Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,777–1,800 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 214-2I14 cooling tower (483 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2I14 — an AT cooling tower, 483 nominal tons (2125 kW): rated to cool 1455 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1594–2656 kWEUOpen in the builder
Baltimore Aircoil PCC-0530-1224N030 evaporative condenser (3.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0530-1224N030 — a PCC evaporative condenser rejecting 3219 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 70.6 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2415–4024 kWEUOpen in the builder
EVAPCO ATWB 9-7H8 closed-circuit cooler (153 tons, 673 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7H8 — an ATWB closed-circuit cooler, 153 nominal tons (673 kW): rated to cool 384 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 13.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection505–842 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-2D2DS-J1 closed-circuit cooler (75 tons, 329 kW) — modelled Example modelled from published data
BAC's PFI-1012N-2D2DS-J1 — a PFi closed-circuit cooler, 75 nominal tons (329 kW): rated to cool 225 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 27.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection246–411 kWEUOpen in the builder
EVAPCO AT 214-2I18 cooling tower (583 tons, 2.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2I18 — an AT cooling tower, 583 nominal tons (2563 kW): rated to cool 1755 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 77.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1922–3204 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-11MN cooling tower (720 tons, 3.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-11MN — a Series 1500 cooling tower, 720 nominal tons (3163 kW): rated to cool 2166 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2373–3954 kWEUOpen in the builder
EVAPCO ATWB 9-7I18 closed-circuit cooler (349 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7I18 — an ATWB closed-circuit cooler, 349 nominal tons (1536 kW): rated to cool 877 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 34.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1152–1920 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-07P cooling tower (678 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-07P — a Series 3000 cooling tower, 678 nominal tons (2979 kW): rated to cool 2040 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 79.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2235–3724 kWEUOpen in the builder
EVAPCO AT 214-2I9 cooling tower (297 tons, 1.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2I9 — an AT cooling tower, 297 nominal tons (1306 kW): rated to cool 894 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection979–1632 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M560-P cooling tower (558 tons, 2.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C11B-92R07) ✓
BAC's VT1-M560-P — a Series V cooling tower, 558 nominal tons (2454 kW): rated to cool 1680 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1840–3067 kWEUOpen in the builder
EVAPCO ATWB 9-7I8 closed-circuit cooler (168 tons, 740 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7I8 — an ATWB closed-circuit cooler, 168 nominal tons (740 kW): rated to cool 422 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 15.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection555–925 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-1018N-8D closed-circuit cooler (306 tons, 1.3 MW) — modelled Example modelled from published data
BAC's VF1-1018N-8D — a Series V closed circuit closed-circuit cooler, 306 nominal tons (1345 kW): rated to cool 921 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 60.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1009–1681 kWEUOpen in the builder
EVAPCO AT 214-2J12 cooling tower (403 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2J12 — an AT cooling tower, 403 nominal tons (1770 kW): rated to cool 1212 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 53.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1328–2213 kWEUOpen in the builder
Baltimore Aircoil VCA-393A evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-393A — a VCA evaporative condenser rejecting 1693 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 23.6 m³/s of the maker's own printed air, with a 7.5 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1270–2116 kWEUOpen in the builder
EVAPCO ATWB 9-7J11 closed-circuit cooler (225 tons, 988 kW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7J11 — an ATWB closed-circuit cooler, 225 nominal tons (988 kW): rated to cool 564 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 21.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection741–1235 kWEUOpen in the builder
Baltimore Aircoil VRC-0489B-1218N-KA evaporative condenser (3.0 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0489B-1218N-KA — a Vertex VRC evaporative condenser rejecting 2964 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 51.8 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2223–3705 kWEUOpen in the builder
EVAPCO AT 214-2J14 cooling tower (429 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2J14 — an AT cooling tower, 429 nominal tons (1884 kW): rated to cool 1290 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 60.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1413–2355 kWEUOpen in the builder
Baltimore Aircoil CXVB-387-0818-30 evaporative condenser (2.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-387-0818-30 — a CXVB evaporative condenser rejecting 2345 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 50.6 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1758–2931 kWEUOpen in the builder
EVAPCO ATWB 9-7J18 closed-circuit cooler (396 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7J18 — an ATWB closed-circuit cooler, 396 nominal tons (1743 kW): rated to cool 995 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 39.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1307–2179 kWEUOpen in the builder
Baltimore Aircoil FXV-1212C-16Q-P closed-circuit cooler (175 tons, 771 kW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212C-16Q-P — an FXV closed-circuit cooler, 175 nominal tons (771 kW): rated to cool 528 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 53.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection578–964 kWEUOpen in the builder
EVAPCO AT 214-2J18 cooling tower (671 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-2J18 — an AT cooling tower, 671 nominal tons (2949 kW): rated to cool 2019 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 88.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2212–3686 kWEUOpen in the builder
Baltimore Aircoil PCC-0530-2412N030 evaporative condenser (3.2 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0530-2412N030 — a PCC evaporative condenser rejecting 3219 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 70.6 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2415–4024 kWEUOpen in the builder
EVAPCO ATWB 9-7J21 closed-circuit cooler (441 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13F-09R12) ✓
EVAPCO's 9-7J21 — an ATWB closed-circuit cooler, 441 nominal tons (1940 kW): rated to cool 1107 USGPM of process fluid from 102 to 90 °F at a 75 °F entering wet bulb on 43.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1455–2425 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-2D2ES-L1 closed-circuit cooler (90 tons, 394 kW) — modelled Example modelled from published data
BAC's PFI-1012N-2D2ES-L1 — a PFi closed-circuit cooler, 90 nominal tons (394 kW): rated to cool 270 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 32.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection296–493 kWEUOpen in the builder
‹ Previous1…7374757677…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers