCO AT 110-2K18 cooling tower (388 tons, 1.7 MW) — modelled

EVAPCO's 110-2K18 — a AT cooling tower, 388 nominal tons (1704 kW): rated to cool 1167 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1278–2130 kW · EU

EVAPCO AT 110-2L12 cooling tower (325 tons, 1.4 MW) — modelled

EVAPCO's 110-2L12 — a AT cooling tower, 325 nominal tons (1428 kW): rated to cool 978 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 40.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1071–1785 kW · EU

EVAPCO AT 110-2L18 cooling tower (419 tons, 1.8 MW) — modelled

EVAPCO's 110-2L18 — a AT cooling tower, 419 nominal tons (1840 kW): rated to cool 1260 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 54.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1380–2300 kW · EU

EVAPCO AT 110-2M12 cooling tower (341 tons, 1.5 MW) — modelled

EVAPCO's 110-2M12 — a AT cooling tower, 341 nominal tons (1498 kW): rated to cool 1026 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 43.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1124–1873 kW · EU

EVAPCO AT 110-2M18 cooling tower (444 tons, 1.9 MW) — modelled

EVAPCO's 110-2M18 — a AT cooling tower, 444 nominal tons (1950 kW): rated to cool 1335 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1462–2437 kW · EU

EVAPCO AT 110-3I12 cooling tower (263 tons, 1.2 MW) — modelled

EVAPCO's 110-3I12 — a AT cooling tower, 263 nominal tons (1157 kW): rated to cool 792 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 868–1446 kW · EU

EVAPCO AT 110-3I18 cooling tower (332 tons, 1.5 MW) — modelled

EVAPCO's 110-3I18 — a AT cooling tower, 332 nominal tons (1459 kW): rated to cool 999 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 40.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1094–1824 kW · EU

EVAPCO AT 110-3J12 cooling tower (308 tons, 1.4 MW) — modelled

EVAPCO's 110-3J12 — a AT cooling tower, 308 nominal tons (1354 kW): rated to cool 927 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1015–1692 kW · EU

EVAPCO AT 110-3J18 cooling tower (394 tons, 1.7 MW) — modelled

EVAPCO's 110-3J18 — a AT cooling tower, 394 nominal tons (1731 kW): rated to cool 1185 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1298–2163 kW · EU

EVAPCO AT 110-3K12 cooling tower (337 tons, 1.5 MW) — modelled

EVAPCO's 110-3K12 — a AT cooling tower, 337 nominal tons (1481 kW): rated to cool 1014 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1111–1851 kW · EU
‹ Previous1…5051525354…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers