Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1753–1776 of 3346

EVAPCO AT 217-3J12 cooling tower (562 tons, 2.5 MW) — modelled

EVAPCO's 217-3J12 — a AT cooling tower, 562 nominal tons (2471 kW): rated to cool 1692 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1853–3089 kW · EU

EVAPCO AT 217-3J14 cooling tower (619 tons, 2.7 MW) — modelled

EVAPCO's 217-3J14 — a AT cooling tower, 619 nominal tons (2721 kW): rated to cool 1863 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2041–3401 kW · EU

EVAPCO AT 217-3J9 cooling tower (462 tons, 2.0 MW) — modelled

EVAPCO's 217-3J9 — a AT cooling tower, 462 nominal tons (2033 kW): rated to cool 1392 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1525–2541 kW · EU

EVAPCO AT 217-3K11 cooling tower (574 tons, 2.5 MW) — modelled

EVAPCO's 217-3K11 — a AT cooling tower, 574 nominal tons (2524 kW): rated to cool 1728 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1893–3155 kW · EU

EVAPCO AT 217-3K12 cooling tower (620 tons, 2.7 MW) — modelled

EVAPCO's 217-3K12 — a AT cooling tower, 620 nominal tons (2725 kW): rated to cool 1866 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2044–3407 kW · EU

EVAPCO AT 217-3K14 cooling tower (683 tons, 3.0 MW) — modelled

EVAPCO's 217-3K14 — a AT cooling tower, 683 nominal tons (3001 kW): rated to cool 2055 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 71.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2251–3752 kW · EU

EVAPCO AT 217-3L12 cooling tower (663 tons, 2.9 MW) — modelled

EVAPCO's 217-3L12 — a AT cooling tower, 663 nominal tons (2914 kW): rated to cool 1995 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 67.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2185–3642 kW · EU

EVAPCO AT 217-3L14 cooling tower (742 tons, 3.3 MW) — modelled

EVAPCO's 217-3L14 — a AT cooling tower, 742 nominal tons (3260 kW): rated to cool 2232 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2445–4075 kW · EU

EVAPCO AT 217-3M14 cooling tower (784 tons, 3.4 MW) — modelled

EVAPCO's 217-3M14 — a AT cooling tower, 784 nominal tons (3448 kW): rated to cool 2361 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 80.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2586–4310 kW · EU

EVAPCO AT 217-4G11 cooling tower (384 tons, 1.7 MW) — modelled

EVAPCO's 217-4G11 — a AT cooling tower, 384 nominal tons (1687 kW): rated to cool 1155 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1265–2109 kW · EU

EVAPCO AT 217-4G9 cooling tower (329 tons, 1.4 MW) — modelled

EVAPCO's 217-4G9 — a AT cooling tower, 329 nominal tons (1446 kW): rated to cool 990 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1084–1807 kW · EU

EVAPCO AT 217-4H11 cooling tower (443 tons, 1.9 MW) — modelled

EVAPCO's 217-4H11 — a AT cooling tower, 443 nominal tons (1945 kW): rated to cool 1332 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1459–2432 kW · EU

EVAPCO AT 217-4H12 cooling tower (472 tons, 2.1 MW) — modelled

EVAPCO's 217-4H12 — a AT cooling tower, 472 nominal tons (2077 kW): rated to cool 1422 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1558–2596 kW · EU

EVAPCO AT 217-4H14 cooling tower (523 tons, 2.3 MW) — modelled

EVAPCO's 217-4H14 — a AT cooling tower, 523 nominal tons (2300 kW): rated to cool 1575 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1725–2875 kW · EU

EVAPCO AT 217-4H9 cooling tower (380 tons, 1.7 MW) — modelled

EVAPCO's 217-4H9 — a AT cooling tower, 380 nominal tons (1669 kW): rated to cool 1143 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1252–2087 kW · EU

EVAPCO AT 217-4I11 cooling tower (478 tons, 2.1 MW) — modelled

EVAPCO's 217-4I11 — a AT cooling tower, 478 nominal tons (2103 kW): rated to cool 1440 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1577–2629 kW · EU

EVAPCO AT 217-4I12 cooling tower (522 tons, 2.3 MW) — modelled

EVAPCO's 217-4I12 — a AT cooling tower, 522 nominal tons (2296 kW): rated to cool 1572 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 49.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1722–2870 kW · EU

EVAPCO AT 217-4I14 cooling tower (579 tons, 2.5 MW) — modelled

EVAPCO's 217-4I14 — a AT cooling tower, 579 nominal tons (2546 kW): rated to cool 1743 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1909–3182 kW · EU

EVAPCO AT 217-4I9 cooling tower (417 tons, 1.8 MW) — modelled

EVAPCO's 217-4I9 — a AT cooling tower, 417 nominal tons (1831 kW): rated to cool 1254 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 40.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1374–2289 kW · EU

EVAPCO AT 217-4J11 cooling tower (543 tons, 2.4 MW) — modelled

EVAPCO's 217-4J11 — a AT cooling tower, 543 nominal tons (2388 kW): rated to cool 1635 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1791–2985 kW · EU

EVAPCO AT 217-4J12 cooling tower (583 tons, 2.6 MW) — modelled

EVAPCO's 217-4J12 — a AT cooling tower, 583 nominal tons (2563 kW): rated to cool 1755 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1922–3204 kW · EU

EVAPCO AT 217-4J14 cooling tower (647 tons, 2.8 MW) — modelled

EVAPCO's 217-4J14 — a AT cooling tower, 647 nominal tons (2844 kW): rated to cool 1947 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2133–3554 kW · EU

EVAPCO AT 217-4J9 cooling tower (482 tons, 2.1 MW) — modelled

EVAPCO's 217-4J9 — a AT cooling tower, 482 nominal tons (2121 kW): rated to cool 1452 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1590–2651 kW · EU

EVAPCO AT 217-4K11 cooling tower (600 tons, 2.6 MW) — modelled

EVAPCO's 217-4K11 — a AT cooling tower, 600 nominal tons (2638 kW): rated to cool 1806 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1978–3297 kW · EU
‹ Previous1…7273747576…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers