Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1729–1752 of 3346

EVAPCO AT 217-2H14 cooling tower (434 tons, 1.9 MW) — modelled

EVAPCO's 217-2H14 — a AT cooling tower, 434 nominal tons (1906 kW): rated to cool 1305 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1429–2382 kW · EU

EVAPCO AT 217-2H9 cooling tower (323 tons, 1.4 MW) — modelled

EVAPCO's 217-2H9 — a AT cooling tower, 323 nominal tons (1420 kW): rated to cool 972 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 38.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1065–1774 kW · EU

EVAPCO AT 217-2I11 cooling tower (407 tons, 1.8 MW) — modelled

EVAPCO's 217-2I11 — a AT cooling tower, 407 nominal tons (1788 kW): rated to cool 1224 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1341–2235 kW · EU

EVAPCO AT 217-2I12 cooling tower (446 tons, 2.0 MW) — modelled

EVAPCO's 217-2I12 — a AT cooling tower, 446 nominal tons (1958 kW): rated to cool 1341 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1469–2448 kW · EU

EVAPCO AT 217-2I14 cooling tower (492 tons, 2.2 MW) — modelled

EVAPCO's 217-2I14 — a AT cooling tower, 492 nominal tons (2164 kW): rated to cool 1482 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1623–2706 kW · EU

EVAPCO AT 217-2I9 cooling tower (355 tons, 1.6 MW) — modelled

EVAPCO's 217-2I9 — a AT cooling tower, 355 nominal tons (1560 kW): rated to cool 1068 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1170–1950 kW · EU

EVAPCO AT 217-2J11 cooling tower (465 tons, 2.0 MW) — modelled

EVAPCO's 217-2J11 — a AT cooling tower, 465 nominal tons (2046 kW): rated to cool 1401 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 54.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1535–2558 kW · EU

EVAPCO AT 217-2J12 cooling tower (497 tons, 2.2 MW) — modelled

EVAPCO's 217-2J12 — a AT cooling tower, 497 nominal tons (2186 kW): rated to cool 1497 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1640–2733 kW · EU

EVAPCO AT 217-2J14 cooling tower (549 tons, 2.4 MW) — modelled

EVAPCO's 217-2J14 — a AT cooling tower, 549 nominal tons (2414 kW): rated to cool 1653 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 66.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1811–3018 kW · EU

EVAPCO AT 217-2J9 cooling tower (415 tons, 1.8 MW) — modelled

EVAPCO's 217-2J9 — a AT cooling tower, 415 nominal tons (1823 kW): rated to cool 1248 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1367–2278 kW · EU

EVAPCO AT 217-2K12 cooling tower (548 tons, 2.4 MW) — modelled

EVAPCO's 217-2K12 — a AT cooling tower, 548 nominal tons (2410 kW): rated to cool 1650 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1807–3012 kW · EU

EVAPCO AT 217-2K14 cooling tower (606 tons, 2.7 MW) — modelled

EVAPCO's 217-2K14 — a AT cooling tower, 606 nominal tons (2664 kW): rated to cool 1824 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1998–3330 kW · EU

EVAPCO AT 217-2L14 cooling tower (662 tons, 2.9 MW) — modelled

EVAPCO's 217-2L14 — a AT cooling tower, 662 nominal tons (2909 kW): rated to cool 1992 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 77.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2182–3637 kW · EU

EVAPCO AT 217-3G11 cooling tower (346 tons, 1.5 MW) — modelled

EVAPCO's 217-3G11 — a AT cooling tower, 346 nominal tons (1520 kW): rated to cool 1041 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1140–1900 kW · EU

EVAPCO AT 217-3G9 cooling tower (307 tons, 1.3 MW) — modelled

EVAPCO's 217-3G9 — a AT cooling tower, 307 nominal tons (1349 kW): rated to cool 924 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1012–1687 kW · EU

EVAPCO AT 217-3H11 cooling tower (408 tons, 1.8 MW) — modelled

EVAPCO's 217-3H11 — a AT cooling tower, 408 nominal tons (1792 kW): rated to cool 1227 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1344–2240 kW · EU

EVAPCO AT 217-3H12 cooling tower (445 tons, 2.0 MW) — modelled

EVAPCO's 217-3H12 — a AT cooling tower, 445 nominal tons (1954 kW): rated to cool 1338 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1466–2443 kW · EU

EVAPCO AT 217-3H14 cooling tower (488 tons, 2.1 MW) — modelled

EVAPCO's 217-3H14 — a AT cooling tower, 488 nominal tons (2147 kW): rated to cool 1470 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1610–2684 kW · EU

EVAPCO AT 217-3H9 cooling tower (361 tons, 1.6 MW) — modelled

EVAPCO's 217-3H9 — a AT cooling tower, 361 nominal tons (1586 kW): rated to cool 1086 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1190–1983 kW · EU

EVAPCO AT 217-3I11 cooling tower (446 tons, 2.0 MW) — modelled

EVAPCO's 217-3I11 — a AT cooling tower, 446 nominal tons (1958 kW): rated to cool 1341 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1469–2448 kW · EU

EVAPCO AT 217-3I12 cooling tower (497 tons, 2.2 MW) — modelled

EVAPCO's 217-3I12 — a AT cooling tower, 497 nominal tons (2186 kW): rated to cool 1497 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1640–2733 kW · EU

EVAPCO AT 217-3I14 cooling tower (549 tons, 2.4 MW) — modelled

EVAPCO's 217-3I14 — a AT cooling tower, 549 nominal tons (2414 kW): rated to cool 1653 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1811–3018 kW · EU

EVAPCO AT 217-3I9 cooling tower (398 tons, 1.7 MW) — modelled

EVAPCO's 217-3I9 — a AT cooling tower, 398 nominal tons (1748 kW): rated to cool 1197 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1311–2185 kW · EU

EVAPCO AT 217-3J11 cooling tower (514 tons, 2.3 MW) — modelled

EVAPCO's 217-3J11 — a AT cooling tower, 514 nominal tons (2261 kW): rated to cool 1548 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1696–2826 kW · EU
‹ Previous1…7172737475…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers