Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,633–1,656 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 212-4G9 cooling tower (261 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-4G9 — an AT cooling tower, 261 nominal tons (1148 kW): rated to cool 786 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 24.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection861–1435 kWEUOpen in the builder
Baltimore Aircoil CXVB-342-0818-15 evaporative condenser (2.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-342-0818-15 — a CXVB evaporative condenser rejecting 2072 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 40.2 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1554–2590 kWEUOpen in the builder
EVAPCO ATWB 9-4L14 closed-circuit cooler (241 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-4L14 — an ATWB closed-circuit cooler, 241 nominal tons (1061 kW): rated to cool 606 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 34.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection796–1327 kWEUOpen in the builder
Baltimore Aircoil FXV-1212B-20D-O closed-circuit cooler (199 tons, 876 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212B-20D-O — an FXV closed-circuit cooler, 199 nominal tons (876 kW): rated to cool 600 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 45.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection657–1095 kWEUOpen in the builder
EVAPCO AT 212-4H9 cooling tower (286 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-4H9 — an AT cooling tower, 286 nominal tons (1257 kW): rated to cool 861 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 27.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection943–1572 kWEUOpen in the builder
Baltimore Aircoil PCC-0492-1024N020 evaporative condenser (3.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0492-1024N020 — a PCC evaporative condenser rejecting 2988 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 45.7 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2241–3736 kWEUOpen in the builder
EVAPCO ATWB 9-4M14 closed-circuit cooler (256 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-4M14 — an ATWB closed-circuit cooler, 256 nominal tons (1127 kW): rated to cool 643 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 35.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection845–1408 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-5D1ES-L2 closed-circuit cooler (187 tons, 824 kW) — modelled Example modelled from published data
BAC's PFI-0718N-5D1ES-L2 — a PFi closed-circuit cooler, 187 nominal tons (824 kW): rated to cool 564 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection618–1030 kWEUOpen in the builder
EVAPCO AT 212-4I24 cooling tower (672 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-4I24 — an AT cooling tower, 672 nominal tons (2953 kW): rated to cool 2022 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2215–3691 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-10MN-2 cooling tower (1383 tons, 6.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-10MN-2 — a Series 1500 cooling tower, 1383 nominal tons (6081 kW): rated to cool 4164 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 147.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4561–7602 kWEUOpen in the builder
EVAPCO ATWB 9-5H18 closed-circuit cooler (273 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-5H18 — an ATWB closed-circuit cooler, 273 nominal tons (1199 kW): rated to cool 684 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 33.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection899–1498 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1222-14R-2 cooling tower (1963 tons, 8.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1222-14R-2 — a Series 3000 cooling tower, 1963 nominal tons (8631 kW): rated to cool 5910 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 216.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection6473–10789 kWEUOpen in the builder
EVAPCO AT 212-4I28 cooling tower (739 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-4I28 — an AT cooling tower, 739 nominal tons (3247 kW): rated to cool 2223 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 71.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2435–4058 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M455-O cooling tower (453 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-M455-O — a Series V cooling tower, 453 nominal tons (1994 kW): rated to cool 1365 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1495–2492 kWEUOpen in the builder
EVAPCO ATWB 9-5H8 closed-circuit cooler (113 tons, 497 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-5H8 — an ATWB closed-circuit cooler, 113 nominal tons (497 kW): rated to cool 284 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 14.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection373–621 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-1012N-6D closed-circuit cooler (176 tons, 776 kW) — modelled Example modelled from published data
BAC's VF1-1012N-6D — a Series V closed circuit closed-circuit cooler, 176 nominal tons (776 kW): rated to cool 531 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 41.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection582–969 kWEUOpen in the builder
EVAPCO AT 212-4I9 cooling tower (314 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-4I9 — an AT cooling tower, 314 nominal tons (1380 kW): rated to cool 945 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1035–1725 kWEUOpen in the builder
Baltimore Aircoil VCA-340A evaporative condenser (1.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-340A — a VCA evaporative condenser rejecting 1465 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 26.1 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1099–1831 kWEUOpen in the builder
EVAPCO ATWB 9-5I11 closed-circuit cooler (153 tons, 672 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-5I11 — an ATWB closed-circuit cooler, 153 nominal tons (672 kW): rated to cool 383 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 20.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection504–840 kWEUOpen in the builder
Baltimore Aircoil VRC-0467B-1218N-HB evaporative condenser (2.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0467B-1218N-HB — a Vertex VRC evaporative condenser rejecting 2829 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 56.6 m³/s of the maker's own printed air, with a 25.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2122–3536 kWEUOpen in the builder
EVAPCO AT 212-4J24 cooling tower (772 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 212-4J24 — an AT cooling tower, 772 nominal tons (3396 kW): rated to cool 2325 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 74.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2547–4244 kWEUOpen in the builder
Baltimore Aircoil CXVB-345-0818-30 evaporative condenser (2.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-345-0818-30 — a CXVB evaporative condenser rejecting 2090 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 51.7 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1568–2613 kWEUOpen in the builder
EVAPCO ATWB 9-5I18 closed-circuit cooler (299 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-5I18 — an ATWB closed-circuit cooler, 299 nominal tons (1315 kW): rated to cool 751 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 37.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection986–1644 kWEUOpen in the builder
Baltimore Aircoil FXV-1212B-23Q-O closed-circuit cooler (190 tons, 837 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212B-23Q-O — an FXV closed-circuit cooler, 190 nominal tons (837 kW): rated to cool 573 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 45.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection628–1046 kWEUOpen in the builder
‹ Previous1…6768697071…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers