Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 1,849–1,872 of 3,474

NameCompanyCategoryCapacityMarketsOpen in the builder
EVAPCO AT 214-3I14 cooling tower (522 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3I14 — an AT cooling tower, 522 nominal tons (2296 kW): rated to cool 1572 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1722–2870 kWEUOpen in the builder
Baltimore Aircoil VCA-404A evaporative condenser (1.7 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-404A — a VCA evaporative condenser rejecting 1741 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 35.5 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1305–2176 kWEUOpen in the builder
EVAPCO AT 214-3I18 cooling tower (659 tons, 2.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3I18 — an AT cooling tower, 659 nominal tons (2896 kW): rated to cool 1983 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 76.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2172–3620 kWEUOpen in the builder
Baltimore Aircoil VRC-0511B-1018N-HB evaporative condenser (3.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0511B-1018N-HB — a Vertex VRC evaporative condenser rejecting 3102 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 42.3 m³/s of the maker's own printed air, with a 25.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2327–3878 kWEUOpen in the builder
EVAPCO AT 214-3I9 cooling tower (335 tons, 1.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3I9 — an AT cooling tower, 335 nominal tons (1472 kW): rated to cool 1008 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1104–1840 kWEUOpen in the builder
Baltimore Aircoil CXVB-409-0818-45 evaporative condenser (2.5 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's CXVB-409-0818-45 — a CXVB evaporative condenser rejecting 2478 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 58.0 m³/s of the maker's own printed air, with a 33.6 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1858–3097 kWEUOpen in the builder
EVAPCO AT 214-3J12 cooling tower (454 tons, 2.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3J12 — an AT cooling tower, 454 nominal tons (1998 kW): rated to cool 1368 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1498–2497 kWEUOpen in the builder
Baltimore Aircoil FXV-1212C-23T-P closed-circuit cooler (228 tons, 1.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓
BAC's FXV-1212C-23T-P — an FXV closed-circuit cooler, 228 nominal tons (1003 kW): rated to cool 687 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 52.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection753–1254 kWEUOpen in the builder
EVAPCO AT 214-3J14 cooling tower (495 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3J14 — an AT cooling tower, 495 nominal tons (2178 kW): rated to cool 1491 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 59.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1633–2722 kWEUOpen in the builder
Baltimore Aircoil PCC-0538-2012N060 evaporative condenser (3.3 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's PCC-0538-2012N060 — a PCC evaporative condenser rejecting 3268 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 80.0 m³/s of the maker's own printed air, with a 44.7 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2451–4085 kWEUOpen in the builder
EVAPCO AT 214-3J18 cooling tower (757 tons, 3.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3J18 — an AT cooling tower, 757 nominal tons (3330 kW): rated to cool 2280 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 86.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2497–4162 kWEUOpen in the builder
Baltimore Aircoil PFI-1012N-3D1DS-L1 closed-circuit cooler (109 tons, 478 kW) — modelled Example modelled from published data
BAC's PFI-1012N-3D1DS-L1 — a PFi closed-circuit cooler, 109 nominal tons (478 kW): rated to cool 327 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 33.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection358–597 kWEUOpen in the builder
EVAPCO AT 214-3J9 cooling tower (384 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3J9 — an AT cooling tower, 384 nominal tons (1687 kW): rated to cool 1155 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1265–2109 kWEUOpen in the builder
Baltimore Aircoil Series 1500 S15E-1218-12LC cooling tower (645 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S15E-1218-12LC — a Series 1500 cooling tower, 645 nominal tons (2835 kW): rated to cool 1941 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2126–3543 kWEUOpen in the builder
EVAPCO AT 214-3K12 cooling tower (502 tons, 2.2 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3K12 — an AT cooling tower, 502 nominal tons (2208 kW): rated to cool 1512 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1656–2760 kWEUOpen in the builder
Baltimore Aircoil Series 3000 S3E-1424-07R cooling tower (769 tons, 3.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓
BAC's S3E-1424-07R — a Series 3000 cooling tower, 769 nominal tons (3382 kW): rated to cool 2316 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 89.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2537–4228 kWEUOpen in the builder
EVAPCO AT 214-3K14 cooling tower (631 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3K14 — an AT cooling tower, 631 nominal tons (2773 kW): rated to cool 1899 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 64.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2080–3467 kWEUOpen in the builder
Baltimore Aircoil Series V VT1-M656-O cooling tower (654 tons, 2.9 MW) — modelled Example modelled from published data
BAC's VT1-M656-O — a Series V cooling tower, 654 nominal tons (2874 kW): rated to cool 1968 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2156–3593 kWEUOpen in the builder
EVAPCO AT 214-3K18 cooling tower (837 tons, 3.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3K18 — an AT cooling tower, 837 nominal tons (3680 kW): rated to cool 2520 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 95.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection2760–4600 kWEUOpen in the builder
Baltimore Aircoil Series V closed circuit VF1-1024N-7D closed-circuit cooler (384 tons, 1.7 MW) — modelled Example modelled from published data
BAC's VF1-1024N-7D — a Series V closed circuit closed-circuit cooler, 384 nominal tons (1687 kW): rated to cool 1155 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 83.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1265–2109 kWEUOpen in the builder
EVAPCO AT 214-3K48 cooling tower (1378 tons, 6.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3K48 — an AT cooling tower, 1378 nominal tons (6059 kW): rated to cool 4149 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 145.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection4545–7574 kWEUOpen in the builder
Baltimore Aircoil VCA-407A evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VCA-407A — a VCA evaporative condenser rejecting 1753 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 30.9 m³/s of the maker's own printed air, with a 14.9 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection1315–2192 kWEUOpen in the builder
EVAPCO AT 214-3K9 cooling tower (425 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓
EVAPCO's 214-3K9 — an AT cooling tower, 425 nominal tons (1866 kW): rated to cool 1278 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.
HVAC BuilderCooling tower / heat rejection1400–2333 kWEUOpen in the builder
Baltimore Aircoil VRC-0516B-1218N-JB evaporative condenser (3.1 MW rejection) — modelled Example modelled from published data
Baltimore Aircoil's VRC-0516B-1218N-JB — a Vertex VRC evaporative condenser rejecting 3126 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 65.7 m³/s of the maker's own printed air, with a 40.0 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection.
HVAC BuilderCooling tower / heat rejection2345–3908 kWEUOpen in the builder
‹ Previous1…7677787980…145Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers