Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1,729–1,752 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 212-4N40 cooling tower (1452 tons, 6.4 MW) — modelled Example modelled from published data EVAPCO's 212-4N40 — an AT cooling tower, 1452 nominal tons (6384 kW): rated to cool 4371 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 139.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4788–7980 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-377A evaporative condenser (1.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-377A — a VCA evaporative condenser rejecting 1624 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1218–2030 kW | EU | Open in the builder |
| EVAPCO ATWB 9-6J11 closed-circuit cooler (198 tons, 870 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-6J11 — an ATWB closed-circuit cooler, 198 nominal tons (870 kW): rated to cool 497 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 22.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 653–1088 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0481B-1018N-JB evaporative condenser (2.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0481B-1018N-JB — a Vertex VRC evaporative condenser rejecting 2920 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 58.3 m³/s of the maker's own printed air, with a 40.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2190–3649 kW | EU | Open in the builder |
| EVAPCO AT 212-4O36 cooling tower (1508 tons, 6.6 MW) — modelled Example modelled from published data EVAPCO's 212-4O36 — an AT cooling tower, 1508 nominal tons (6629 kW): rated to cool 4539 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 146.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 4972–8286 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-370-1212-25 evaporative condenser (2.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-370-1212-25 — a CXVB evaporative condenser rejecting 2242 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 44.2 m³/s of the maker's own printed air, with a 18.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1681–2802 kW | EU | Open in the builder |
| EVAPCO ATWB 9-6J18 closed-circuit cooler (366 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-6J18 — an ATWB closed-circuit cooler, 366 nominal tons (1609 kW): rated to cool 918 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 40.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1207–2012 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-1212B-28D-O closed-circuit cooler (240 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-1212B-28D-O — an FXV closed-circuit cooler, 240 nominal tons (1056 kW): rated to cool 723 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 44.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 792–1320 kW | EU | Open in the builder |
| EVAPCO AT 212-4O40 cooling tower (1571 tons, 6.9 MW) — modelled Example modelled from published data EVAPCO's 212-4O40 — an AT cooling tower, 1571 nominal tons (6905 kW): rated to cool 4728 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 149.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5179–8631 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0517-1218N030 evaporative condenser (3.1 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0517-1218N030 — a PCC evaporative condenser rejecting 3141 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 51.9 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2355–3926 kW | EU | Open in the builder |
| EVAPCO ATWB 9-6J21 closed-circuit cooler (411 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-6J21 — an ATWB closed-circuit cooler, 411 nominal tons (1808 kW): rated to cool 1032 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 45.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1356–2261 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-0718N-6D1ES-L2 closed-circuit cooler (199 tons, 876 kW) — modelled Example modelled from published data BAC's PFI-0718N-6D1ES-L2 — a PFi closed-circuit cooler, 199 nominal tons (876 kW): rated to cool 600 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 36.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 657–1095 kW | EU | Open in the builder |
| EVAPCO AT 212-4P36 cooling tower (1565 tons, 6.9 MW) — modelled Example modelled from published data EVAPCO's 212-4P36 — an AT cooling tower, 1565 nominal tons (6879 kW): rated to cool 4710 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 155.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5159–8598 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1218-11LN cooling tower (653 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1218-11LN — a Series 1500 cooling tower, 653 nominal tons (2870 kW): rated to cool 1965 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2152–3587 kW | EU | Open in the builder |
| EVAPCO ATWB 9-6J8 closed-circuit cooler (166 tons, 729 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-6J8 — an ATWB closed-circuit cooler, 166 nominal tons (729 kW): rated to cool 416 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 17.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 546–911 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1424-07O cooling tower (619 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1424-07O — a Series 3000 cooling tower, 619 nominal tons (2721 kW): rated to cool 1863 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2041–3401 kW | EU | Open in the builder |
| EVAPCO AT 212-4P40 cooling tower (1630 tons, 7.2 MW) — modelled Example modelled from published data EVAPCO's 212-4P40 — an AT cooling tower, 1630 nominal tons (7164 kW): rated to cool 4905 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 158.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 5373–8954 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-M544-O cooling tower (542 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓ BAC's VT1-M544-O — a Series V cooling tower, 542 nominal tons (2383 kW): rated to cool 1632 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1788–2979 kW | EU | Open in the builder |
| EVAPCO ATWB 9-6K11 closed-circuit cooler (218 tons, 956 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-6K11 — an ATWB closed-circuit cooler, 218 nominal tons (956 kW): rated to cool 546 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 24.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 717–1195 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-1018N-6D closed-circuit cooler (272 tons, 1.2 MW) — modelled Example modelled from published data BAC's VF1-1018N-6D — a Series V closed circuit closed-circuit cooler, 272 nominal tons (1196 kW): rated to cool 819 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 61.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 897–1495 kW | EU | Open in the builder |
| EVAPCO AT 214-2G18 cooling tower (440 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-2G18 — an AT cooling tower, 440 nominal tons (1932 kW): rated to cool 1323 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 62.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1449–2415 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-381A evaporative condenser (1.6 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-381A — a VCA evaporative condenser rejecting 1641 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 28.2 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1231–2052 kW | EU | Open in the builder |
| EVAPCO ATWB 9-6K14 closed-circuit cooler (267 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓ EVAPCO's 9-6K14 — an ATWB closed-circuit cooler, 267 nominal tons (1174 kW): rated to cool 670 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 30.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 881–1468 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0484B-1024N-HA evaporative condenser (2.9 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0484B-1024N-HA — a Vertex VRC evaporative condenser rejecting 2930 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 52.3 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2197–3662 kW | EU | Open in the builder |
Publishing here
Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers