Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1657–1680 of 3346

EVAPCO AT 214-3I12 cooling tower (395 tons, 1.7 MW) — modelled

EVAPCO's 214-3I12 — a AT cooling tower, 395 nominal tons (1735 kW): rated to cool 1188 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1301–2169 kW · EU

EVAPCO AT 214-3I14 cooling tower (522 tons, 2.3 MW) — modelled

EVAPCO's 214-3I14 — a AT cooling tower, 522 nominal tons (2296 kW): rated to cool 1572 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1722–2870 kW · EU

EVAPCO AT 214-3I18 cooling tower (659 tons, 2.9 MW) — modelled

EVAPCO's 214-3I18 — a AT cooling tower, 659 nominal tons (2896 kW): rated to cool 1983 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2172–3620 kW · EU

EVAPCO AT 214-3I9 cooling tower (335 tons, 1.5 MW) — modelled

EVAPCO's 214-3I9 — a AT cooling tower, 335 nominal tons (1472 kW): rated to cool 1008 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1104–1840 kW · EU

EVAPCO AT 214-3J12 cooling tower (454 tons, 2.0 MW) — modelled

EVAPCO's 214-3J12 — a AT cooling tower, 454 nominal tons (1998 kW): rated to cool 1368 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1498–2497 kW · EU

EVAPCO AT 214-3J14 cooling tower (495 tons, 2.2 MW) — modelled

EVAPCO's 214-3J14 — a AT cooling tower, 495 nominal tons (2178 kW): rated to cool 1491 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 59.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1633–2722 kW · EU

EVAPCO AT 214-3J18 cooling tower (757 tons, 3.3 MW) — modelled

EVAPCO's 214-3J18 — a AT cooling tower, 757 nominal tons (3330 kW): rated to cool 2280 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 86.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2497–4162 kW · EU

EVAPCO AT 214-3J9 cooling tower (384 tons, 1.7 MW) — modelled

EVAPCO's 214-3J9 — a AT cooling tower, 384 nominal tons (1687 kW): rated to cool 1155 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1265–2109 kW · EU

EVAPCO AT 214-3K12 cooling tower (502 tons, 2.2 MW) — modelled

EVAPCO's 214-3K12 — a AT cooling tower, 502 nominal tons (2208 kW): rated to cool 1512 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1656–2760 kW · EU

EVAPCO AT 214-3K14 cooling tower (631 tons, 2.8 MW) — modelled

EVAPCO's 214-3K14 — a AT cooling tower, 631 nominal tons (2773 kW): rated to cool 1899 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2080–3467 kW · EU

EVAPCO AT 214-3K18 cooling tower (837 tons, 3.7 MW) — modelled

EVAPCO's 214-3K18 — a AT cooling tower, 837 nominal tons (3680 kW): rated to cool 2520 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 95.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2760–4600 kW · EU

EVAPCO AT 214-3K48 cooling tower (1378 tons, 6.1 MW) — modelled

EVAPCO's 214-3K48 — a AT cooling tower, 1378 nominal tons (6059 kW): rated to cool 4149 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 145.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 4545–7574 kW · EU

EVAPCO AT 214-3K9 cooling tower (425 tons, 1.9 MW) — modelled

EVAPCO's 214-3K9 — a AT cooling tower, 425 nominal tons (1866 kW): rated to cool 1278 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1400–2333 kW · EU

EVAPCO AT 214-3L12 cooling tower (543 tons, 2.4 MW) — modelled

EVAPCO's 214-3L12 — a AT cooling tower, 543 nominal tons (2388 kW): rated to cool 1635 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1791–2985 kW · EU

EVAPCO AT 214-3L14 cooling tower (532 tons, 2.3 MW) — modelled

EVAPCO's 214-3L14 — a AT cooling tower, 532 nominal tons (2340 kW): rated to cool 1602 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 69.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1755–2925 kW · EU

EVAPCO AT 214-3L48 cooling tower (1512 tons, 6.6 MW) — modelled

EVAPCO's 214-3L48 — a AT cooling tower, 1512 nominal tons (6647 kW): rated to cool 4551 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 156.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 4985–8308 kW · EU

EVAPCO AT 214-3M14 cooling tower (621 tons, 2.7 MW) — modelled

EVAPCO's 214-3M14 — a AT cooling tower, 621 nominal tons (2730 kW): rated to cool 1869 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 73.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2047–3412 kW · EU

EVAPCO AT 214-3M48 cooling tower (1584 tons, 7.0 MW) — modelled

EVAPCO's 214-3M48 — a AT cooling tower, 1584 nominal tons (6962 kW): rated to cool 4767 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 165.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 5222–8703 kW · EU

EVAPCO AT 214-3N48 cooling tower (1742 tons, 7.7 MW) — modelled

EVAPCO's 214-3N48 — a AT cooling tower, 1742 nominal tons (7659 kW): rated to cool 5244 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 181.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 5744–9573 kW · EU

EVAPCO AT 214-3O48 cooling tower (1857 tons, 8.2 MW) — modelled

EVAPCO's 214-3O48 — a AT cooling tower, 1857 nominal tons (8163 kW): rated to cool 5589 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 194.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 6122–10203 kW · EU

EVAPCO AT 214-3P48 cooling tower (1971 tons, 8.7 MW) — modelled

EVAPCO's 214-3P48 — a AT cooling tower, 1971 nominal tons (8666 kW): rated to cool 5934 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 206.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 6500–10833 kW · EU

EVAPCO AT 214-4G18 cooling tower (563 tons, 2.5 MW) — modelled

EVAPCO's 214-4G18 — a AT cooling tower, 563 nominal tons (2475 kW): rated to cool 1695 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1857–3094 kW · EU

EVAPCO AT 214-4G9 cooling tower (286 tons, 1.3 MW) — modelled

EVAPCO's 214-4G9 — a AT cooling tower, 286 nominal tons (1257 kW): rated to cool 861 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 943–1572 kW · EU

EVAPCO AT 214-4H12 cooling tower (392 tons, 1.7 MW) — modelled

EVAPCO's 214-4H12 — a AT cooling tower, 392 nominal tons (1722 kW): rated to cool 1179 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1291–2152 kW · EU
‹ Previous1…6869707172…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers