Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,801–1,824 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 214-2J9 cooling tower (341 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2J9 — an AT cooling tower, 341 nominal tons (1498 kW): rated to cool 1026 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1124–1873 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-11MN-2 cooling tower (1439 tons, 6.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-11MN-2 — a Series 1500 cooling tower, 1439 nominal tons (6327 kW): rated to cool 4332 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 152.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4745–7908 kWEUOpen in the builder
EVAPCO ATWB 9-7J8 closed-circuit cooler (192 tons, 844 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7J8 — an ATWB closed-circuit cooler, 192 nominal tons (844 kW): rated to cool 482 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 17.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection633–1055 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-07P-2 cooling tower (1355 tons, 6.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-07P-2 — a Series 3000 cooling tower, 1355 nominal tons (5959 kW): rated to cool 4080 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 158.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4469–7448 kWEUOpen in the builder
EVAPCO AT 214-2K12 cooling tower (445 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2K12 — an AT cooling tower, 445 nominal tons (1954 kW): rated to cool 1338 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1466–2443 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M595-P cooling tower (593 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-M595-P — a Series V cooling tower, 593 nominal tons (2607 kW): rated to cool 1785 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1955–3259 kWEUOpen in the builder
EVAPCO ATWB 9-7K11 closed-circuit cooler (246 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7K11 — an ATWB closed-circuit cooler, 246 nominal tons (1084 kW): rated to cool 618 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 23.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection813–1354 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-1024N-4D closed-circuit cooler (254 tons, 1.1 MW) — modelled Example modelled from published data
BAC's VF1-1024N-4D — a Series V closed circuit closed-circuit cooler, 254 nominal tons (1117 kW): rated to cool 765 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 79.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection838–1397 kWEUOpen in the builder
EVAPCO AT 214-2K14 cooling tower (591 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2K14 — an AT cooling tower, 591 nominal tons (2598 kW): rated to cool 1779 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 65.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1949–3248 kWEUOpen in the builder
Baltimore Aircoil VCA-401A evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-401A — a VCA evaporative condenser rejecting 1728 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 25.7 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1296–2160 kWEUOpen in the builder
EVAPCO ATWB 9-7K14 closed-circuit cooler (295 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7K14 — an ATWB closed-circuit cooler, 295 nominal tons (1297 kW): rated to cool 740 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 29.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection973–1622 kWEUOpen in the builder
Baltimore Aircoil VRC-0502B-1018N-KA evaporative condenser (3.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0502B-1018N-KA — a Vertex VRC evaporative condenser rejecting 3046 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 44.5 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2284–3807 kWEUOpen in the builder
EVAPCO AT 214-2K48 cooling tower (1201 tons, 5.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2K48 — an AT cooling tower, 1201 nominal tons (5280 kW): rated to cool 3615 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 148.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3960–6599 kWEUOpen in the builder
Baltimore Aircoil CXVB-393-1212-30 evaporative condenser (2.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-393-1212-30 — a CXVB evaporative condenser rejecting 2381 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 46.5 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1786–2976 kWEUOpen in the builder
EVAPCO ATWB 9-7K21 closed-circuit cooler (482 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7K21 — an ATWB closed-circuit cooler, 482 nominal tons (2119 kW): rated to cool 1209 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 47.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1589–2649 kWEUOpen in the builder
Baltimore Aircoil FXV-1212C-20D-P closed-circuit cooler (225 tons, 990 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212C-20D-P — an FXV closed-circuit cooler, 225 nominal tons (990 kW): rated to cool 678 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 52.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection743–1238 kWEUOpen in the builder
EVAPCO AT 214-2L14 cooling tower (469 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2L14 — an AT cooling tower, 469 nominal tons (2064 kW): rated to cool 1413 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 70.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1548–2580 kWEUOpen in the builder
Baltimore Aircoil PCC-0531-1218N040 evaporative condenser (3.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0531-1218N040 — a PCC evaporative condenser rejecting 3226 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 60.4 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2419–4032 kWEUOpen in the builder
EVAPCO ATWB 9-7L11 closed-circuit cooler (265 tons, 1.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7L11 — an ATWB closed-circuit cooler, 265 nominal tons (1163 kW): rated to cool 664 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 25.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection872–1454 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-2D4ES-K1 closed-circuit cooler (88 tons, 386 kW) — modelled Example modelled from published data
BAC's PFI-1012N-2D4ES-K1 — a PFi closed-circuit cooler, 88 nominal tons (386 kW): rated to cool 264 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 27.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection289–482 kWEUOpen in the builder
EVAPCO AT 214-2L48 cooling tower (1332 tons, 5.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2L48 — an AT cooling tower, 1332 nominal tons (5854 kW): rated to cool 4008 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 158.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4390–7317 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-12KN cooling tower (603 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-12KN — a Series 1500 cooling tower, 603 nominal tons (2651 kW): rated to cool 1815 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1988–3313 kWEUOpen in the builder
EVAPCO ATWB 9-7L14 closed-circuit cooler (317 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7L14 — an ATWB closed-circuit cooler, 317 nominal tons (1392 kW): rated to cool 794 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 30.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1044–1740 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-07Q cooling tower (727 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-07Q — a Series 3000 cooling tower, 727 nominal tons (3194 kW): rated to cool 2187 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 84.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2396–3993 kWEUOpen in the builder
‹ Previous1…7475767778…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers