Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1,513–1,536 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 212-2M40 cooling tower (1084 tons, 4.8 MW) — modelled Example modelled from published data EVAPCO's 212-2M40 — an AT cooling tower, 1084 nominal tons (4767 kW): rated to cool 3264 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 132.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3575–5959 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-315-1212-10 evaporative condenser (1.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-315-1212-10 — a CXVB evaporative condenser rejecting 1908 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.2 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1431–2386 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3I21 closed-circuit cooler (307 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3I21 — an ATWB closed-circuit cooler, 307 nominal tons (1349 kW): rated to cool 770 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 43.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1012–1687 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0818B-24T-O closed-circuit cooler (274 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0818B-24T-O — an FXV closed-circuit cooler, 274 nominal tons (1205 kW): rated to cool 825 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 59.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 904–1506 kW | EU | Open in the builder |
| EVAPCO AT 212-2N36 cooling tower (1215 tons, 5.3 MW) — modelled Example modelled from published data EVAPCO's 212-2N36 — an AT cooling tower, 1215 nominal tons (5341 kW): rated to cool 3657 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 142.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4006–6676 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0431-1220N015 evaporative condenser (2.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0431-1220N015 — a PCC evaporative condenser rejecting 2618 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 52.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1964–3273 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3I8 closed-circuit cooler (96 tons, 424 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3I8 — an ATWB closed-circuit cooler, 96 nominal tons (424 kW): rated to cool 242 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 17.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 318–529 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0718N-4D2ES-L2 closed-circuit cooler (179 tons, 789 kW) — modelled Example modelled from published data BAC's PFI-0718N-4D2ES-L2 — a PFi closed-circuit cooler, 179 nominal tons (789 kW): rated to cool 540 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 591–986 kW | EU | Open in the builder |
| EVAPCO AT 212-2N40 cooling tower (1246 tons, 5.5 MW) — modelled Example modelled from published data EVAPCO's 212-2N40 — an AT cooling tower, 1246 nominal tons (5477 kW): rated to cool 3750 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 144.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4108–6846 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1218-10KN-2 cooling tower (1118 tons, 4.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1218-10KN-2 — a Series 1500 cooling tower, 1118 nominal tons (4916 kW): rated to cool 3366 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 120.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3687–6145 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3J11 closed-circuit cooler (143 tons, 628 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3J11 — an ATWB closed-circuit cooler, 143 nominal tons (628 kW): rated to cool 358 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 24.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 471–785 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1222-13S-2 cooling tower (2018 tons, 8.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1222-13S-2 — a Series 3000 cooling tower, 2018 nominal tons (8872 kW): rated to cool 6075 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 222.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 6654–11090 kW | EU | Open in the builder |
| EVAPCO AT 212-2O40 cooling tower (1352 tons, 5.9 MW) — modelled Example modelled from published data EVAPCO's 212-2O40 — an AT cooling tower, 1352 nominal tons (5946 kW): rated to cool 4071 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 155.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4459–7432 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-M352-P cooling tower (351 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VT1-M352-P — a Series V cooling tower, 351 nominal tons (1542 kW): rated to cool 1056 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1157–1928 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3J14 closed-circuit cooler (190 tons, 835 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3J14 — an ATWB closed-circuit cooler, 190 nominal tons (835 kW): rated to cool 477 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 30.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 626–1044 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-096-41P closed-circuit cooler (99 tons, 434 kW) — modelled Example modelled from published data CTI STD-201 (validation C11K-00R03) ✓ BAC's VF1-096-41P — a Series V closed circuit closed-circuit cooler, 99 nominal tons (434 kW): rated to cool 297 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 27.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 325–542 kW | EU | Open in the builder |
| EVAPCO AT 212-3F9 cooling tower (202 tons, 889 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-3F9 — an AT cooling tower, 202 nominal tons (889 kW): rated to cool 609 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 21.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 667–1112 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-301A evaporative condenser (1.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-301A — a VCA evaporative condenser rejecting 1297 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 22.9 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 973–1621 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3J18 closed-circuit cooler (304 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3J18 — an ATWB closed-circuit cooler, 304 nominal tons (1334 kW): rated to cool 761 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 44.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1001–1668 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0441B-1018N-JB evaporative condenser (2.7 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0441B-1018N-JB — a Vertex VRC evaporative condenser rejecting 2675 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 62.8 m³/s of the maker's own printed air, with a 40.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2006–3344 kW | EU | Open in the builder |
| EVAPCO AT 212-3G9 cooling tower (249 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 212-3G9 — an AT cooling tower, 249 nominal tons (1095 kW): rated to cool 750 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 24.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 822–1369 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-321-0818-15 evaporative condenser (1.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-321-0818-15 — a CXVB evaporative condenser rejecting 1945 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.0 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1459–2431 kW | EU | Open in the builder |
| EVAPCO ATWB 9-3J21 closed-circuit cooler (350 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-3J21 — an ATWB closed-circuit cooler, 350 nominal tons (1538 kW): rated to cool 877 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 49.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1153–1922 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-0818B-30T-K closed-circuit cooler (226 tons, 995 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-0818B-30T-K — an FXV closed-circuit cooler, 226 nominal tons (995 kW): rated to cool 681 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 41.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 746–1243 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers