Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,825–1,848 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 214-2M48 cooling tower (1405 tons, 6.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2M48 — an AT cooling tower, 1405 nominal tons (6178 kW): rated to cool 4230 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 168.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4633–7722 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M610-P cooling tower (608 tons, 2.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-M610-P — a Series V cooling tower, 608 nominal tons (2673 kW): rated to cool 1830 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 55.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2004–3341 kWEUOpen in the builder
EVAPCO ATWB 9-7L21 closed-circuit cooler (516 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7L21 — an ATWB closed-circuit cooler, 516 nominal tons (2269 kW): rated to cool 1295 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 50.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1702–2836 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-1024N-5D closed-circuit cooler (289 tons, 1.3 MW) — modelled Example modelled from published data
BAC's VF1-1024N-5D — a Series V closed circuit closed-circuit cooler, 289 nominal tons (1271 kW): rated to cool 870 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 78.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection953–1588 kWEUOpen in the builder
EVAPCO AT 214-2N48 cooling tower (1522 tons, 6.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2N48 — an AT cooling tower, 1522 nominal tons (6690 kW): rated to cool 4581 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 184.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5018–8363 kWEUOpen in the builder
Baltimore Aircoil VCA-402A evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-402A — a VCA evaporative condenser rejecting 1732 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.9 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1299–2165 kWEUOpen in the builder
EVAPCO ATWB 9-7M14 closed-circuit cooler (335 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7M14 — an ATWB closed-circuit cooler, 335 nominal tons (1473 kW): rated to cool 841 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 32.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1105–1842 kWEUOpen in the builder
Baltimore Aircoil VRC-0510B-1218N-HB evaporative condenser (3.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0510B-1218N-HB — a Vertex VRC evaporative condenser rejecting 3093 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 54.3 m³/s of the maker's own printed air, with a 25.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2320–3866 kWEUOpen in the builder
EVAPCO AT 214-2O48 cooling tower (1636 tons, 7.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2O48 — an AT cooling tower, 1636 nominal tons (7190 kW): rated to cool 4923 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 198.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection5392–8987 kWEUOpen in the builder
Baltimore Aircoil CXVB-403-1218-15 evaporative condenser (2.4 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-403-1218-15 — a CXVB evaporative condenser rejecting 2442 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 51.0 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1831–3052 kWEUOpen in the builder
EVAPCO AT 214-3G18 cooling tower (506 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3G18 — an AT cooling tower, 506 nominal tons (2226 kW): rated to cool 1524 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1669–2782 kWEUOpen in the builder
Baltimore Aircoil FXV-1212C-23Q-P closed-circuit cooler (216 tons, 951 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212C-23Q-P — an FXV closed-circuit cooler, 216 nominal tons (951 kW): rated to cool 651 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 52.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection713–1188 kWEUOpen in the builder
EVAPCO AT 214-3G9 cooling tower (258 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3G9 — an AT cooling tower, 258 nominal tons (1135 kW): rated to cool 777 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection851–1418 kWEUOpen in the builder
Baltimore Aircoil PCC-0538-1024N060 evaporative condenser (3.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0538-1024N060 — a PCC evaporative condenser rejecting 3268 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 80.0 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2451–4085 kWEUOpen in the builder
EVAPCO AT 214-3H12 cooling tower (357 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3H12 — an AT cooling tower, 357 nominal tons (1569 kW): rated to cool 1074 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 42.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1176–1961 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-2D4ES-N1 closed-circuit cooler (106 tons, 464 kW) — modelled Example modelled from published data
BAC's PFI-1012N-2D4ES-N1 — a PFi closed-circuit cooler, 106 nominal tons (464 kW): rated to cool 318 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 36.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection348–581 kWEUOpen in the builder
EVAPCO AT 214-3H14 cooling tower (379 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3H14 — an AT cooling tower, 379 nominal tons (1665 kW): rated to cool 1140 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 47.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1249–2081 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-12KN-2 cooling tower (1206 tons, 5.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-12KN-2 — a Series 1500 cooling tower, 1206 nominal tons (5301 kW): rated to cool 3630 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 128.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection3976–6627 kWEUOpen in the builder
EVAPCO AT 214-3H18 cooling tower (595 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3H18 — an AT cooling tower, 595 nominal tons (2616 kW): rated to cool 1791 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 69.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1962–3270 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-07Q-2 cooling tower (1454 tons, 6.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-07Q-2 — a Series 3000 cooling tower, 1454 nominal tons (6392 kW): rated to cool 4377 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 169.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4794–7991 kWEUOpen in the builder
EVAPCO AT 214-3H9 cooling tower (302 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3H9 — an AT cooling tower, 302 nominal tons (1328 kW): rated to cool 909 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection996–1659 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M632-O cooling tower (630 tons, 2.8 MW) — modelled Example modelled from published data
BAC's VT1-M632-O — a Series V cooling tower, 630 nominal tons (2769 kW): rated to cool 1896 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 62.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2077–3461 kWEUOpen in the builder
EVAPCO AT 214-3I12 cooling tower (395 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3I12 — an AT cooling tower, 395 nominal tons (1735 kW): rated to cool 1188 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 46.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1301–2169 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-1024N-6D closed-circuit cooler (354 tons, 1.6 MW) — modelled Example modelled from published data
BAC's VF1-1024N-6D — a Series V closed circuit closed-circuit cooler, 354 nominal tons (1555 kW): rated to cool 1065 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 83.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1167–1944 kWEUOpen in the builder
‹ Previous1…7576777879…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers