Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1681–1704 of 3346

EVAPCO AT 214-4H14 cooling tower (437 tons, 1.9 MW) — modelled

EVAPCO's 214-4H14 — a AT cooling tower, 437 nominal tons (1919 kW): rated to cool 1314 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1439–2399 kW · EU

EVAPCO AT 214-4H18 cooling tower (646 tons, 2.8 MW) — modelled

EVAPCO's 214-4H18 — a AT cooling tower, 646 nominal tons (2839 kW): rated to cool 1944 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2129–3549 kW · EU

EVAPCO AT 214-4H9 cooling tower (327 tons, 1.4 MW) — modelled

EVAPCO's 214-4H9 — a AT cooling tower, 327 nominal tons (1437 kW): rated to cool 984 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1078–1796 kW · EU

EVAPCO AT 214-4I12 cooling tower (429 tons, 1.9 MW) — modelled

EVAPCO's 214-4I12 — a AT cooling tower, 429 nominal tons (1884 kW): rated to cool 1290 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1413–2355 kW · EU

EVAPCO AT 214-4I14 cooling tower (387 tons, 1.7 MW) — modelled

EVAPCO's 214-4I14 — a AT cooling tower, 387 nominal tons (1700 kW): rated to cool 1164 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1275–2125 kW · EU

EVAPCO AT 214-4I18 cooling tower (705 tons, 3.1 MW) — modelled

EVAPCO's 214-4I18 — a AT cooling tower, 705 nominal tons (3098 kW): rated to cool 2121 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2323–3872 kW · EU

EVAPCO AT 214-4I9 cooling tower (357 tons, 1.6 MW) — modelled

EVAPCO's 214-4I9 — a AT cooling tower, 357 nominal tons (1569 kW): rated to cool 1074 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1176–1961 kW · EU

EVAPCO AT 214-4J12 cooling tower (484 tons, 2.1 MW) — modelled

EVAPCO's 214-4J12 — a AT cooling tower, 484 nominal tons (2129 kW): rated to cool 1458 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1597–2662 kW · EU

EVAPCO AT 214-4J14 cooling tower (547 tons, 2.4 MW) — modelled

EVAPCO's 214-4J14 — a AT cooling tower, 547 nominal tons (2405 kW): rated to cool 1647 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1804–3007 kW · EU

EVAPCO AT 214-4J18 cooling tower (796 tons, 3.5 MW) — modelled

EVAPCO's 214-4J18 — a AT cooling tower, 796 nominal tons (3501 kW): rated to cool 2397 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2626–4376 kW · EU

EVAPCO AT 214-4J9 cooling tower (403 tons, 1.8 MW) — modelled

EVAPCO's 214-4J9 — a AT cooling tower, 403 nominal tons (1770 kW): rated to cool 1212 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1328–2213 kW · EU

EVAPCO AT 214-4K12 cooling tower (528 tons, 2.3 MW) — modelled

EVAPCO's 214-4K12 — a AT cooling tower, 528 nominal tons (2322 kW): rated to cool 1590 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1742–2903 kW · EU

EVAPCO AT 214-4K14 cooling tower (430 tons, 1.9 MW) — modelled

EVAPCO's 214-4K14 — a AT cooling tower, 430 nominal tons (1888 kW): rated to cool 1293 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1416–2360 kW · EU

EVAPCO AT 214-4K18 cooling tower (868 tons, 3.8 MW) — modelled

EVAPCO's 214-4K18 — a AT cooling tower, 868 nominal tons (3816 kW): rated to cool 2613 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 93.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2862–4770 kW · EU

EVAPCO AT 214-4K48 cooling tower (1509 tons, 6.6 MW) — modelled

EVAPCO's 214-4K48 — a AT cooling tower, 1509 nominal tons (6633 kW): rated to cool 4542 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 143.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 4975–8292 kW · EU

EVAPCO AT 214-4K9 cooling tower (440 tons, 1.9 MW) — modelled

EVAPCO's 214-4K9 — a AT cooling tower, 440 nominal tons (1932 kW): rated to cool 1323 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1449–2415 kW · EU

EVAPCO AT 214-4L12 cooling tower (565 tons, 2.5 MW) — modelled

EVAPCO's 214-4L12 — a AT cooling tower, 565 nominal tons (2484 kW): rated to cool 1701 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1863–3105 kW · EU

EVAPCO AT 214-4L14 cooling tower (580 tons, 2.5 MW) — modelled

EVAPCO's 214-4L14 — a AT cooling tower, 580 nominal tons (2550 kW): rated to cool 1746 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1912–3187 kW · EU

EVAPCO AT 214-4L48 cooling tower (1632 tons, 7.2 MW) — modelled

EVAPCO's 214-4L48 — a AT cooling tower, 1632 nominal tons (7172 kW): rated to cool 4911 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 153.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 5379–8965 kW · EU

EVAPCO AT 214-4M14 cooling tower (656 tons, 2.9 MW) — modelled

EVAPCO's 214-4M14 — a AT cooling tower, 656 nominal tons (2883 kW): rated to cool 1974 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2162–3604 kW · EU

EVAPCO AT 214-4M48 cooling tower (1707 tons, 7.5 MW) — modelled

EVAPCO's 214-4M48 — a AT cooling tower, 1707 nominal tons (7505 kW): rated to cool 5139 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 162.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 5629–9382 kW · EU

EVAPCO AT 214-4N48 cooling tower (1854 tons, 8.1 MW) — modelled

EVAPCO's 214-4N48 — a AT cooling tower, 1854 nominal tons (8149 kW): rated to cool 5580 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 178.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 6112–10187 kW · EU

EVAPCO AT 214-4O48 cooling tower (1953 tons, 8.6 MW) — modelled

EVAPCO's 214-4O48 — a AT cooling tower, 1953 nominal tons (8588 kW): rated to cool 5880 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 191.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 6441–10734 kW · EU

EVAPCO AT 214-4P48 cooling tower (2068 tons, 9.1 MW) — modelled

EVAPCO's 214-4P48 — a AT cooling tower, 2068 nominal tons (9091 kW): rated to cool 6225 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 202.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 6819–11364 kW · EU
‹ Previous1…6970717273…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers