Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,753–1,776 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 214-2G9 cooling tower (224 tons, 986 kW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2G9 — an AT cooling tower, 224 nominal tons (986 kW): rated to cool 675 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 30.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection739–1232 kWEUOpen in the builder
Baltimore Aircoil CXVB-373-0818-30 evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-373-0818-30 — a CXVB evaporative condenser rejecting 2260 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 51.1 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1695–2825 kWEUOpen in the builder
EVAPCO ATWB 9-6K18 closed-circuit cooler (401 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-6K18 — an ATWB closed-circuit cooler, 401 nominal tons (1761 kW): rated to cool 1005 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 43.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1320–2201 kWEUOpen in the builder
Baltimore Aircoil FXV-1212C-12D-P closed-circuit cooler (183 tons, 806 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212C-12D-P — an FXV closed-circuit cooler, 183 nominal tons (806 kW): rated to cool 552 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 53.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection605–1008 kWEUOpen in the builder
EVAPCO AT 214-2H12 cooling tower (316 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2H12 — an AT cooling tower, 316 nominal tons (1389 kW): rated to cool 951 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1042–1736 kWEUOpen in the builder
Baltimore Aircoil PCC-0519-1220N020 evaporative condenser (3.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0519-1220N020 — a PCC evaporative condenser rejecting 3153 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 48.8 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2364–3941 kWEUOpen in the builder
EVAPCO ATWB 9-6K21 closed-circuit cooler (450 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-6K21 — an ATWB closed-circuit cooler, 450 nominal tons (1978 kW): rated to cool 1128 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 48.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1483–2472 kWEUOpen in the builder
Baltimore Aircoil PFI-0718N-6D2ES-M2 closed-circuit cooler (213 tons, 938 kW) — modelled Example modelled from published data
BAC's PFI-0718N-6D2ES-M2 — a PFi closed-circuit cooler, 213 nominal tons (938 kW): rated to cool 642 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 38.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection703–1172 kWEUOpen in the builder
EVAPCO AT 214-2H14 cooling tower (341 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2H14 — an AT cooling tower, 341 nominal tons (1498 kW): rated to cool 1026 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 48.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1124–1873 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-11LN-2 cooling tower (1306 tons, 5.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-11LN-2 — a Series 1500 cooling tower, 1306 nominal tons (5740 kW): rated to cool 3930 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 140.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4305–7175 kWEUOpen in the builder
EVAPCO ATWB 9-6L11 closed-circuit cooler (234 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-6L11 — an ATWB closed-circuit cooler, 234 nominal tons (1028 kW): rated to cool 587 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 25.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection771–1285 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-07O-2 cooling tower (1237 tons, 5.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-07O-2 — a Series 3000 cooling tower, 1237 nominal tons (5437 kW): rated to cool 3723 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 145.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4078–6797 kWEUOpen in the builder
EVAPCO AT 214-2H18 cooling tower (526 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2H18 — an AT cooling tower, 526 nominal tons (2313 kW): rated to cool 1584 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 71.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1735–2892 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M557-O cooling tower (555 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-M557-O — a Series V cooling tower, 555 nominal tons (2440 kW): rated to cool 1671 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 50.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1830–3051 kWEUOpen in the builder
EVAPCO ATWB 9-6L14 closed-circuit cooler (287 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-6L14 — an ATWB closed-circuit cooler, 287 nominal tons (1261 kW): rated to cool 720 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 31.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection946–1576 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-1018N-7D closed-circuit cooler (293 tons, 1.3 MW) — modelled Example modelled from published data
BAC's VF1-1018N-7D — a Series V closed circuit closed-circuit cooler, 293 nominal tons (1288 kW): rated to cool 882 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 60.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection966–1610 kWEUOpen in the builder
EVAPCO AT 214-2H9 cooling tower (268 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2H9 — an AT cooling tower, 268 nominal tons (1179 kW): rated to cool 807 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 34.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection884–1473 kWEUOpen in the builder
Baltimore Aircoil VCA-382A evaporative condenser (1.6 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-382A — a VCA evaporative condenser rejecting 1641 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 35.2 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1231–2052 kWEUOpen in the builder
EVAPCO ATWB 9-6L21 closed-circuit cooler (482 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-6L21 — an ATWB closed-circuit cooler, 482 nominal tons (2118 kW): rated to cool 1209 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 52.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1589–2648 kWEUOpen in the builder
Baltimore Aircoil VRC-0486B-1224N-HA evaporative condenser (2.9 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0486B-1224N-HA — a Vertex VRC evaporative condenser rejecting 2947 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 56.4 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2210–3683 kWEUOpen in the builder
EVAPCO AT 214-2I12 cooling tower (349 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2I12 — an AT cooling tower, 349 nominal tons (1533 kW): rated to cool 1050 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1150–1917 kWEUOpen in the builder
Baltimore Aircoil CXVB-381-1212-30 evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-381-1212-30 — a CXVB evaporative condenser rejecting 2308 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 46.5 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1731–2885 kWEUOpen in the builder
EVAPCO ATWB 9-6M14 closed-circuit cooler (304 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-6M14 — an ATWB closed-circuit cooler, 304 nominal tons (1336 kW): rated to cool 762 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 33.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1002–1670 kWEUOpen in the builder
Baltimore Aircoil FXV-1212C-16D-P closed-circuit cooler (207 tons, 911 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212C-16D-P — an FXV closed-circuit cooler, 207 nominal tons (911 kW): rated to cool 624 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 53.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection683–1139 kWEUOpen in the builder
‹ Previous1…7273747576…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers