Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,609–1,632 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 212-3N28 cooling tower (1093 tons, 4.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-3N28 — an AT cooling tower, 1093 nominal tons (4806 kW): rated to cool 3291 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 111.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3605–6008 kWEUOpen in the builder
Baltimore Aircoil VCA-323A evaporative condenser (1.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-323A — a VCA evaporative condenser rejecting 1392 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 27.9 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1044–1739 kWEUOpen in the builder
EVAPCO ATWB 9-4J21 closed-circuit cooler (366 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-4J21 — an ATWB closed-circuit cooler, 366 nominal tons (1608 kW): rated to cool 917 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 47.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1206–2010 kWEUOpen in the builder
Baltimore Aircoil VRC-0456B-1218N-JA evaporative condenser (2.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0456B-1218N-JA — a Vertex VRC evaporative condenser rejecting 2766 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 47.0 m³/s of the maker's own printed air, with a 16.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2074–3457 kWEUOpen in the builder
EVAPCO AT 212-3N36 cooling tower (1346 tons, 5.9 MW) — modelled Example modelled from published data
EVAPCO's 212-3N36 — an AT cooling tower, 1346 nominal tons (5915 kW): rated to cool 4050 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 139.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4436–7394 kWEUOpen in the builder
Baltimore Aircoil CXVB-341-1212-20 evaporative condenser (2.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-341-1212-20 — a CXVB evaporative condenser rejecting 2066 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 41.2 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1549–2582 kWEUOpen in the builder
EVAPCO ATWB 9-4J8 closed-circuit cooler (126 tons, 553 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-4J8 — an ATWB closed-circuit cooler, 126 nominal tons (553 kW): rated to cool 316 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 18.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection415–691 kWEUOpen in the builder
Baltimore Aircoil FXV-1212B-16D-O closed-circuit cooler (184 tons, 811 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212B-16D-O — an FXV closed-circuit cooler, 184 nominal tons (811 kW): rated to cool 555 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 46.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection608–1013 kWEUOpen in the builder
EVAPCO AT 212-3N40 cooling tower (1391 tons, 6.1 MW) — modelled Example modelled from published data
EVAPCO's 212-3N40 — an AT cooling tower, 1391 nominal tons (6116 kW): rated to cool 4188 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 142.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4587–7646 kWEUOpen in the builder
Baltimore Aircoil PCC-0491-1220N020 evaporative condenser (3.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0491-1220N020 — a PCC evaporative condenser rejecting 2983 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 52.0 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2237–3728 kWEUOpen in the builder
EVAPCO ATWB 9-4K11 closed-circuit cooler (173 tons, 762 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-4K11 — an ATWB closed-circuit cooler, 173 nominal tons (762 kW): rated to cool 435 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 25.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection572–953 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-5D1ES-K2 closed-circuit cooler (172 tons, 758 kW) — modelled Example modelled from published data
BAC's PFI-0718N-5D1ES-K2 — a PFi closed-circuit cooler, 172 nominal tons (758 kW): rated to cool 519 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 33.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection568–947 kWEUOpen in the builder
EVAPCO AT 212-3O36 cooling tower (1443 tons, 6.3 MW) — modelled Example modelled from published data
EVAPCO's 212-3O36 — an AT cooling tower, 1443 nominal tons (6344 kW): rated to cool 4344 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 149.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4758–7930 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-10MN cooling tower (692 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-10MN — a Series 1500 cooling tower, 692 nominal tons (3041 kW): rated to cool 2082 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 73.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2281–3801 kWEUOpen in the builder
EVAPCO ATWB 9-4K14 closed-circuit cooler (224 tons, 986 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-4K14 — an ATWB closed-circuit cooler, 224 nominal tons (986 kW): rated to cool 563 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 31.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection740–1233 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-14R cooling tower (982 tons, 4.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-14R — a Series 3000 cooling tower, 982 nominal tons (4316 kW): rated to cool 2955 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 108.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3237–5395 kWEUOpen in the builder
EVAPCO AT 212-3O40 cooling tower (1510 tons, 6.6 MW) — modelled Example modelled from published data
EVAPCO's 212-3O40 — an AT cooling tower, 1510 nominal tons (6638 kW): rated to cool 4545 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 152.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4978–8297 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M431-N cooling tower (430 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-M431-N — a Series V cooling tower, 430 nominal tons (1888 kW): rated to cool 1293 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 48.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1416–2360 kWEUOpen in the builder
EVAPCO ATWB 9-4K18 closed-circuit cooler (350 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-4K18 — an ATWB closed-circuit cooler, 350 nominal tons (1540 kW): rated to cool 879 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 46.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1155–1925 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-1012N-5D closed-circuit cooler (145 tons, 635 kW) — modelled Example modelled from published data
BAC's VF1-1012N-5D — a Series V closed circuit closed-circuit cooler, 145 nominal tons (635 kW): rated to cool 435 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 39.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection476–794 kWEUOpen in the builder
EVAPCO AT 212-4F9 cooling tower (218 tons, 960 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-4F9 — an AT cooling tower, 218 nominal tons (960 kW): rated to cool 657 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 20.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection720–1199 kWEUOpen in the builder
Baltimore Aircoil VCA-331A evaporative condenser (1.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-331A — a VCA evaporative condenser rejecting 1426 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1070–1783 kWEUOpen in the builder
EVAPCO ATWB 9-4K21 closed-circuit cooler (401 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-4K21 — an ATWB closed-circuit cooler, 401 nominal tons (1761 kW): rated to cool 1005 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 51.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1321–2201 kWEUOpen in the builder
Baltimore Aircoil VRC-0464B-1018N-KA evaporative condenser (2.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0464B-1018N-KA — a Vertex VRC evaporative condenser rejecting 2813 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 42.5 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2110–3516 kWEUOpen in the builder
‹ Previous1…6667686970…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers