Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,681–1,704 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 212-4K40 cooling tower (1139 tons, 5.0 MW) — modelled Example modelled from published data
EVAPCO's 212-4K40 — an AT cooling tower, 1139 nominal tons (5008 kW): rated to cool 3429 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 112.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3756–6260 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-11KN-2 cooling tower (1164 tons, 5.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-11KN-2 — a Series 1500 cooling tower, 1164 nominal tons (5117 kW): rated to cool 3504 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 124.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3838–6397 kWEUOpen in the builder
EVAPCO ATWB 9-5J8 closed-circuit cooler (144 tons, 632 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-5J8 — an ATWB closed-circuit cooler, 144 nominal tons (632 kW): rated to cool 360 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 18.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection474–790 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-14S-2 cooling tower (2105 tons, 9.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-14S-2 — a Series 3000 cooling tower, 2105 nominal tons (9253 kW): rated to cool 6336 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 230.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6940–11567 kWEUOpen in the builder
EVAPCO AT 212-4L24 cooling tower (905 tons, 4.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-4L24 — an AT cooling tower, 905 nominal tons (3978 kW): rated to cool 2724 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 87.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2984–4973 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M514-O cooling tower (512 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-M514-O — a Series V cooling tower, 512 nominal tons (2252 kW): rated to cool 1542 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1689–2815 kWEUOpen in the builder
EVAPCO ATWB 9-5K11 closed-circuit cooler (193 tons, 849 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-5K11 — an ATWB closed-circuit cooler, 193 nominal tons (849 kW): rated to cool 485 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 25.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection637–1062 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-1012N-8D closed-circuit cooler (200 tons, 881 kW) — modelled Example modelled from published data
BAC's VF1-1012N-8D — a Series V closed circuit closed-circuit cooler, 200 nominal tons (881 kW): rated to cool 603 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 41.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection660–1101 kWEUOpen in the builder
EVAPCO AT 212-4L28 cooling tower (984 tons, 4.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-4L28 — an AT cooling tower, 984 nominal tons (4324 kW): rated to cool 2961 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 95.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3243–5406 kWEUOpen in the builder
Baltimore Aircoil VCA-356A evaporative condenser (1.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-356A — a VCA evaporative condenser rejecting 1534 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 31.9 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1150–1917 kWEUOpen in the builder
EVAPCO ATWB 9-5K14 closed-circuit cooler (244 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-5K14 — an ATWB closed-circuit cooler, 244 nominal tons (1071 kW): rated to cool 611 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 31.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection803–1338 kWEUOpen in the builder
Baltimore Aircoil VRC-0470B-1024N-JA evaporative condenser (2.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0470B-1024N-JA — a Vertex VRC evaporative condenser rejecting 2852 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 64.7 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2139–3565 kWEUOpen in the builder
EVAPCO AT 212-4L36 cooling tower (1209 tons, 5.3 MW) — modelled Example modelled from published data
EVAPCO's 212-4L36 — an AT cooling tower, 1209 nominal tons (5315 kW): rated to cool 3639 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 118.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3986–6643 kWEUOpen in the builder
Baltimore Aircoil CXVB-357-0818-22.5 evaporative condenser (2.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-357-0818-22.5 — a CXVB evaporative condenser rejecting 2163 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 46.4 m³/s of the maker's own printed air, with a 16.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1622–2704 kWEUOpen in the builder
EVAPCO ATWB 9-5K18 closed-circuit cooler (373 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-5K18 — an ATWB closed-circuit cooler, 373 nominal tons (1639 kW): rated to cool 935 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 45.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1229–2049 kWEUOpen in the builder
Baltimore Aircoil FXV-1212B-24D-O closed-circuit cooler (229 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212B-24D-O — an FXV closed-circuit cooler, 229 nominal tons (1008 kW): rated to cool 690 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 45.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection756–1260 kWEUOpen in the builder
EVAPCO AT 212-4L40 cooling tower (1231 tons, 5.4 MW) — modelled Example modelled from published data
EVAPCO's 212-4L40 — an AT cooling tower, 1231 nominal tons (5411 kW): rated to cool 3705 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 120.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4058–6764 kWEUOpen in the builder
Baltimore Aircoil PCC-0498-1224N020 evaporative condenser (3.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0498-1224N020 — a PCC evaporative condenser rejecting 3025 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 60.5 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2269–3781 kWEUOpen in the builder
EVAPCO ATWB 9-5K21 closed-circuit cooler (423 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-5K21 — an ATWB closed-circuit cooler, 423 nominal tons (1858 kW): rated to cool 1060 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 50.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1394–2323 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-6D1DS-J2 closed-circuit cooler (158 tons, 697 kW) — modelled Example modelled from published data
BAC's PFI-0718N-6D1DS-J2 — a PFi closed-circuit cooler, 158 nominal tons (697 kW): rated to cool 477 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 30.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection522–871 kWEUOpen in the builder
EVAPCO AT 212-4M24 cooling tower (960 tons, 4.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-4M24 — an AT cooling tower, 960 nominal tons (4219 kW): rated to cool 2889 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 92.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3164–5274 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-11LC cooling tower (623 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-11LC — a Series 1500 cooling tower, 623 nominal tons (2738 kW): rated to cool 1875 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 66.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2054–3423 kWEUOpen in the builder
EVAPCO ATWB 9-5L11 closed-circuit cooler (208 tons, 914 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-5L11 — an ATWB closed-circuit cooler, 208 nominal tons (914 kW): rated to cool 522 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 26.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection686–1143 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-14T cooling tower (1143 tons, 5.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-14T — a Series 3000 cooling tower, 1143 nominal tons (5025 kW): rated to cool 3441 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 125.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3769–6282 kWEUOpen in the builder
‹ Previous1…6970717273…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers