Published systems
Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.
Showing 1,897–1,920 of 3,474
| Name | Company | Category | Capacity | Markets | Open in the builder |
|---|---|---|---|---|---|
| EVAPCO AT 214-4H18 cooling tower (646 tons, 2.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4H18 — an AT cooling tower, 646 nominal tons (2839 kW): rated to cool 1944 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2129–3549 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0541-1218N040 evaporative condenser (3.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0541-1218N040 — a PCC evaporative condenser rejecting 3286 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 60.1 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2465–4108 kW | EU | Open in the builder |
| EVAPCO AT 214-4H9 cooling tower (327 tons, 1.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4H9 — an AT cooling tower, 327 nominal tons (1437 kW): rated to cool 984 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1078–1796 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1012N-3D2DS-M1 closed-circuit cooler (119 tons, 521 kW) — modelled Example modelled from published data BAC's PFI-1012N-3D2DS-M1 — a PFi closed-circuit cooler, 119 nominal tons (521 kW): rated to cool 357 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 35.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 391–652 kW | EU | Open in the builder |
| EVAPCO AT 214-4I12 cooling tower (429 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4I12 — an AT cooling tower, 429 nominal tons (1884 kW): rated to cool 1290 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 45.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1413–2355 kW | EU | Open in the builder |
| Baltimore Aircoil Series 1500 S15E-1218-12LN cooling tower (676 tons, 3.0 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S15E-1218-12LN — a Series 1500 cooling tower, 676 nominal tons (2971 kW): rated to cool 2034 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2228–3713 kW | EU | Open in the builder |
| EVAPCO AT 214-4I14 cooling tower (387 tons, 1.7 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4I14 — an AT cooling tower, 387 nominal tons (1700 kW): rated to cool 1164 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1275–2125 kW | EU | Open in the builder |
| Baltimore Aircoil Series 3000 S3E-1424-12Q cooling tower (992 tons, 4.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C11F-92R20) ✓ BAC's S3E-1424-12Q — a Series 3000 cooling tower, 992 nominal tons (4359 kW): rated to cool 2985 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 110.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 3270–5449 kW | EU | Open in the builder |
| EVAPCO AT 214-4I18 cooling tower (705 tons, 3.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4I18 — an AT cooling tower, 705 nominal tons (3098 kW): rated to cool 2121 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2323–3872 kW | EU | Open in the builder |
| Baltimore Aircoil Series V VT1-M700-O cooling tower (698 tons, 3.1 MW) — modelled Example modelled from published data BAC's VT1-M700-O — a Series V cooling tower, 698 nominal tons (3067 kW): rated to cool 2100 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 59.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2300–3834 kW | EU | Open in the builder |
| EVAPCO AT 214-4I9 cooling tower (357 tons, 1.6 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4I9 — an AT cooling tower, 357 nominal tons (1569 kW): rated to cool 1074 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1176–1961 kW | EU | Open in the builder |
| Baltimore Aircoil Series V closed circuit VF1-1036N-4D closed-circuit cooler (440 tons, 1.9 MW) — modelled Example modelled from published data BAC's VF1-1036N-4D — a Series V closed circuit closed-circuit cooler, 440 nominal tons (1932 kW): rated to cool 1323 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 125.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with a forced-draft fan on the leaving air, where its nameplate cannot be counted twice against a certified point. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1449–2415 kW | EU | Open in the builder |
| EVAPCO AT 214-4J12 cooling tower (484 tons, 2.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4J12 — an AT cooling tower, 484 nominal tons (2129 kW): rated to cool 1458 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1597–2662 kW | EU | Open in the builder |
| Baltimore Aircoil VCA-420A evaporative condenser (1.8 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VCA-420A — a VCA evaporative condenser rejecting 1809 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 32.3 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 1357–2262 kW | EU | Open in the builder |
| EVAPCO AT 214-4J14 cooling tower (547 tons, 2.4 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4J14 — an AT cooling tower, 547 nominal tons (2405 kW): rated to cool 1647 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1804–3007 kW | EU | Open in the builder |
| Baltimore Aircoil VRC-0533B-1024N-JA evaporative condenser (3.2 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's VRC-0533B-1024N-JA — a Vertex VRC evaporative condenser rejecting 3231 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 59.8 m³/s of the maker's own printed air, with a 22.4 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2424–4039 kW | EU | Open in the builder |
| EVAPCO AT 214-4J18 cooling tower (796 tons, 3.5 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4J18 — an AT cooling tower, 796 nominal tons (3501 kW): rated to cool 2397 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 2626–4376 kW | EU | Open in the builder |
| Baltimore Aircoil CXVB-444-1218-15 evaporative condenser (2.7 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's CXVB-444-1218-15 — a CXVB evaporative condenser rejecting 2690 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 49.6 m³/s of the maker's own printed air, with a 11.2 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2017–3362 kW | EU | Open in the builder |
| EVAPCO AT 214-4J9 cooling tower (403 tons, 1.8 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4J9 — an AT cooling tower, 403 nominal tons (1770 kW): rated to cool 1212 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1328–2213 kW | EU | Open in the builder |
| Baltimore Aircoil FXV-1212C-24T-P closed-circuit cooler (251 tons, 1.1 MW) — modelled Example modelled from published data CTI STD-201 (validation C11J-98R12) ✓ BAC's FXV-1212C-24T-P — an FXV closed-circuit cooler, 251 nominal tons (1104 kW): rated to cool 756 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 52.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 828–1380 kW | EU | Open in the builder |
| EVAPCO AT 214-4K12 cooling tower (528 tons, 2.3 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4K12 — an AT cooling tower, 528 nominal tons (2322 kW): rated to cool 1590 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 56.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1742–2903 kW | EU | Open in the builder |
| Baltimore Aircoil PCC-0544-1024N040 evaporative condenser (3.3 MW rejection) — modelled Example modelled from published data Baltimore Aircoil's PCC-0544-1024N040 — a PCC evaporative condenser rejecting 3304 kW at a 40.6 °C condensing temperature and a 25.6 °C entering wet bulb, on 66.0 m³/s of the maker's own printed air, with a 29.8 kW fan. The heat comes from outside the drawing, because that is what this machine is: heat rejection, and the plant that sends it the heat is the customer's. Given exactly the rejection BAC certify, the model solves the condensing temperature the machine settles at — which is the reading, and the only figure here that is ours rather than theirs. The rating condition is an inference and the listing says so: BAC's sheets never define the condition of their Base Heat Rejection. | HVAC Builder | Cooling tower / heat rejection | 2478–4130 kW | EU | Open in the builder |
| EVAPCO AT 214-4K14 cooling tower (430 tons, 1.9 MW) — modelled Example modelled from published data CTI STD-201 (validation C13A-99R28) ✓ EVAPCO's 214-4K14 — an AT cooling tower, 430 nominal tons (1888 kW): rated to cool 1293 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 1416–2360 kW | EU | Open in the builder |
| Baltimore Aircoil PFI-1012N-3D2ES-L1 closed-circuit cooler (121 tons, 530 kW) — modelled Example modelled from published data BAC's PFI-1012N-3D2ES-L1 — a PFi closed-circuit cooler, 121 nominal tons (530 kW): rated to cool 363 USGPM of process fluid from 95 to 85 °F at a 78 °F entering wet bulb on 30.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. The process fluid runs inside a coil under the spray — the evaporative wet-coil model, its two conductances split as the range's own coil volumes say. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving process fluid exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by Baltimore Aircoil. Published as an example; the figures below are solved from this model. | HVAC Builder | Cooling tower / heat rejection | 398–663 kW | EU | Open in the builder |