Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1,441–1,464 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 212-2G9 cooling tower (224 tons, 986 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-2G9 — an AT cooling tower, 224 nominal tons (986 kW): rated to cool 675 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 739–1232 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1218-09LC-2 cooling tower (1140 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1218-09LC-2 — a Series 1500 cooling tower, 1140 nominal tons (5012 kW): rated to cool 3432 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 123.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3759–6265 kW | EU | Open in the builder |
| EVAPCO ATWB 7-5J9 closed-circuit cooler (144 tons, 632 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-5J9 — an ATWB closed-circuit cooler, 144 nominal tons (632 kW): rated to cool 361 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 18.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 474–790 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-13Q-2 cooling tower (1788 tons, 7.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-13Q-2 — a Series 3000 cooling tower, 1788 nominal tons (7860 kW): rated to cool 5382 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 198.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5895–9825 kW | EU | Open in the builder |
| EVAPCO AT 212-2H9 cooling tower (246 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-2H9 — an AT cooling tower, 246 nominal tons (1082 kW): rated to cool 741 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 812–1353 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-M316-O cooling tower (315 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VT1-M316-O — a Series V cooling tower, 315 nominal tons (1385 kW): rated to cool 948 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 31.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1038–1731 kW | EU | Open in the builder |
| EVAPCO ATWB 7-5K12 closed-circuit cooler (199 tons, 874 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-5K12 — an ATWB closed-circuit cooler, 199 nominal tons (874 kW): rated to cool 499 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 24.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 656–1093 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-096-31O closed-circuit cooler (81 tons, 355 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-096-31O — a Series V closed circuit closed-circuit cooler, 81 nominal tons (355 kW): rated to cool 243 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 25.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 266–444 kW | EU | Open in the builder |
| EVAPCO AT 212-2I24 cooling tower (558 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-2I24 — an AT cooling tower, 558 nominal tons (2454 kW): rated to cool 1680 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 67.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1840–3067 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-259A evaporative condenser (1.1 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-259A — a VCA evaporative condenser rejecting 1116 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 21.0 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 837–1395 kW | EU | Open in the builder |
| EVAPCO ATWB 7-6H18 closed-circuit cooler (273 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-6H18 — an ATWB closed-circuit cooler, 273 nominal tons (1198 kW): rated to cool 684 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 29.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 899–1498 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0427B-1018N-KA evaporative condenser (2.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0427B-1018N-KA — a Vertex VRC evaporative condenser rejecting 2585 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 49.7 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1939–3231 kW | EU | Open in the builder |
| EVAPCO AT 212-2I28 cooling tower (596 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-2I28 — an AT cooling tower, 596 nominal tons (2620 kW): rated to cool 1794 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 73.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1965–3275 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-306-1212-10 evaporative condenser (1.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-306-1212-10 — a CXVB evaporative condenser rejecting 1854 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.6 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1390–2317 kW | EU | Open in the builder |
| EVAPCO ATWB 7-6I18 closed-circuit cooler (299 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-6I18 — an ATWB closed-circuit cooler, 299 nominal tons (1312 kW): rated to cool 749 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 32.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 984–1640 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0818B-12D-O closed-circuit cooler (205 tons, 903 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0818B-12D-O — an FXV closed-circuit cooler, 205 nominal tons (903 kW): rated to cool 618 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 61.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 677–1128 kW | EU | Open in the builder |
| EVAPCO AT 212-2J24 cooling tower (665 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-2J24 — an AT cooling tower, 665 nominal tons (2922 kW): rated to cool 2001 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2192–3653 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0406-1212N040 evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0406-1212N040 — a PCC evaporative condenser rejecting 2466 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 39.9 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1850–3083 kW | EU | Open in the builder |
| EVAPCO ATWB 7-6J18 closed-circuit cooler (339 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-6J18 — an ATWB closed-circuit cooler, 339 nominal tons (1490 kW): rated to cool 850 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 36.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1117–1862 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0718N-3D2DS-K2 closed-circuit cooler (136 tons, 596 kW) — modelled Example modelled from published data BAC's PFI-0718N-3D2DS-K2 — a PFi closed-circuit cooler, 136 nominal tons (596 kW): rated to cool 408 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 37.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 447–745 kW | EU | Open in the builder |
| EVAPCO AT 212-2J28 cooling tower (715 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-2J28 — an AT cooling tower, 715 nominal tons (3141 kW): rated to cool 2151 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 83.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2356–3927 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1218-09LN cooling tower (604 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1218-09LN — a Series 1500 cooling tower, 604 nominal tons (2655 kW): rated to cool 1818 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1991–3319 kW | EU | Open in the builder |
| EVAPCO ATWB 7-6J9 closed-circuit cooler (165 tons, 724 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 7-6J9 — an ATWB closed-circuit cooler, 165 nominal tons (724 kW): rated to cool 413 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 18.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 543–905 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-13R cooling tower (944 tons, 4.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-13R — a Series 3000 cooling tower, 944 nominal tons (4149 kW): rated to cool 2841 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 104.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3112–5186 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers