Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1633–1656 of 3346

EVAPCO AT 214-2H18 cooling tower (526 tons, 2.3 MW) — modelled

EVAPCO's 214-2H18 — a AT cooling tower, 526 nominal tons (2313 kW): rated to cool 1584 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 71.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1735–2892 kW · EU

EVAPCO AT 214-2H9 cooling tower (268 tons, 1.2 MW) — modelled

EVAPCO's 214-2H9 — a AT cooling tower, 268 nominal tons (1179 kW): rated to cool 807 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 884–1473 kW · EU

EVAPCO AT 214-2I12 cooling tower (349 tons, 1.5 MW) — modelled

EVAPCO's 214-2I12 — a AT cooling tower, 349 nominal tons (1533 kW): rated to cool 1050 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1150–1917 kW · EU

EVAPCO AT 214-2I14 cooling tower (483 tons, 2.1 MW) — modelled

EVAPCO's 214-2I14 — a AT cooling tower, 483 nominal tons (2125 kW): rated to cool 1455 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1594–2656 kW · EU

EVAPCO AT 214-2I18 cooling tower (583 tons, 2.6 MW) — modelled

EVAPCO's 214-2I18 — a AT cooling tower, 583 nominal tons (2563 kW): rated to cool 1755 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 77.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1922–3204 kW · EU

EVAPCO AT 214-2I9 cooling tower (297 tons, 1.3 MW) — modelled

EVAPCO's 214-2I9 — a AT cooling tower, 297 nominal tons (1306 kW): rated to cool 894 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 979–1632 kW · EU

EVAPCO AT 214-2J12 cooling tower (403 tons, 1.8 MW) — modelled

EVAPCO's 214-2J12 — a AT cooling tower, 403 nominal tons (1770 kW): rated to cool 1212 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1328–2213 kW · EU

EVAPCO AT 214-2J14 cooling tower (429 tons, 1.9 MW) — modelled

EVAPCO's 214-2J14 — a AT cooling tower, 429 nominal tons (1884 kW): rated to cool 1290 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1413–2355 kW · EU

EVAPCO AT 214-2J18 cooling tower (671 tons, 2.9 MW) — modelled

EVAPCO's 214-2J18 — a AT cooling tower, 671 nominal tons (2949 kW): rated to cool 2019 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 88.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2212–3686 kW · EU

EVAPCO AT 214-2J9 cooling tower (341 tons, 1.5 MW) — modelled

EVAPCO's 214-2J9 — a AT cooling tower, 341 nominal tons (1498 kW): rated to cool 1026 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1124–1873 kW · EU

EVAPCO AT 214-2K12 cooling tower (445 tons, 2.0 MW) — modelled

EVAPCO's 214-2K12 — a AT cooling tower, 445 nominal tons (1954 kW): rated to cool 1338 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1466–2443 kW · EU

EVAPCO AT 214-2K14 cooling tower (591 tons, 2.6 MW) — modelled

EVAPCO's 214-2K14 — a AT cooling tower, 591 nominal tons (2598 kW): rated to cool 1779 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1949–3248 kW · EU

EVAPCO AT 214-2K48 cooling tower (1201 tons, 5.3 MW) — modelled

EVAPCO's 214-2K48 — a AT cooling tower, 1201 nominal tons (5280 kW): rated to cool 3615 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 148.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 3960–6599 kW · EU

EVAPCO AT 214-2L14 cooling tower (469 tons, 2.1 MW) — modelled

EVAPCO's 214-2L14 — a AT cooling tower, 469 nominal tons (2064 kW): rated to cool 1413 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1548–2580 kW · EU

EVAPCO AT 214-2L48 cooling tower (1332 tons, 5.9 MW) — modelled

EVAPCO's 214-2L48 — a AT cooling tower, 1332 nominal tons (5854 kW): rated to cool 4008 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 158.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 4390–7317 kW · EU

EVAPCO AT 214-2M48 cooling tower (1405 tons, 6.2 MW) — modelled

EVAPCO's 214-2M48 — a AT cooling tower, 1405 nominal tons (6178 kW): rated to cool 4230 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 168.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 4633–7722 kW · EU

EVAPCO AT 214-2N48 cooling tower (1522 tons, 6.7 MW) — modelled

EVAPCO's 214-2N48 — a AT cooling tower, 1522 nominal tons (6690 kW): rated to cool 4581 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 184.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 5018–8363 kW · EU

EVAPCO AT 214-2O48 cooling tower (1636 tons, 7.2 MW) — modelled

EVAPCO's 214-2O48 — a AT cooling tower, 1636 nominal tons (7190 kW): rated to cool 4923 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 198.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 5392–8987 kW · EU

EVAPCO AT 214-3G18 cooling tower (506 tons, 2.2 MW) — modelled

EVAPCO's 214-3G18 — a AT cooling tower, 506 nominal tons (2226 kW): rated to cool 1524 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1669–2782 kW · EU

EVAPCO AT 214-3G9 cooling tower (258 tons, 1.1 MW) — modelled

EVAPCO's 214-3G9 — a AT cooling tower, 258 nominal tons (1135 kW): rated to cool 777 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 851–1418 kW · EU

EVAPCO AT 214-3H12 cooling tower (357 tons, 1.6 MW) — modelled

EVAPCO's 214-3H12 — a AT cooling tower, 357 nominal tons (1569 kW): rated to cool 1074 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1176–1961 kW · EU

EVAPCO AT 214-3H14 cooling tower (379 tons, 1.7 MW) — modelled

EVAPCO's 214-3H14 — a AT cooling tower, 379 nominal tons (1665 kW): rated to cool 1140 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1249–2081 kW · EU

EVAPCO AT 214-3H18 cooling tower (595 tons, 2.6 MW) — modelled

EVAPCO's 214-3H18 — a AT cooling tower, 595 nominal tons (2616 kW): rated to cool 1791 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 69.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1962–3270 kW · EU

EVAPCO AT 214-3H9 cooling tower (302 tons, 1.3 MW) — modelled

EVAPCO's 214-3H9 — a AT cooling tower, 302 nominal tons (1328 kW): rated to cool 909 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 996–1659 kW · EU
‹ Previous1…6768697071…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers