Published systems

Complete machines published by their suppliers — each with a public spec page whose design-point performance is solved live from the actual model, not copied from a brochure. Open one in the builder to run it against your own climate, or request a quote right here.

Suppliers 26Systems 3346Components 10248
All categoriesCooling tower / heat rejection 3307VRF / multi-split 8Air handler 7Plant / central 5Fan coil / terminal 4Condensing unit 3Rooftop / packaged 3Split system 3Chiller 2Heat recovery / DOAS 2Evaporative air cooler 1Unit cooler / refrigeration 1
All manufacturersBaltimore Aircoil 1900EVAPCO 1408Midea 2Gree 1Hitachi 1Samsung 1
All seriesAT 992ATWB 416PFi 359PCC 214Series 3000 189Series 1500 173Series V closed circuit 173Vertex VRC 157VCA 151Series V 122CXVB 118FXV 100PT2 46CXVT 40Series V EC 26FXT 20Nexus 12DVM S 1GMV5 1Set Free FSXN 1V4+ 1V6 1
Any capacity500 kW and up 3088100–500 kW 39125–100 kW 76up to 25 kW 25
Any certificationCTI STD-201 (validation C13A-99R28) 822CTI STD-201 (validation C13F-09R12) 416CTI STD-201 (validation C11F-92R20) 362CTI STD-201 (validation C11K-00R03) 153CTI STD-201 (validation C11J-98R12) 100CTI STD-201 (validation C11B-92R07) 90CTI STD-201 (validation C11L-07R05) 46CTI STD-201 (validation C11Q-18R02) 2
All marketsEU 3346
All tagsexample 3346
All suppliersHVAC Builder 3345Aeronim Systems (fictional) 1
SortNewestName A–ZSupplier A–ZCapacity ↑Capacity ↓

Showing 1921–1944 of 3346

EVAPCO AT 27-4I28 cooling tower (389 tons, 1.7 MW) — modelled

EVAPCO's 27-4I28 — a AT cooling tower, 389 nominal tons (1709 kW): rated to cool 1170 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 51.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1282–2136 kW · EU

EVAPCO AT 27-4I36 cooling tower (708 tons, 3.1 MW) — modelled

EVAPCO's 27-4I36 — a AT cooling tower, 708 nominal tons (3111 kW): rated to cool 2130 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 75.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2333–3888 kW · EU

EVAPCO AT 27-4J24 cooling tower (490 tons, 2.2 MW) — modelled

EVAPCO's 27-4J24 — a AT cooling tower, 490 nominal tons (2156 kW): rated to cool 1476 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 52.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1617–2695 kW · EU

EVAPCO AT 27-4J28 cooling tower (549 tons, 2.4 MW) — modelled

EVAPCO's 27-4J28 — a AT cooling tower, 549 nominal tons (2414 kW): rated to cool 1653 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 58.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1811–3018 kW · EU

EVAPCO AT 27-4J36 cooling tower (799 tons, 3.5 MW) — modelled

EVAPCO's 27-4J36 — a AT cooling tower, 799 nominal tons (3514 kW): rated to cool 2406 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 85.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2635–4392 kW · EU

EVAPCO AT 27-4K24 cooling tower (535 tons, 2.4 MW) — modelled

EVAPCO's 27-4K24 — a AT cooling tower, 535 nominal tons (2353 kW): rated to cool 1611 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 57.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1765–2941 kW · EU

EVAPCO AT 27-4K28 cooling tower (432 tons, 1.9 MW) — modelled

EVAPCO's 27-4K28 — a AT cooling tower, 432 nominal tons (1897 kW): rated to cool 1299 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 63.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1423–2371 kW · EU

EVAPCO AT 27-4K36 cooling tower (872 tons, 3.8 MW) — modelled

EVAPCO's 27-4K36 — a AT cooling tower, 872 nominal tons (3834 kW): rated to cool 2625 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 93.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2875–4792 kW · EU

EVAPCO AT 27-4L24 cooling tower (572 tons, 2.5 MW) — modelled

EVAPCO's 27-4L24 — a AT cooling tower, 572 nominal tons (2515 kW): rated to cool 1722 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 61.2 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1886–3144 kW · EU

EVAPCO AT 27-4L28 cooling tower (582 tons, 2.6 MW) — modelled

EVAPCO's 27-4L28 — a AT cooling tower, 582 nominal tons (2559 kW): rated to cool 1752 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 68.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1919–3198 kW · EU

EVAPCO AT 27-4M28 cooling tower (658 tons, 2.9 MW) — modelled

EVAPCO's 27-4M28 — a AT cooling tower, 658 nominal tons (2892 kW): rated to cool 1980 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 72.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 2169–3615 kW · EU

EVAPCO AT 28-2F17 cooling tower (216 tons, 951 kW) — modelled

EVAPCO's 28-2F17 — a AT cooling tower, 216 nominal tons (951 kW): rated to cool 651 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 25.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 713–1188 kW · EU

EVAPCO AT 28-2G17 cooling tower (273 tons, 1.2 MW) — modelled

EVAPCO's 28-2G17 — a AT cooling tower, 273 nominal tons (1200 kW): rated to cool 822 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.5 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 900–1501 kW · EU

EVAPCO AT 28-2H17 cooling tower (296 tons, 1.3 MW) — modelled

EVAPCO's 28-2H17 — a AT cooling tower, 296 nominal tons (1301 kW): rated to cool 891 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 976–1627 kW · EU

EVAPCO AT 28-2I17 cooling tower (318 tons, 1.4 MW) — modelled

EVAPCO's 28-2I17 — a AT cooling tower, 318 nominal tons (1398 kW): rated to cool 957 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 37.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1048–1747 kW · EU

EVAPCO AT 28-3F17 cooling tower (246 tons, 1.1 MW) — modelled

EVAPCO's 28-3F17 — a AT cooling tower, 246 nominal tons (1082 kW): rated to cool 741 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 24.8 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 812–1353 kW · EU

EVAPCO AT 28-3G17 cooling tower (303 tons, 1.3 MW) — modelled

EVAPCO's 28-3G17 — a AT cooling tower, 303 nominal tons (1332 kW): rated to cool 912 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 29.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 999–1665 kW · EU

EVAPCO AT 28-3H17 cooling tower (330 tons, 1.5 MW) — modelled

EVAPCO's 28-3H17 — a AT cooling tower, 330 nominal tons (1450 kW): rated to cool 993 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 33.1 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1088–1813 kW · EU

EVAPCO AT 28-3I17 cooling tower (357 tons, 1.6 MW) — modelled

EVAPCO's 28-3I17 — a AT cooling tower, 357 nominal tons (1569 kW): rated to cool 1074 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 36.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1176–1961 kW · EU

EVAPCO AT 28-3J17 cooling tower (392 tons, 1.7 MW) — modelled

EVAPCO's 28-3J17 — a AT cooling tower, 392 nominal tons (1722 kW): rated to cool 1179 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 41.3 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1291–2152 kW · EU

EVAPCO AT 28-4F17 cooling tower (266 tons, 1.2 MW) — modelled

EVAPCO's 28-4F17 — a AT cooling tower, 266 nominal tons (1170 kW): rated to cool 801 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 24.4 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 877–1462 kW · EU

EVAPCO AT 28-4G17 cooling tower (318 tons, 1.4 MW) — modelled

EVAPCO's 28-4G17 — a AT cooling tower, 318 nominal tons (1398 kW): rated to cool 957 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 28.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1048–1747 kW · EU

EVAPCO AT 28-4H17 cooling tower (345 tons, 1.5 MW) — modelled

EVAPCO's 28-4H17 — a AT cooling tower, 345 nominal tons (1516 kW): rated to cool 1038 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 32.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1137–1895 kW · EU

EVAPCO AT 28-4I17 cooling tower (372 tons, 1.6 MW) — modelled

EVAPCO's 28-4I17 — a AT cooling tower, 372 nominal tons (1634 kW): rated to cool 1119 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 35.7 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Examplemodelled from published dataCTI STD-201 (validation C13A-99R28) ✓
Cooling tower / heat rejection · 1226–2043 kW · EU
‹ Previous1…7980818283…140Next ›

Publishing here

Suppliers publish from the builder's supplier portal — free to register, free to publish. How it works for system suppliers